Plan Review Details - Permit 03120302
Plan Review Stops For Permit 03120302
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-12-19 Cont ID  
Sent By kstevens Date 2003-12-17 Time 18:07 Rev Time 1.00
Received By lsmith Date 2003-12-19 Time 10:21 Sent To  
Notes
2003-12-19 00:00:00BUILDING FAILED:
  
 1. PLANS DRAWN BY ENGINEER MUST BE
 SIGNED & SEALED PER STATE STATUTE.
  
 2. NEED MORE INFORMATION ON SWIM SPA.
 SEE FBC CHAPTER 424 "RESIDENTIAL POOL"
  
 3. NEED DESIGN CERTIFICATION FOR ROOF
 TO MEET 140 MPH.
  
 4. PATIO NOT SHOWN ON PLANS, SUBMIT
 DRAWINGS SHOWING DECK & FOOTER IF
 REQUIRED BY CODE
  
 5. PERMIT APPLICATION SAYS SCREEN &
 ROOF& PATIO BY OTHERS.PLEASE CLARIFY.
  
 6. SUBMIT DRAWINGS FOR SCREEN ENCLOSURE
 INCLUDING ENGINEERING TO MEET FBC 2001
  
 7. CLARIFY SIZE OF SCREEN ENCLOSURE.
 APPLICATION SAYS 13' COVERED PORCH &
 PATIO IS 26 X 40.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINEER
 805-6713

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-16 Cont ID  
Sent By csiegber Date 2003-12-11 Time 14:30 Rev Time 0.50
Received By dpalmer Date 2003-12-16 Time 07:14 Sent To P
Notes
2003-12-16 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE HAVE PLANS SIGNED, DATED
 AND SEALED BY THE ENGINEER OF RECORD.
 PER FS 471.025
 PLEASE PROVIDE ALL LICENSE #S ON TITLE
 BLOCK. PLEASE SEE FAC CODE AND FS.
 61G15-23.002 AND 471.025
  
 2)NOTE: PLEASE SEE THAT THERE IS NOT
 ENOUGH INFORMATION FOR REVIEW OF PROPOS-
 -ED NEW INGROUND SPA/SWIM UNIT?
 NO LOAD, NO WIRING DIAGRAM, NO LOAD CALC
 AND OCP FROM EXISTING PANEL??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-12-11 Cont ID  
Sent By csiegber Date 2003-12-11 Time 14:30 Rev Time 0.00
Received By csiegber Date 2003-12-11 Time 14:30 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-04 Cont ID  
Sent By mmclean Date 2003-12-11 Time 09:27 Rev Time 0.00
Received By csiegber Date 2003-12-04 Time 14:52 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-12-17 Cont ID  
Sent By dpalmer Date 2003-12-16 Time 07:16 Rev Time 0.33
Received By kstevens Date 2003-12-17 Time 18:07 Sent To B
Notes
2003-12-17 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FLA. ADMIN. CODE
 FLA. STATUTES
  
 A) FOLLOWING INFORMATION REQUIRED FOR
 POOL PLANS AND PLAN REVIEW:
 B) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) COMPLY WITH FBC-2001 SEC 424.2
 PRIVATE SWIMMING POOLS.
 2) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-5. (ADD TO NOTES)
 3) FBC-2001 SEC 424.2.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. (DETAIL)
 4) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES)
 5) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL)
 6) FBC-2001424.2.6.6.4 MINIMUM OF TWO
 SUCTION INLETS SHALL BE PROVIDED FOR EA
 PUMP. SEPARATED BY A MINIMUM OF 3 FEET
 OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL)
 7) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER.
 8) FBC-2001424.2.7.1 POOL CIRCULATING
 PUMPS SHALL BE EQUIPPED ON THE INLET
 SIDE WITH AN APPROVED TYPE HAIR AND LINT
 STRAINER WHEN USED WITH A PRESSURE FIL-
 TER. (DETAIL OR ADD TO NOTES)
 9) FBC-2001 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 10) FBC-2001 424.2.8.1 VALVES SHALL BE
 MADE OF MATERIALS THAT ARE APPROVED IN
 THE FLA BLDG CODE, PLUMBING. THEY WILL
 BE READILY ACCESSIBLE FOR MAINT. AND RE-
 MOVAL. SEC 424.2.8.2 FULL WAY VALVES
 SHALL BE INSTALLED TO INSURE PROPER FUN-
 CTION OF THE FILTRATION AND PIPING SYS-
 TEM. SEC 424.2.8.3 WHERE CHECK VALVES
 ARE INSTALLED THEY SHALL BE OF THE SWING
 OR VERTICAL CHECK PATTERNS. SEC 424.2.8.
 4 COMBINATION VALVES SHALL REQUIRE APP-
 ROVAL OF THE ADMINISTRATIVE AUTHORITY
 PRIOR TO THEIR INSTALLATION.
 11) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 12) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 13) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 ******IF A POOL HEATER IS INSTALLED*****
 14) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 15) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 16) FBC-2001 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
 17) FBC02001 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT REQUIRED.
 18) SUBMIT A POOL LAYOUT WITH DRAINS,
 RETURNS, SKIMMERS, VENTS, VACUUM (IF
 APPLICABLE), PIPING WITH PIPE SIZE FROM
 FITTINGS TO POOL EQUIPMENT PAD, ECT.
 19) SUBMIT A PIPING SCHEMATIC FOR POOL
 EQUIPMENT SHOWING ALL POOL EQUIPMENT,
 PUMP, FILTER, HEATER (WITH BYPASS),
 VALVES (AS REQUIRED), LINES FROM MAIN
 DRAINS, SKIMMER, INLETS, VAC LINE ECT.
 20) SUBMIT A POOL SPECIFICATION LIST
 SHOWING POOL SIZE, POOL DEPTH, PERIMETER
 VOLUME (GALLONS), SURFACE AREA SQ. FT.,
 TURNOVER TIME, PUMP SIZE HP, POOL FILTER
 NUMBER OF INLETS, SKIMMER #, POOL HEATER
 VACUUM LINE, CHLORINE DISPERSER ECT.
 21) SUBMIT A DETAIL FOR HYDROSTATIC
 RELIEF PER 424.2.21.4
 22) INDICATE HOW THE WASTE WATER WILL BE
 DISPOSED PER 424.2.10
 23) WATER VELOCITY SHALL NOT EXCEED 10
 FEET PER SECOND. 424.2.6.3.
 24) MORE COMMENTS MAY BE REQUIRED BASED
 ON INFORMATION SUBMITTED FOR NEXT REVIEW
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2003-12-11 Cont ID  
Sent By csiegber Date 2003-12-04 Time 14:52 Rev Time 0.00
Received By mmclean Date 2003-12-11 Time 09:27 Sent To I
Notes
2003-12-11 00:00:00DENIED, NEED TO GIVE SETBACKS ON SURVEY
 FOR POOL & DECK LEFT MSG ON VOICE MAIL M