Plan Review Details - Permit 03120348
Plan Review Stops For Permit 03120348
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2003-12-23 Cont ID  
Sent By nmccray Date 2003-12-23 Time 11:03 Rev Time 0.00
Received By nmccray Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-01-20 Cont ID  
Sent By nmccray Date 2004-01-20 Time 10:47 Rev Time 0.00
Received By nmccray Date 2004-01-20 Time 10:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-12-23 Cont ID  
Sent By csiegber Date 2004-01-14 Time 16:31 Rev Time 0.00
Received By nmccray Date 2003-12-23 Time 11:03 Sent To  
Notes
2003-12-23 00:00:00**************DENIED********************
 FLOW DATA CALCULATION FOR THE SAFETY
 MARGIN IS 2.194 WEST PALM BEACH REQUIRES
 A SAFETY MARGIN 5 PSI MINIMUM.
  
 ALSO THE FIRST SPRINKLER CONTRACTOR AND
 THIS OFFICE REVIEWED PROJECT AND THERE
 WERE SPRINKLER COVERAGE PROBLEMS
 REGARDING LIGHT FIXTURES, RAFTERS AND
 BEAMS.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-14 Cont ID  
Sent By csiegber Date 2004-01-14 Time 16:31 Rev Time 0.00
Received By csiegber Date 2004-01-14 Time 16:31 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-05 Cont ID  
Sent By csiegber Date 2003-12-05 Time 13:19 Rev Time 0.00
Received By csiegber Date 2003-12-05 Time 13:19 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-12-23 Cont ID  
Sent By nmccray Date 2003-12-23 Time 11:19 Rev Time 0.00
Received By nmccray Date   Time   Sent To  
Notes
***NONE***