Plan Review Details - Permit 03111377
Plan Review Stops For Permit 03111377
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-10-04 Cont ID  
Sent By mmclean Date 2004-11-18 Time 11:45 Rev Time 0.55
Received By jwitmer Date 2004-10-04 Time 16:10 Sent To PC
Notes
2004-10-04 00:00:00ROOFING PLAN- OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-06-11 Cont ID  
Sent By csiegber Date 2004-09-15 Time 15:55 Rev Time 0.50
Received By jwitmer Date 2004-06-11 Time 07:18 Sent To PC
Notes
2004-06-11 00:00:006-11-04 ROOF FRAMING, OK JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-03-10 Cont ID  
Sent By csiegber Date 2004-06-08 Time 13:42 Rev Time 1.00
Received By jwitmer Date 2004-03-10 Time 12:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-03-02 Cont ID  
Sent By jwitmer Date 2004-03-02 Time 15:06 Rev Time 2.00
Received By jwitmer Date 2004-03-02 Time 15:05 Sent To  
Notes
2004-03-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03111377
 ADD: 700 S OLIVE AV
 CONT: TRAMMELL
 TEL: (904)334-5691
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) ONLY 1 SET OF PRODUCT TESTING REPORTS
 SUBMITTED. (2) TWO SETS OF PRODUCT TEST-
 ING REPORTS REQUIRED.
 *************IMPORTANT****************
 *************IMPORTANT****************
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-12-31 Cont ID  
Sent By jwitmer Date 2003-12-31 Time 13:32 Rev Time 2.25
Received By jwitmer Date 2003-12-31 Time 13:32 Sent To  
Notes
2003-12-31 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03111377
 ADD: 700 S. OLIVE AVE.
 CONT: TRAMMELL CONST
 TEL: (904)334-5691
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 FIRST REVIEW
 ACTION: DENIED
  
 1) FIRE DISTRICT:
 NO TYPE VI CONSTRUCTION, SHEET A-3
 DETAIL"B" INDICATES WOOD STUDS AND PLY-
 WOOD SHEATHING NOT TO BE USED IN THE
 FIRE DISTRICT. F102.1.
  
 2) PLANS DO NOT INDICATE THE TYPE OF CON
 STRUCTION, TYPE VI NOT ALLOWED ,FIRE DIS
 TRICT, TABLE 600 REQUIRES A 3 HR WALL
 FOR TYPE V CONST. WHEN LOCATED LESS THAN
 3'-0" FROM THE PROPERTY LINE. SEE FOOT-
 NOTE "B".
  
 3) 2117.1.2 CATHEDRAL ENDWALLS.
 GABLE ENDWALLS ADJACENT TO CATHEDRAL
 CEILINGS SHALL BE CONTINIOUS FROM THE
 UPPERMOST FLOOR TO THE CEILING DIAPHRAM
 OR TO THE ROOF DIAPHRAM. THE MASONARY
 WALL CAN NOT STOP AT THE PROPOSED LOCA-
 TION.
  
 4)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A-3 DETAIL "C" INDICATES A 4-BAR
 BEAM, THE PLAN INDICATES A ARCH TO BE IN
 CORPORATED INTO THE BEAM, AT WHAT DEPTH
 IS THE BOTTOM STEEL TO BE PLACED? ALSO
 WILL THERE BE STIRRIPS OR HOOPS IN THIS
 BEAM? SIZE & WHAT SPACING?
  
 5) OCCUPANCY: STORAGE, 1027.1.1 SINGLE
 EXIT REQUIREMENTS (3) THE MAXIMUM DISTAN
 CE OF TRAVEL TO THE EXIT DOES NOT EX-
 CEED 50'.1012.1.2 EGRESS DOORS SHALL BE
 SIDE SWINGING TYPE.
  
 6)FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
  
 7)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 8) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS: LOUVER
  
 A REPORT FOR SERIES 238 ALUM CASEMENT
 WINDOW IS INCLUDED IN THE PERMIT PACKAGE
 BUT NOT SHOWN ON PLAN.
  
 ALSO INCLUDED IN THE PACKAGE IS A REPORT
 FOR A SERIES 1000 8'-0" OUTSWING WOOD
 DOOR, PLAN CALLS FOR A 3'-10" WIDE DOOR
 BUT THE REPORT IS FOR 3'-0".
  
