Plan Review Details - Permit 03120391
Plan Review Stops For Permit 03120391
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status N Date 2004-07-15 Cont ID  
Sent By rmcdouga Date 2004-07-15 Time 09:25 Rev Time 1.00
Received By rmcdouga Date 2004-07-15 Time 09:25 Sent To  
Notes
2004-11-04 00:00:00CHANGE STATUS TO "N" PER ROBERT
 MCDOUGAL. 11/04/2004
2004-07-15 00:00:00LETTER SUBMITTED FROM ENGINEER IS NOT
 ACCEPTABLE AT THIS TIME. THE PROVISO
 REQUIRES THE FRONT DOOR TO HAVE A
 SEPARATE PERMIT. ADDITIONAL FEES AND
 PRODUCT APPROVALS ARE REQUIRED. OUR
 RECORDS INDICATE THAT NO PERMIT HAS BEEN
 ISSUED FOR THE FRONT DOOR. REFERENCE THE
 PERMIT NUMBER FOR THE STRUCTURE ON THE
 APPLICATION FOR THE DOOR PERMIT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-02-13 Cont ID  
Sent By csiegber Date 2004-07-14 Time 15:30 Rev Time 3.00
Received By rmcdouga Date 2004-02-13 Time 15:12 Sent To  
Notes
2004-02-13 00:00:00BUILDING PROVISO
  
 SUBMIT PRODUCT APPROVALS FOR ENTRY DOOR
 UNDER A SEPARATE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-02-05 Cont ID  
Sent By jleech Date 2004-02-13 Time 08:42 Rev Time 3.00
Received By rmcdouga Date 2004-02-05 Time 10:17 Sent To  
Notes
2004-02-05 00:00:00DENIED
  
 1) BUCK FASTENING DETAILS ON A-7 FOR
 ENTRY DOOR SPECIFIES 1X4 PT BUCK AND
 STATES THAT FRAME WILL BE ATTACHED TO
 BUCK WITH SCREWS WITH 3/4" EMBEDMENT
 INTO THE BUCK. FBC 1707.4.4.2 REQUIRES
 THE FRAME TO BE FASTENED THROUGH THE
 BUCK INTO THE STRUCTURAL SUBSTRATE.
 PLEASE CORRECT. ITEM #8
  
 2) THE PRODUCT APPROVAL FOR THE DOUBLE
 ELLIPTICAL TOP ENTRY DOORS SUBMITTED,
 DOES NOT COMPLY WITH RULE 9B-72. SEE
 RULE AND SUBMIT ALL REQUIRED PAPERWORK.
 DRAWINGS MUST MATCH DOORS, QUALITY
 ASSURANCE IS REQUIRED, ETC. ITEM #10
  
 3) TWO COPIES OF THE STATE PRODUCT
 APPROVAL COVER SHEETS IS REQUIRED.
 ITEM #9
  
 4) FLOOR PLANS AND ELEVATIONS DO NOT
 INDICATE THAT ELLIPTICAL TOPS OF FRENCH
 DOOR AND CASEMENT WINDOWS HAS BEEN
 ELIMINATED. ITEM #11
  
 5) PRODUCT APPROVAL FOR THE SINGLE SWING
 DOOR AT THE GARAGE IS FOR A DOUBLE DOOR
 THAT REQUIRES IMPACT PROTECTION. SUBMIT
 APPROPRIATE PRODUCT APPROVALS. ITEM #14
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-13 Cont ID  
Sent By jleech Date 2004-02-03 Time 08:54 Rev Time 3.00
Received By rmcdouga Date 2004-01-13 Time 14:36 Sent To  
Notes
2004-01-13 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A SEPARATE PERMIT IS REQUIRED FOR THE
 POOL.
  
 3) SUBMIT 2 COPIES OF A RECENT SURVEY.
  
 4) FBC TABLE 1604.1 REQUIRES A LIVE LOAD
 OF 10 PSF FOR ATTICS WITHOUT STORAGE AND
 30 PSF FOR ATTICS WITH STORAGE. PLEASE
 NOTE THIS ON THE PLANS FOR THE BOTTOM
 CORD LIVE LOAD OF THE TRUSSES.
  
