Plan Review Details - Permit 03120434
Plan Review Stops For Permit 03120434
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-01-26 Cont ID  
Sent By dpalmer Date 2004-02-05 Time 14:32 Rev Time 0.66
Received By alange Date 2004-01-26 Time 09:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-12-30 Cont ID  
Sent By pkrauss Date 2004-01-23 Time 09:45 Rev Time 1.30
Received By alange Date 2003-12-30 Time 14:46 Sent To  
Notes
2003-12-30 00:00:001.905.2.1 RESIDENTIAL SMOKE ALARMS:
 NFPA 72.A-8-1.2.1 IN FAMILY UNITS WITH
 MORE THAN ONE BEDROOM AREA OR WITH BED-
 ROOMS ON MORE THAN ONE FLOOR, MORE THAN
 ONE SMOKE DETECTOR IS REQUIRED.
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 3. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
 4.A SEPERATE ROOFING PERMIT IS
 REQUIRED.
 5. STORM PANEL PRODUCT APPROVALS NOT
 LISTED ON THE FBC APPROCAL SITE.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ART LANGE
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-02-05 Cont ID  
Sent By dpalmer Date 2004-02-05 Time 14:31 Rev Time 0.33
Received By dpalmer Date 2004-02-05 Time 14:31 Sent To B
Notes
2004-02-05 00:00:00SENT TO BLDG FOR PROCESSING.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-01-20 Cont ID  
Sent By kstevens Date 2004-01-29 Time 18:17 Rev Time 1.50
Received By dpalmer Date 2004-01-20 Time 13:49 Sent To P
Notes
2004-01-20 00:00:00************ UNSAT *****************
  
 1)NOTE: PLEASE SEE THAT THERE ARE SOME
 ITEMS THAT STILL NEED TO CORRELATE.
  
 2)NOTE: PLANS SHOW NEW PANEL "B" SCHED-
 -ULE, HOWEVER, DOES NOT CARRY OVER SOME
 OLD ITEMS. DRYER, WATER HEATER ETC.
  
 3)NOTE: PLEASE ALSO SEE THAT WASHER AND
 DRYER ARE NOW BEING SHOWN AS GFI?
  
 4)NOTE: PLEASE SEE 210.52D, 210.11C3,
 NO OTHER RECEPTS ARE PERMITTED TO BE ON
 BATH RECEPT CIRCUIT.
  
 5)NOTE: PLEASE SEE PLANS NOW SUBMITTED
 SHOW A NEW RISER DIAGRAM. PLANS NOW
 SHOW A NEW/ EXST MAIN DISC.
 PLANS SHOW EXIST METER AND MAIN PANEL
 OUTSIDE? IS THIS PANEL "A"? PLEASE LABEL
 SHOW ON PLANS.
  
 6)NOTE: MISSING EQUIPMENT GROUNDING
 CONDUCTORS BETWEEN MAIN DISC AND PANEL
 "A". 250.24,250.110,250.122
  
 7)NOTE: PLEASE SEE MIN LOADS REQ`D FOR
 WATER HEATER AND DRYER NOT SHOWN IN
 LOAD CALCS. 220.18 ETC
  
 8)NOTE: PLEASE VERIFY WATER HEATER SHOWN
 IN CLOSET. WATER HEATER NOT PERMITTED IN
 AREA W/OUT PERMENANT BARRIER. 422.17
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
 PLEASE REMOVE ALL OLD VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW/STAMPING.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-22 Cont ID  
Sent By csiegber Date 2004-01-12 Time 15:45 Rev Time 1.25
Received By dpalmer Date 2003-12-22 Time 10:04 Sent To P
Notes
2003-12-22 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM/
 PLANS AND PANEL SCHEDULES. THERE IS ONE
 SET HIGHLIGHTED WITH MANY ITEMS SHOWN.
  
 2)NOTE: PLEASE INCLUDE ALL MIN CIRCUIT-
 -ING ON PANEL SCHEDULES. PLEASE ALSO
 INCLUDE LOAD SHOWNS ON LOAD CALCULATIONS
 IE;SM APPL, WASHER ETC ETC. 210.11,
 220.16,220.18 ETC.
  
 3)NOTE: PLEASE SEE MISSING REQ'D ARC
 FAULT PROTECTION PER 220.12
  
 4)NOTE: PLEASE SEE MISSING BATH CIRCUIT
 PER 210.52D, 210.11C3 MIN #12 AND 20A.
  
 5)NOTE: PLEASE INCLUDE ALL CONDUCTOR
 SIZES ON RISER DIAGRAM AFTER CORRELATING
 PLANS.
  
 6)NOTE: PLEASE CLARIFY BRKR SHOWN TO
 "GARAGE" ? DETACHED?
  
 7)NOTE: PLEASE SEE 200A BRKR SHOWN AS
 AND 8-POLE AND 100A PANEL SHOWN W/ A
 3-POLE BRKR??
  
