Plan Review Details - Permit 03120127
Plan Review Stops For Permit 03120127
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-06-23 Cont ID  
Sent By shill Date 2004-06-23 Time 13:26 Rev Time 0.50
Received By shill Date 2004-06-23 Time 13:26 Sent To  
Notes
2004-06-23 00:00:00INSPECTION LETTER BY DAVID HUSTAD, PE

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-01-03 Cont ID  
Sent By csiegber Date 2004-06-23 Time 10:47 Rev Time 1.50
Received By shill Date 2004-01-03 Time 19:04 Sent To  
Notes
2004-01-03 00:00:00*****PROVISO******
  
 SUBMIT REVISIONS BEFORE FRAMING
 INSPECTION.
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)THE GIRDER/WALL CONNECTION (SHEET
 3) SPECIFIES HUGHES CONNECTORS; HUGHES
 IS NO LONGER IN BUSINESS.
  
 2.)THE WOOD CONSTRUCTION NOTES, ITEM
 #4, REFERS TO FBC3218.17.NOT IN THE
 FBC CODE BOOK.
  
 3.)HHGT1 AND HHGT2, CONNECTOR KST260
 SHEET RF1, NAILING CONFLICTS WITH THE
 CATALOG AND DESIGN UPLIFT ON THE PLAN
 EXCEEDS MAX ALLOWED BY THE CATALOG
 (USE THE GREY BAR WITHOUT STRESS
 INCREASE FOR STEEL, USP 2003 CATALOG).
  
 4.)WOOD-TO-WOOD CONNECTORS ARE
 SPECIFIED IN WOOD-TO-MASONRY
 APPLICATIONS; FOR EXAMPLE, USP HTW.
 ADDRESS. (SHEET RF1).
  
 5.)PROVIDE A FIREBLOCK DETAIL FOR THE
 DROPPED CEILINGS/SOFFITS, FBC705.3,
 2305.1.4.
  
 6.)PROVIDE STATEWIDE OR SITE SPECIFIC
 PRODUCT APPROVALS FOR
 GARAGE DOOR
 GLASS BLOCK
 FIXED GLASS WINDOW
  
 7.)PROVIDE CORRECT PRODUCT APPROVAL
 AND STATEWIDE PRODUCT APPROVAL FOR THE
 SHUTTERS.SAFEGUARD IS OUT OF BUSINESS.
  
 8.)REMOVE THE TITLE BLOCK FOR AFFINITI
 FROM THE PLAN AS THEY ARE NOT THE
 DESIGNER OF RECORD.
  
 9.)THE ENGINEER'S NAME AND LICENSE
 NUMBER IS TO BE PRINTED ON THE PLAN,
 FAC61G15-23.002.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-12-11 Cont ID  
Sent By jleech Date 2003-12-10 Time 16:27 Rev Time 0.50
Received By dpalmer Date 2003-12-11 Time 07:23 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-23 Cont ID  
Sent By csiegber Date 2004-06-23 Time 10:47 Rev Time 0.00
Received By csiegber Date 2004-06-23 Time 10:47 Sent To B
Notes
2004-06-23 00:00:00TO SH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-03 Cont ID  
Sent By mmclean Date 2003-12-04 Time 11:31 Rev Time 0.00
Received By shill Date 2003-12-02 Time 13:55 Sent To  
Notes
2003-12-04 00:00:00TO SFD RACK/E
2003-12-02 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-12-16 Cont ID  
Sent By dpalmer Date 2003-12-11 Time 07:24 Rev Time 0.50
Received By rregueir Date 2003-12-16 Time 16:37 Sent To B
Notes
2003-12-16 00:00:00PROVISO:
 ATTIC ACCESS OPENING SHALL BE NO LESS
 THAN 30" X 22" AS PER 2001 FBC(M) 306.3
  
 2001 FBC CHAPTER 13 610.1.ABC.3.5.2 -
 1. THE SERVICE PANEL OF THE EQUIPMENT IS
 LOCATED WITHIN 6 FT OF AN ATTIC
 ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE
 OWNER OR SHUT DOWN WHEN THE
 CONDENSATE DRAIN IS NOT WORKING
 PROPERLY.
 4. A NOTICE IS POSTED ON THE ELECTRIC
 SERVICE PANEL INDICATING TO THE
 HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC.SPECIFIC TEXT
 IS REQUIRED IN THIS NOTIFICATION PER
 FBC CHAPTER 13, SUB610.1.ABC.3.5.2

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-12-10 Cont ID  
Sent By csiegber Date 2004-08-17 Time 14:28 Rev Time 0.33
Received By jleech Date 2003-12-10 Time 16:27 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-04 Cont ID  
Sent By mmclean Date 2003-12-04 Time 11:31 Rev Time 0.00
Received By mmclean Date 2003-12-04 Time 11:31 Sent To I
Notes
***NONE***