 5) SUBMIT SPECIFICATIONS FROM WINDOW
 MANUFACTURER INDICATING THE CLEAR
 OPENING SIZES OF THE CASEMENT WINDOWS IN
 THE SLEEPING ROOMS FOR DETERMINING
 COMPLIANCE WITH FBC 1005.4 FOR EMERGENCY
 EGRESS.
  
 6) SUBMIT MANUFACTURER,S SPECIFICATIONS
 AND LISTING INFORMATION FOR THE PREFAB
 FIREPLACE AND FLUE PIPE.
  
 7) THE CITY OF WPB AMENDMENTS TO FBC
 TABLE 2306.1 REQUIRES THE ROOF SHEATHING
 TO BE NAILED 4"OC AT EDGES AND 6"OC IN
 ZONE 3 WHICH INCLUDES THE OUTSIDE
 CORNERS OF HIP ROOFS. SEE FBC FIGURE
 1606.2(C). PLEASE REVISE THE NOTES ON
 A6, S2 AND S3.
  
 8) FBC 1707.4.4.2 REQUIRES DOOR FRAMES
 TO BE ATTACHED THROUGH THE BUCK AND INTO
 THE STRUCTURAL SUBSTRATE WHEN THE BUCK
 IS LESS THAN 1-1/2". PLEASE REVISE THE
 DOOR BUCK DETAIL ON A7. NOTE THE PRODUCT
 APPROVALS FOR THE PELLA DOORS REQUIRE
 2X BUCKS.
  
 9)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10) SUBMIT PRODUCT APPROVALS FOR DOUBLE
 OUTSWING ELLIPTICAL TOP WOOD DOORS WITH
 SIDELITES FOR THE FRONT ENTRY DOORS AS
 SHOWN ON THE PLANS.
  
 11) SUBMIT PRODUCT APPROVALS FOR THE
 ELLIPTICAL TOP GLAZED FRENCH DOORS AND
 THE ELLIPTICAL TOP VENTED CASEMENT
 WINDOWS AS SHOWN ON THE PLANS.
  
 12) CLARIFY WHY THE DRAWINGS FOR THE
 NON-IMPACT OPERABLE CASEMENT WINDOWS
 WAS SUBMITTED. (DRAWING #1161)
  
 13) SUBMIT PRODUCT APPROVALS FOR THE
 GLASS BLOCK.
  
 14) SUBMIT PRODUCT APPROVALS FOR THE
 SINGLE OUTSWING SOLID GARAGE DOOR.
  
 15) SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS INDICATING
 HOW AND WHERE THEY WILL BE INSTALLED.
 NOTE: GLASS BLOCK COMPLYING WITH FBC
 SECTION 2112 DO NOT HAVE TO BE PROTECTED
  
 16) SPECIFY THE UPLIFT CAPACITIES AND
 THE WELD TYPES FOR THE STEEL COLUMNS ON
 S3.
  
 17) ON SHEET S4 PLEASE CHANGE THE
 REFERENCES FROM SBC TO FBC AND CORRECT
 THE MEAN ROOF HEIGHT TO CONCUR WITH THE
 ONE LISTED ON A1.
  
 18)1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
 PLEASE REVISE THE VALUES IN THE TRUSS
 ANCHOR SCHEDULE & UPDATE THE CONNECTORS
 TO THOSE IN CURRENT CATALOGS WITH STATE
 PRODUCT APPROVAL.
  