 8)NOTE: PLEASE SEE 210.8 FOR ALL RECEPTS
 IN GARAGE AS GFI.
  
 9)NOTE: PLEASE SEE MISSING SD REQ'D
 OUTSIDE BEDROOM.
  
 10)NOTE: PLEASE INCLUDE NEW FOOTER STEEL
 AS PART OF THE GROUNDING ELECTRODE
 SYSTEM. 250.50
  
 11)NOTE: THIS IS JUST A NOTE; IF THERE
 IS GOING TO BE ANY NEW LV(TV,PHONE,ETC)
 PLEASE SHOW ON PLANS. IF NOT SEPARATE
 PLANS WILL NEED TO COME BACK IN WHEN
 LV PERMIT IS APPLIED FOR.
  
 12)NOTE: PLEASE CLARIFY PANEL SHOWN
 STICKING OUT INTO DOORWAY? IS THIS
 MOVING? BEING RELOCATED?
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW AND MAKE ALL CORRECTIONS.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-01-28 Cont ID  
Sent By csiegber Date 2004-01-28 Time 14:33 Rev Time 0.00
Received By csiegber Date 2004-01-28 Time 14:33 Sent To P
Notes
2004-01-28 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-01-12 Cont ID  
Sent By csiegber Date 2004-01-12 Time 15:45 Rev Time 0.00
Received By csiegber Date 2004-01-12 Time 15:45 Sent To E
Notes
2004-01-12 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-12-12 Cont ID  
Sent By csiegber Date 2003-12-12 Time 09:30 Rev Time 0.00
Received By csiegber Date 2003-12-12 Time 09:30 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-08 Cont ID  
Sent By mmclean Date 2003-12-11 Time 16:56 Rev Time 0.00
Received By csiegber Date 2003-12-08 Time 14:21 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2004-01-23 Cont ID  
Sent By pkrauss Date 2004-01-23 Time 09:41 Rev Time 0.33
Received By pkrauss Date 2004-01-23 Time 09:40 Sent To B
Notes
2004-01-23 00:00:00PLAN SHEET A06 OF 6 INDICATES A/C
 CONTRACTOR TO PROVIDE DUCT LAYOUT WITH
 CEILING RETURN WITH MECHANICAL PERMIT
 APPLICATION. FORM 600C SUBMITTED WITH
 THE BUILDING PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2003-12-30 Cont ID  
Sent By kstevens Date 2004-01-21 Time 12:52 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-12-29 Cont ID  
Sent By kstevens Date 2003-12-29 Time 13:08 Rev Time 0.33
Received By pkrauss Date 2003-12-29 Time 14:53 Sent To B
Notes
2003-12-29 00:00:00DENIED:
 PLEASE INDICATE VENTING REQUIREMENTS FOR
 THE GAS DRYER INDICATED ON PLAN SHEET 6
 OF 6.PROVIDE INFORMATION ON COMBUSTION
 AIR REQUIREMENTS AS DEFINED IN 2001 FBC
 (M) 702.
  
 A/C NOTES ON PLAN SHEET 6 OF 6 INDICATE
 A/C CONTRACTOR TO SUBMIT PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-01-29 Cont ID  
Sent By kstevens Date 2004-01-29 Time 18:17 Rev Time 0.33
Received By kstevens Date 2004-01-29 Time 18:17 Sent To E
Notes
2004-01-29 00:00:00SEPARATE GAS PERMIT REQUIRED

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-01-21 Cont ID  
Sent By csiegber Date 2004-01-28 Time 14:33 Rev Time 0.33
Received By kstevens Date 2004-01-21 Time 12:51 Sent To M
Notes
2004-01-21 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1) TWO OR MORE COPIES OF DRAWINGS SHALL
 BE SUBMITTED. REMOVE OLD VOIDED SHEETS
 AND INSERT NEW REVISED SHEETS FOR REVIEW
 SECTION 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-12-29 Cont ID  
Sent By dpalmer Date 2004-01-20 Time 15:31 Rev Time 1.00
Received By kstevens Date 2003-12-29 Time 13:07 Sent To M
Notes
2003-12-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) SANITARY RISER DIAGRAM AND FLOOR PLAN
 DOES NOT MEET CODE REQUIREMENTS. SECTION
 909.1. ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUP SHALL CONNECT TO THE WET-
 VENTED HORIZONTAL BRANCH DRAIN, ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE DOWN
 STREAM OF THE WET VENT. THE WASHMACHINE
 SHALL CONNECT DOWNSTREAM OF BATHROOM
 FIXTURES.
 2) SEPARATE GAS AND PLUMBING PERMITS ARE
 REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-11 Cont ID  
Sent By csiegber Date 2003-12-08 Time 14:21 Rev Time 0.00
Received By mmclean Date 2003-12-11 Time 16:56 Sent To I
Notes
***NONE***