Plan Review Details - Permit 03120255
Plan Review Stops For Permit 03120255
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-03-10 Cont ID  
Sent By jwitmer Date 2004-03-10 Time 13:21 Rev Time 1.00
Received By jwitmer Date 2004-03-10 Time 13:21 Sent To  
Notes
2004-03-10 00:00:00BUILDINGPROVISO
 03120255
 4065 N HAVERHILL
 CHINA STAR RESTRAUNT
  
 FIRE SPRINKLERED BUILDINGS!!!!!!!!!
 2603.5.1.2(4) WHERE THE COOLER OR
 FREEZER IS WITHIN A FIRE SPRINKLERED
 BUILDING, BOTH THE COOLER AND FREEZER
 AND PART OF THE BUILDING IN WHICH IT IS
 LOCATED SHALL BE SPRINKLERED.
 A SEPERATE PERMIT WITH PLANS SHALL BE
 REQUIRED BEFORE A CERTIFICATE OF
 OCCUPANCY SHALL BE ISSUED.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-15 Cont ID  
Sent By jwitmer Date 2004-01-15 Time 16:12 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2004-01-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03120255
 ADD: 4065 N HAVERHILL
 CONT: QUALITY MAINENCE
 TEL: (321)432-5666
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 BUILDING
 1SR REVIEW
  
 ACTION: DENIED
  
 1) COMMENT# 2 FROM FIRE DEPARTMENT TO BE
 VARIFIED. FIRE SPRINKLERED BUILDINGS
 THAT CONTAIN WALK IN COOLERS ALSO RE-
 QUIRE FIRE SPRINKLERS.
 2603.5.1.2(4) WHERE THE COOLER OR
 FREEZER IS WITHIN A BUILDING, BOTH THE
 COOLER AND FREEZER AND PART OF THE BUILD
 ING IN WHICH IT IS LOCATED SHALL BE
 SPRINKLERED.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2004-05-10 Cont ID  
Sent By dpalmer Date 2004-05-10 Time 08:57 Rev Time 0.50
Received By dpalmer Date 2004-05-10 Time 08:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2004-04-23 Cont ID  
Sent By csiegber Date 2004-05-04 Time 15:25 Rev Time 0.50
Received By dpalmer Date 2004-04-23 Time 21:34 Sent To  
Notes
2004-04-23 00:00:00********** UNSAT 5TH TIME ***********
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004,
 AND FS 481.219. PLEASE SEE TITLE BLOCK
 STILL CONTAINS THE FICTITIOUS NAME OF
 "PALM TREE DESIGN"
 IF THIS NAME IS GOING TO REMAIN ON
 TITLE BLOCK, THEN A CERTIFICATE OF
 AUTHORIZATION # IS REQ'D.
 PLEASE ALSO SEE ELECTRICAL SHEET IS NOW
 SEALED OVER A COPY OF ARCH'S INITIALS/
 SIGNATURE.
 PLANS MUST CONTAIN ORIGINAL SIGNATURE
 AS REQ'D BY FS 481.221.
  
 PLEASE SEE THAT ONE SET OF PLANS ARE
 NOW BEING RETAINED TO BE SENT INTO
 DBPR/BOARD OF ARCH'S FOR REVIEW OF
 SAID VIOLATIONS UNDER FS/FAC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-04-19 Cont ID  
Sent By lmartine Date 2004-04-23 Time 17:21 Rev Time 0.26
Received By dpalmer Date 2004-04-19 Time 14:52 Sent To  
Notes
2004-04-19 00:00:00******** UNSAT *********
  
 1)NOTE: PLEASE SEE NO NEW ELECTRICAL
 SHEETS WERE SUBMITTED TO ADDRESS COMMENT
 -S GIVEN ON 3/4/04.
 PLEASE SEE FS 481.219 FOR REQ'D CERTIF-
 -ICATE OF AUTHORIZATION #.
 PLEASE SEE 61G1-16.004, ALL LICENSE
 #'S ARE REQ'D TO BE ON TITLE BLOCK.
  
 2)NOTE: PLEASE CORRECT CIRCUITING FOR
 EM LTS WHEN REVISING SHEET. 700.12E
 LETTER FROM ARCH WAS NOTED.
  
 COMMENT # 1 MUST BE ADDRESSED.
  