 19) SUBMIT STATE PRODUCT APPROVAL FOR
 TRUSS CONNECTORS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-07-14 Cont ID  
Sent By dpalmer Date 2004-07-14 Time 17:40 Rev Time 0.33
Received By dpalmer Date 2004-07-14 Time 17:40 Sent To  
Notes
2004-07-14 00:00:00*** NOTE***
  
 NOTE # 9 REMOVED PER CONVERSATION WITH
 CONSULTING ENGINEER AND ARCHITECT ON
 PREVIOUS CONVERSATIONS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-06-11 Cont ID  
Sent By csiegber Date 2004-07-14 Time 15:28 Rev Time 1.50
Received By dpalmer Date 2004-06-11 Time 11:55 Sent To  
Notes
2004-06-11 00:00:00*********** UNSAT ****************
  
 PLEASE SEE SOME COMMENTS FROM PREVIOUS
 REVIEW HAS NOT BEEN ADDRESS.
  
 1)NOTE: NOTE #1 OK
  
 2)NOTE: NOTE #2 OK
  
 3)NOTE: NOTE #3 PLEASE SEE LICENSE #'S
 HAVE NOW BEEN ADDED TO TITLE BLOCK BUT
 DO NOT CORRELATE WITH DBPR FOR CORRECT
 #'S. PER CONVERSATION WITH DBPR/ ONE
 COPY IS TO BE SENT OFF TO STATE FOR
 REVIEW.
  
 4)NOTE: NOTE #4 NO PLEASE SEE PLANS,
 210.52C1
  
 5)NOTE: NOTE #5 OK
  
 6)NOTE: NOTE #6 OK, NOTED ON PLANS.
  
 7)NOTE: NOTE #7 NO. PLEASE ALSO SEE
 PLANS NOW CONTAIN TWO DIFFERENT SET OF
 LOAD CALCULATIONS. PLEASE REMOVE OLD
 AND REVISE NEW.
 PLEASE ALSO SEE LOAD CALCULATIONS DO NOT
 INDICATE LOADS FOR SPA TUB/ HEAT AS
 NOTED ON PLANS?
 215.5/220
  
 8)NOTE: PLEASE SEE NOTE # 9 ON ELECT-
 -RICAL GENERAL NOTES, MENTIONS ALL WIRE
 TO BE #12. PANEL SCHEDULE INDICATES
 #14
  
 THIS IS ONLY GIVEN AS A NOTICE.
 PLEASE SEE FS 553.80(2)(B) ATTACHED.
 PLEASE ADDRESS ALL COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-05-20 Cont ID  
Sent By csiegber Date 2004-06-07 Time 11:26 Rev Time 0.50
Received By dpalmer Date 2004-05-20 Time 15:59 Sent To  
Notes
2004-05-20 00:00:00*********** UNSAT *******************
  
 1)NOTE: PLEASE REMOVE EQUIPMENT GROUND-
 -ING CONDUCTOR BETWEEN METER AND MAIN
 DISCONNECT. NOT PERMITTED. 250.6,250.24
  
 2)NOTE: PLEASE INCLUDE FOOTER STEEL AS
 PART OF THE GRND ELEC SYSTEM. PER 250.50
  
 3)NOTE: PLEASE SEE MISSING LICENSE #
 ON TITLE BLOCK PER 61G1-16.004 AND FS
 481.219
  
 4)NOTE: PLEASE SEE 210.52C1 FOR KITCHEN
 COUNTERSPACE RECEPTS.
  
 5 NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 6)NOTE: PLEASE LIST THE REQ'D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULE.
 PER 210.12 2002 NEC.
 PLANS SHOW AFB FOR RECEPTS, REQ'D FOR
 SD'S , FANS, LTS ETC IN BEDRMS.
  
