Plan Review Details - Permit 03120403
Plan Review Stops For Permit 03120403
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-02-24 Cont ID  
Sent By rbrown Date 2004-02-24 Time 16:50 Rev Time 0.00
Received By rbrown Date 2004-02-24 Time 16:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-02-04 Cont ID  
Sent By rbrown Date 2004-02-24 Time 09:02 Rev Time 0.00
Received By rbrown Date 2004-02-04 Time 16:13 Sent To  
Notes
2004-02-04 00:00:001) THE CONSTRUCTION/DEMOLITION SITE
 SHALL NOT BE ACCESSIBLE TO OCCUPANTS OF
 THE EXISTING OCCUPIED BUILDING OR THE
 GENERAL PUBLIC.PROVIDE SECURE BARRIERS
  
 2) EGRESS FROM THE PARKING GARAGE AND
 EXISTING EAST TOWER SHALL BE MAINTAINED
 AND UNOBSTRUCTED AT ALL TIMES.
  
 3) THE UNFINISHED WEST TOWER SHOWS SIGNS
 OF REPEATED WATER INGRESS.SUBMIT
 PROPOSALS FOR MOLD AND MILDEW
 INVESTIGATION/MITIGATION.
  
 4) DURING PRE-INSPECTION NO PARKING
 GARAGE VENTILATION WAS OPERATIONAL.A
 WRITTEN COMMITMENT TO CORRECT THIS IS
 IS REQUIRED FROM THE DEVELOPER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-12-09 Cont ID  
Sent By csiegber Date 2003-12-08 Time 16:21 Rev Time 0.50
Received By shill Date 2003-12-09 Time 15:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2004-02-24 Cont ID  
Sent By dpalmer Date 2004-02-24 Time 15:19 Rev Time 0.50
Received By dpalmer Date 2004-02-24 Time 15:19 Sent To  
Notes
2004-02-24 00:00:00ELECTRICAL TO BE APPLIED FOR UNDER
 SEPARATE PERMIT.
 POMEROY ELECTRIC TO SUBMIT FOR PERMIT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-02-05 Cont ID  
Sent By dpalmer Date 2004-02-05 Time 08:42 Rev Time 1.00
Received By dpalmer Date 2004-02-05 Time 08:41 Sent To  
Notes
2004-02-05 00:00:00**************** UNSAT **********
 ********* NEED INFO ******************
  
 1)NOTE: PLEASE PROVIDE LAYOUT FOR
 ELECTRICAL WORK TO BE PERFORMED.
  
 2)NOTE: UPON FIELD EVALUATION INSPECTION
 OF SITE. DEMO WORK HAS ALREADY COMMENCED
 AND NUMEROUS LOCATIONS OF WIRING AND
 WIRING DEVICES ARE EXPOSED AND MUST
 BE "SAFED" OFF. PLEASE SECURE MAIN
 ELECTRICAL ROOM AND LOCK ALL ELECTRICAL
 EQUIPMENT AS REQ'D UNDER NEC. 110.27
 ETC.
  
 3)NOTE: PLEASE PROVIDE LAYOUT FOR NEW
 TEMPORARY LIGHTING TO BE INSTALLED.
 PER ART 527 OF THE 2002 NEC.
 THE TEMPORARY WIRING OF LTS ON SITE
 ALSO DONE W/OUT PERMITS; DO NOT MEET
 REQUIREMENTS OF NEC.
  
 4)NOTE: AREA ON PLANS THAT CALL TO HAVE
 WALLS DEMOLISHED SEEM TO HAVE ELECTRICAL
 EQUIPMENT ATTACHED. PLEASE PROVIDE
 INFORMATION ON THIS AND/OR REMOVE FROM
 SCOPE OF WORK.
  
 5)NOTE: PLEASE NOTE: FROM THE ON-SITE
 INSPECTION WEST AREA OF PARKING GARAGE
 DIRECTLY BELOW UNFINISHED WEST TOWER.
 A SUBSTANTIAL WATER LEAK HAS CORRODED
 AND RUSTED SOME FEEDERS CONDUITS EXPOSE-
 ING FEEDERS. THIS MUST BE REPAIRED ASAP
 (30DAYS).
  
 PLEASE HAVE AN ELECTRICAL CONTRACTOR
 APPLY FOR PERMIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-02-24 Cont ID  
Sent By mcarsill Date 2004-02-24 Time 14:51 Rev Time 0.00
Received By mcarsill Date 2004-02-24 Time 14:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-01-30 Cont ID  
Sent By mcarsill Date 2004-01-30 Time 16:14 Rev Time 0.00
Received By mcarsill Date 2004-01-30 Time 16:13 Sent To  
Notes
2004-01-30 00:00:001) DEMOLITION, RENOVATION, AND
 CONSTRUCTION SHALL COMPLY WITH
 NFPA 241.
  
 2) ALL EXISTING EXITS SHALL REMAIN
 CLEAR AND UNOBSTRUCTED FOR THE
 EXISTING BUILDING. CLARIFY THE REMOVAL
 OF EXISTING STAIR ON PAGE A-2.1.D.
  
 3) ALL ELECTRICAL LIFE SAFETY SYSTEMS
 AND FIRE SPRINKLER SYSTEMS FOR THE
 EXISTING BUILDING SHALL REMAIN IN
 FULL EFFECT.
  
 4) THE EXISTING FIRE ALARM SYSTEM
 SHALL REMAIN IN OPERATION AT ALL
 TIMES FOR THE EXISTING BUILDING.
  
 5) PROPER SEPARATION IS REQUIRED
 BETWEEN NEW AND EXISTING CONSTRUCTION.
  
 6) A PRE-INSPECTION IS REQUIRED
 WITH FIRE RESCUE PRIOR TO
 DEMOLITION.
  
 7) DEBRIS IS TO REMOVED FROM THE
 SITE DAILY.
  
 8) DEMOLITION OF ANY MECHANICAL,
 ELECTRICAL, FIRE SPRINKLER, OR
 PLUMBING EQUIPMENT SHALL NOT BE
 REMOVED UNTIL FULLY INVESTIGATED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-24 Cont ID  
Sent By rbrown Date 2004-02-24 Time 09:03 Rev Time 0.00
Received By rbrown Date 2004-02-24 Time 09:01 Sent To  
Notes
2004-02-24 00:00:00TO COMMERCIAL BOARD #26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-05 Cont ID  
Sent By csiegber Date 2003-12-08 Time 16:21 Rev Time 0.00
Received By rbrown Date 2003-12-08 Time 16:21 Sent To B
Notes
2003-12-08 00:00:00TO SH DESK/PER LM