 **PLEASE REMOVE ALL OLD/ VOIDED SHEETS
 AND INSERT NEW CORRECT SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-04-03 Cont ID  
Sent By csiegber Date 2004-04-14 Time 11:31 Rev Time 0.50
Received By btrobaug Date 2004-04-03 Time 09:12 Sent To P
Notes
2004-04-03 00:00:00 
 AS PER THE PREVIOUS REVIEWS THE
 ARCHITECT FAILED TO RECIRCUIT THE
 EMERGENCY/EXIT LIGHTS TO MEET THE
 INTENT OF ARTICLE 700.12(E), ATTACHED.
 THE EM/EXIT LIGHTS MUST BE FED FROM THE
 LOCAL BRANCH LIGHTING CIRCUIT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-03-04 Cont ID  
Sent By alange Date 2004-03-30 Time 11:41 Rev Time 0.50
Received By dpalmer Date 2004-03-04 Time 07:20 Sent To  
Notes
2004-03-04 00:00:00************ UNSAT *************
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004 FOR
 ALL REQ'D LICENSE #'S ON TITLE BLOCK.
 PLEASE SEE FS 481.219 FOR LICENSE'S
 REQ'D.
  
 2)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF EM/ EXT LTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-01-07 Cont ID  
Sent By dpalmer Date 2004-01-07 Time 06:28 Rev Time 0.33
Received By dpalmer Date 2004-01-07 Time 06:28 Sent To  
Notes
2004-01-07 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE PROVIDE ALL LICENSE #`S
 ON TITLE BLOCK FOR FIRM. PER FAC 61G1-
 16.004. PER FS 481
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A PANEL SCHED-
 -ULE. IF SOME ARE EXISTING, PLEASE LABEL
 AS "E" IF NEW ,,,,,
 PLEASE SHOW WITH OCP/AWG ON PANEL SCHED-
 -ULE.
  
 3)NOTE: PLEASE SEE 700.12E FOR EM/EXT
 LTS. PLEASE SEE FIRE REVIEW COMMENTS.
  
 4)NOTE: PLEASE SEE EQUIPMENT SCHEDULE,
 SHOWS "MR WINTER" WALK-IN COOLER AS 220V
 , ELECTRICAL SERVICE IS SHOWN AS 208V,
 PLEASE VERFIY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-02-27 Cont ID  
Sent By mcarsill Date 2004-02-27 Time 14:29 Rev Time 0.00
Received By mcarsill Date 2004-02-27 Time 14:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-01-02 Cont ID  
Sent By mcarsill Date 2004-01-02 Time 07:27 Rev Time 0.00
Received By mcarsill Date 2004-01-02 Time 07:27 Sent To  
Notes
2004-01-02 00:00:001) SEPARATE PLANS AND PERMITS REQUIRED
 FOR NEW HOOD, DUCT, AND SUPPRESSION
 SYSTEM.
  
 2) PLANS INDICATE THAT THE PROPOSED
 SPACE IS NOT FIRE SPRINKLER PROTECTED.
 ACCORDING TO FIRE RESCUE PERSONNEL,
 THE SPACE IS FIRE SPRINKLER PROTECTED.
 PLEASE ADVISE.
  
 3) NO EMERGENCY LIGHTS SHOWN ON PLANS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-08-02 Cont ID  
Sent By csiegber Date 2004-08-02 Time 08:37 Rev Time 0.00
Received By csiegber Date 2004-08-02 Time 08:37 Sent To M
Notes
2004-08-02 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-05-04 Cont ID  
Sent By csiegber Date 2004-05-04 Time 15:25 Rev Time 0.00
Received By csiegber Date 2004-05-04 Time 15:25 Sent To E
Notes
2004-05-04 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-04-23 Cont ID  
Sent By lmartine Date 2004-04-23 Time 17:21 Rev Time 0.00
Received By lmartine Date 2004-04-23 Time 17:21 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-04-14 Cont ID  
Sent By csiegber Date 2004-04-14 Time 11:31 Rev Time 0.00
Received By csiegber Date 2004-04-14 Time 11:31 Sent To E
Notes
2004-04-14 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-03-30 Cont ID  
Sent By alange Date 2004-03-30 Time 11:41 Rev Time 0.00
Received By alange Date 2004-03-30 Time 11:41 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-02-25 Time 15:19 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 15:19 Sent To  
Notes
2004-02-25 00:00:00TO COMM BD#25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-30 Cont ID  
Sent By csiegber Date 2003-12-30 Time 16:49 Rev Time 0.00
Received By csiegber Date 2003-12-30 Time 16:49 Sent To  
Notes
2003-12-30 00:00:00TO COMM BD#57