 9)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10) ENCLOSED PARKING GARAGES, MORE THAN
 (4) AUTOMOBILES OR TRUCKS OF 1 TON MAX.
 CAPACITY. 411.4.2 THE MECHANICAL SYSTEM
 SHALL BE CAPABLE OF PROVIDING 6 AIR
 CHANGES PER HR. UNDER NORMAL USE THE
 VENTILATION OF THE ENCLOSED AUTOMOBILE
 PARKING SHALL COMPLY WITH THE VENTILA-
 TION REQUIREMENTS 411.5.4.
  
 11)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-03-10 Cont ID  
Sent By dpalmer Date 2005-03-10 Time 13:32 Rev Time 0.30
Received By dpalmer Date 2005-03-10 Time 13:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2004-07-19 Cont ID  
Sent By dpalmer Date 2004-07-19 Time 13:57 Rev Time 0.25
Received By dpalmer Date 2004-07-19 Time 13:57 Sent To  
Notes
2004-07-19 00:00:00*** UNSAT *********
  
 1)NOTE: ANY CHANGES TO PLANS MUST BE
 DONE BY THE ARCH OR ENG OF RECORD.
 FS 481//471
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-04-27 Cont ID  
Sent By csiegber Date 2004-07-15 Time 13:19 Rev Time 0.25
Received By dpalmer Date 2004-04-27 Time 20:36 Sent To  
Notes
2004-04-27 00:00:00ELEC REV FOR GATE CONTROLS ONLY.
 NOT ON SIGNED AND SEAL ORIG PLANS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-03-09 Cont ID  
Sent By csiegber Date 2004-04-27 Time 13:53 Rev Time 0.33
Received By dpalmer Date 2004-03-09 Time 05:56 Sent To  
Notes
2004-03-09 00:00:00OLD SHEETS NEED TO BE REMOVED AND NEW
 SHEEST INSERTED.
 ELECTRICAL PLANS STAMPED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-02-10 Cont ID  
Sent By dpalmer Date 2004-02-10 Time 13:15 Rev Time 0.75
Received By dpalmer Date 2004-02-10 Time 12:59 Sent To  
Notes
2004-02-10 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE SEE THAT PLANS ARE NOW
 BEING SUBMITTED WITH A RISER DIAGRAM.
  
 2)NOTE: PLEASE SHOW GROUNDING EELCTRODE
 ETC FOR THE DEATCHED BLDG. PER 250.32
 FOOTER STEEL, COLD WATER. 250.50
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 4)NOTE: PLEASE HAVE PLANS SIGNED, DATED
 AND SEALED BY THE ARCH OF RECORD PER
 FS 481.221. PLANS ARE COPIES. MUST BE
 ORIGINAL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-23 Cont ID  
Sent By dpalmer Date 2003-12-23 Time 16:21 Rev Time 0.50
Received By dpalmer Date 2003-12-23 Time 16:21 Sent To  
Notes
2003-12-23 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT ELECTRICAL RISER
 DIAGRAM WITH SERVICE.215.5 CONDUCTORS,
 CONDUIT ETC. PANEL/SIZE ETC.
  
 2)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 SYSTEM FOR DETACHED BLDG. 250.32
  
 3)NOTE: PLEASE SEE THAT ALL RECEPTS IN
 GARAGE TO MEET 210.8 (GFI) EXPT OF
 OPENER/DEDICATED.
  
 4)NOTE: PLEASE SUBMIT INFORMATION FOR
 FEED FOR GARAGE SERVICE.
  
 PLEASE NOTE: DUE TO PLANS NOT BEING
 COMPLETE AT THIS TIME, OTHER COMMENTS
 MAY ARISE WHEN PLANS HAVE BEEN COMPLETED
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2003-12-29 Cont ID  
Sent By mamini Date 2003-12-29 Time 11:38 Rev Time 0.00
Received By mamini Date 2003-12-29 Time 11:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-02-10 Cont ID  
Sent By mcarsill Date 2004-02-10 Time 14:26 Rev Time 0.00
Received By mcarsill Date 2004-02-10 Time 14:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-01-02 Cont ID  
Sent By mcarsill Date 2004-01-02 Time 07:31 Rev Time 0.00
Received By mcarsill Date 2004-01-02 Time 07:31 Sent To  
Notes
2004-01-02 00:00:001) SUBJECT LOCATION IS LOCATED IN THE
 CITY FIRE LIMITS. CERTAIN RESTRICTIONS
 APPLY. PLEASE SEE APPENDIX F, LOCAL
 AMENDMENTS TO THE FLORIDA BUILDING CODE.
  