 7)NOTE: PLEASE SHOW LOAD CALCUALTIONS
 PER NEC 220.
 PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-12-22 Cont ID  
Sent By csiegber Date 2004-05-17 Time 12:26 Rev Time 0.75
Received By dpalmer Date 2003-12-22 Time 16:43 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-07-14 Cont ID  
Sent By csiegber Date 2004-07-14 Time 15:30 Rev Time 0.00
Received By csiegber Date 2004-07-14 Time 15:29 Sent To B
Notes
2004-07-14 00:00:00TO RM DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-07-14 Cont ID  
Sent By csiegber Date 2004-07-14 Time 15:28 Rev Time 0.00
Received By csiegber Date 2004-07-14 Time 15:28 Sent To E
Notes
2004-07-14 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-06-07 Cont ID  
Sent By csiegber Date 2004-06-07 Time 11:26 Rev Time 0.00
Received By csiegber Date 2004-06-07 Time 11:26 Sent To E
Notes
2004-06-07 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-05-17 Cont ID  
Sent By csiegber Date 2004-05-17 Time 12:26 Rev Time 0.00
Received By csiegber Date 2004-05-17 Time 12:26 Sent To E
Notes
2004-05-17 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-05-11 Cont ID  
Sent By csiegber Date 2004-05-11 Time 11:39 Rev Time 0.00
Received By csiegber Date 2004-05-11 Time 11:39 Sent To M
Notes
2004-05-11 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-18 Cont ID  
Sent By csiegber Date 2004-02-18 Time 10:13 Rev Time 0.00
Received By csiegber Date 2004-02-18 Time 10:13 Sent To P
Notes
2004-02-18 00:00:00TO JL DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-09 Cont ID  
Sent By csiegber Date 2004-02-09 Time 16:28 Rev Time 0.00
Received By csiegber Date 2004-02-09 Time 16:28 Sent To P
Notes
2004-02-09 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-30 Cont ID  
Sent By csiegber Date 2004-01-30 Time 15:55 Rev Time 0.00
Received By csiegber Date 2004-01-30 Time 15:55 Sent To P
Notes
2004-01-30 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-13 Cont ID  
Sent By mmclean Date 2003-12-09 Time 15:59 Rev Time 0.00
Received By csiegber Date 2003-12-05 Time 15:44 Sent To  
Notes
2003-12-10 00:00:00TO SFD RACK/E
2003-12-05 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-05-24 Cont ID  
Sent By hmoser Date 2004-05-24 Time 11:37 Rev Time 0.50
Received By hmoser Date 2004-05-24 Time 11:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-12-30 Cont ID  
Sent By csiegber Date 2004-05-11 Time 11:39 Rev Time 0.50
Received By hmoser Date 2003-12-30 Time 18:18 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-02-18 Cont ID  
Sent By jleech Date 2004-02-18 Time 10:19 Rev Time 0.33
Received By jleech Date 2004-02-18 Time 10:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-02-13 Cont ID  
Sent By csiegber Date 2004-02-18 Time 10:13 Rev Time 0.50
Received By jleech Date 2004-02-13 Time 08:42 Sent To B
Notes
2004-02-13 00:00:00DENIED;
 COMENTS FROM FIRST REVIEW WERE NOT
 ADDRESSED.
 W/M, L/T, AND DRIP DRY SHOWER CAN NOT
 BE PART OF BATHROOM #2. A SECOND BRANCH
 DRAIN IS REQUIRED. SEE FBC PLUMBING SEC.
 909.1. ALSO MAKE NOTE ON PLAN, TRAP FOR
 DRIP-DRY SHOWER TO BE A DEEP SEAL TRAP.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-02-03 Cont ID  
Sent By csiegber Date 2004-02-09 Time 16:28 Rev Time 0.50
Received By jleech Date 2004-02-03 Time 08:53 Sent To B
Notes
2004-02-03 00:00:00DENIED;
 PLUMBING PAGE WAS NOT WITH THE NEW SET
 OF PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-12-10 Cont ID  
Sent By csiegber Date 2004-01-30 Time 15:55 Rev Time 0.50
Received By jleech Date 2003-12-10 Time 18:41 Sent To E
Notes
2003-12-10 00:00:00DENIED;
 W/M, L/T ANDDRIP DRY SHOWER CAN NOT BE
 PART OF BATHROOM 2. A SECOND BRANCH
 DRAIN IS REQUIRED. SEE FBC PLUMBING SEC
 909.1
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-09 Cont ID  
Sent By mmclean Date 2003-12-09 Time 15:59 Rev Time 0.00
Received By mmclean Date 2003-12-09 Time 15:59 Sent To I
Notes
***NONE***