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-03-04 Cont ID  
Sent By csiegber Date 2004-08-02 Time 08:37 Rev Time 0.40
Received By pkrauss Date 2004-03-04 Time 08:34 Sent To  
Notes
2004-03-04 00:00:00HVAC EXISTING REVISED O.A. CALCS ON PLAN
 SHEET 2 OF 4.SEPARATE PERMIT REQUIRED
 FOR THE HOOD, FIRE SUPPRESSION &
 WALK-IN COOLERS.
  
 PLEASE NOTE - EXHAUST TERMINATION FOR
 THE GREASE DUCT SHALL BE A MINIMUM OF
 10 FT FROM ADJACENT PROPERTY LINES,
 CONTINGUOUS BUILDINGS AND AIR INTAKES.
 2001 FBC(M) 506.3.14.3.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-08 Cont ID  
Sent By pkrauss Date 2004-01-08 Time 07:12 Rev Time 1.00
Received By pkrauss Date 2004-01-08 Time 07:03 Sent To  
Notes
2004-01-08 00:00:00DENIED:
 PLEASE CLARIFY THAT THE MECHANICAL
 CONTRACTOR SIGNED ON THE PERMIT
 APPLICATION WILL BE DOING THE HVAC,
 GREASE HOOD/GREASE DUCT AND WALK-IN
 COOLER.SEPARATE PERMITS REQUIRED IF
 OTHER CONTRACTORS ARE TO PERFORM WORK.
 SEPARATE PERMIT REQUIRED FOR
 SUPPRESSION, PLEASE PROVIDE PLANS WITH
 PERMIT APPLICATION.
  
 HVAC:
 1.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) 403.3.
  
 2.NOTE ON PLAN SHEET 2 OF 4 REFERS TO
 SHEET 4 FOR AS-BUILT DRAWING.SHEET 4
 INDICATES GREASE DUCT.
  
 HOOD/GREASE DUCT:
 1.PLEASE INDICATE TERMINATION OF
 GREASE DUCT IN RELATION TO THE PROPERTY
 LINES, AND ADJACENT OR CONTINGUOUS
 BUILDINGS.
  
 2.EXHAUST FAN TO BE HINGED UPBLAST
 TYPE PER NFPA 96 4-8.2.1 (E).
  
 3.INDICATE SIZE OF GREASE DUCT ON
 PLAN.
  
 4.SUBMITTAL REQUIRED FOR THE FIRE
 WRAP IF USED FOR CLEARANCE REDUCTION.
  
 WALK-IN COOLER:
 PROVIDE MANUFACUTER SUBMITTAL DATA WITH
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-04-07 Cont ID  
Sent By kstevens Date 2004-04-07 Time 18:31 Rev Time 0.75
Received By kstevens Date 2004-04-07 Time 18:31 Sent To  
Notes
2004-04-07 00:00:00PASSED PLUMBING ONLY
  
 MANUF. SPECIFICATION SHEETS FOR GAS
 APPLIANCES REQUIRED AT TIME OF GAS PER-
 MIT APPLICATION - INFORMATION REQUIRED
 FOR LOCATION OF L-P TANK/TANKS - SUBMIT
 A SITE PLAN.

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-02-28 Cont ID  
Sent By btrobaug Date 2004-04-03 Time 09:49 Rev Time 1.25
Received By kstevens Date 2004-02-28 Time 13:22 Sent To  
Notes
2004-02-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 COMMENTS NOT ADDRESSED FROM FIRST REVIEW
 NUMBERS TO REMAIN THE SAME FOR CLAIRITY.
 3) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE FOR SIZING OF GREASE INTER-
 CEPTOR. WASTE ORD #2938-96 (561) 837-
 4074. NEED COPY OF APPROVAL SHEET REC'D
 FROM R. COMPO.
 4) SHT 3 OF 4 FLOOR SINK STILL REQUIRED
 FOR ITEM #10. CHANGE WAS MADE TO MOP
 SINK NOT SLOP SINK (#10).
 5) SHT 3 OF 4 GREASE RISER DIAGRAM, A
 VENT IS REQUIRED FOR THE MOP SINK, SECT-
 ION 901.2.1 - VENT CAN NOT COME OUT OF
 DRAIN AS SHOWN. SEE RED LINE CORRECTION
 FOR PROPER VENTING.
 6) FIRM LICENSE NUMBER REQUIRED PER FAC
 61G1-16.004(2) & FS 481.219 (SEE SHEETS
 1 OF 4 & 2 OF 4 - PINE TREE DESIGN) -
 CERTIFICATE OF AUTHORIZATION NUMBERS ARE
 REQUIRED FOR ALL FICTICIOUS BUSINESSES.
 7) THE FOLLOWING INFORMATION IS REQUIRED
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. (SECTION OF PIPE BETWEEN
 THE RISE TO #7 STEAM TABLE AND #2 FIRST
 FRYER HAS NO LENGTH SHOWN) - SUBMIT A
 NEW SHEET WITH NEW RISER ON PLAN AND NOT
 TAPED ON EXISTING SHEET.
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2 - THE
 MANUF. SHEET FOR THE RICE COOKER AND THE
 WATER HEATER HAVE NOT BEEN SUBMITTED.
 THE MANUF. SHEETS FOR THE STEAM TABLE,
 THE SALAMANDER, & DEEP FRYERS DO NOT
 SHOW THE BTU'S/HR REQUIRED TO VERIFY
 PIPE SIZE.
 F. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2. - A
 SITE PLAN FOR THIS SPACE IS REQUIRED TO
 SHOW LOCATION AS REQUIRED. - MORE INFOR-
 MATION THAN SUBMITTED IS REQUIRED.
 G. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58.IF NEAR THE
 PARKING AREA OR ROAD WAY PROTECTION OF
 THE TANKS IS REQUIRED. SUBMIT DETAILS.
 H. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. - NO UNION
 IS SHOWN ON RISER DIAGRAM.
 ********NEW COMMENT FOR GAS PERMIT******
 INFORMATION FOR GAS PERMIT CAN BE SUB-
 MITTED AT TIME OF GAS PERMIT APPLICATION
 AND CAN BE OMITTED FROM THESE PLANS IF
 REQUESTED. - THE RISER DIAGRAM AND ALL
 MANUF SHEETS ECT WILL BE REQUIRED WHEN
 APPLYING FOR GAS PERMIT. OTHERWISE ALL
 INFORMATION WILL BE REQUIRED AT TIME OF
 RESUBMITTING PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-01-16 Cont ID  
Sent By kstevens Date 2004-01-16 Time 16:35 Rev Time 1.50
Received By kstevens Date 2004-01-16 Time 16:34 Sent To  
Notes
2004-01-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) SHT 1 OF 4, SPECIFICATION WORKSHEETS
 REFERED TO ON THE DEPT. OF BUSINESS REG-
 ULATION STAMP, COMMENT #3, SHALL BE SUB-
 MITTED WITH PLANS FOR REVIEW. SECTION
 104.2.1.
 2) AN RPZ BACKFLOW IS REQUIRED ON WATER
 SERVICE TO SPACE. SECTION 608.13.2.
 3) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE FOR SIZING OF GREASE INTER-
 CEPTOR. WASTE ORD. #2938-96. (561) 837-
 4074.
 4) SHT 3 OF 4 FLOOR SINKS ARE REQUIRED
 FOR ITEMS 9 & 10, (3 COMP. SINK & SLOP
 SINK). HUB DRAINS ARE APPROVED FOR
 CLEAR WATER WASTE ONLY. SECTION 802.3
 5) SHT 3 OF 4 GREASE RISER DIAGRAM, A
 VENT IS REQUIRED FOR THE MOP SINK, SECT-
 ION 901.2.1
 6) FIRM LICENSE NUMBER REQUIRED PER FAC
 61G1-16.004(2) & FS 481.
 7) FOLLOWING INFORMATION REQUIRED FOR
 GAS PERMIT APPLICATION.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. TYPE OF GAS, (LP OR NATURAL)
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2. SHEETS
 SHALL SHOW A LISTING FROM AN APPROVED
 TESTING AGENCY.
 F. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 G. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 H. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]