 2) SINGLE EXIT THEORY FROM STORAGE
 AREA DOES NOT COMPLY WITH THE
 FLORIDA BUILDING CODE. THE SINGLE
 SIDE SWINGING DOOR MAY NOT MEET FIRE
 CODE REQUIREMENTS FOR PARKING GARAGES.
 PLEASE REVIEW BOTH CODES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-03-08 Cont ID  
Sent By adarroug Date 2005-03-08 Time 08:26 Rev Time 0.00
Received By adarroug Date 2005-03-08 Time 08:26 Sent To E
Notes
2005-03-08 00:00:00TO DPALMER DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-11-15 Cont ID  
Sent By mmclean Date 2004-11-18 Time 11:44 Rev Time 0.00
Received By csiegber Date 2004-11-15 Time 09:09 Sent To B
Notes
2004-11-15 00:00:00TO JW DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-09-15 Cont ID  
Sent By csiegber Date 2004-09-15 Time 15:55 Rev Time 0.00
Received By csiegber Date 2004-09-15 Time 15:55 Sent To B
Notes
2004-09-15 00:00:00TO JW DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-07-15 Cont ID  
Sent By csiegber Date 2004-07-15 Time 13:19 Rev Time 0.00
Received By csiegber Date 2004-07-15 Time 13:19 Sent To E
Notes
2004-07-15 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-06-08 Cont ID  
Sent By csiegber Date 2004-06-08 Time 13:42 Rev Time 0.00
Received By csiegber Date 2004-06-08 Time 13:42 Sent To B
Notes
2004-06-08 00:00:00TO JW DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-04-27 Cont ID  
Sent By csiegber Date 2004-04-27 Time 13:53 Rev Time 0.00
Received By csiegber Date 2004-04-27 Time 13:53 Sent To E
Notes
2004-04-27 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-03-04 Cont ID  
Sent By csiegber Date 2004-03-04 Time 16:46 Rev Time 0.00
Received By csiegber Date 2004-03-04 Time 16:46 Sent To  
Notes
2004-03-04 00:00:00TO COMM BD#2

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-04 Cont ID  
Sent By csiegber Date 2004-02-04 Time 11:52 Rev Time 0.00
Received By csiegber Date 2004-02-04 Time 11:52 Sent To  
Notes
2004-02-04 00:00:00TO COMM BD#44

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-12-17 Cont ID  
Sent By csiegber Date 2003-12-17 Time 15:07 Rev Time 0.00
Received By csiegber Date 2003-12-17 Time 15:07 Sent To  
Notes
2003-12-17 00:00:00TO COMM BD#42

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-01 Cont ID  
Sent By csiegber Date 2003-12-01 Time 09:26 Rev Time 0.00
Received By csiegber Date 2003-12-01 Time 09:26 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-02-10 Cont ID  
Sent By kstevens Date 2004-02-10 Time 18:31 Rev Time 0.33
Received By kstevens Date 2004-02-10 Time 18:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-12-29 Cont ID  
Sent By kstevens Date 2003-12-19 Time 10:28 Rev Time 0.33
Received By kstevens Date 2003-12-19 Time 10:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2004-11-24 Cont ID  
Sent By mmclean Date 2004-11-24 Time 10:36 Rev Time 0.00
Received By aaponte Date 2004-11-24 Time 10:36 Sent To  
Notes
2004-12-01 00:00:00CALLED CONTRACTOR AND FILE UNDER T FOR
 P/U MM
2004-11-24 00:00:001.STREET WALLS AT STREET FRONTS AND SIDE
 PROPERTY LINES FACING STREETS SHALL BE
 36 TO 48 INCHES IN HEIGHT. PROPOSED WALL
 IS DETAILED AS 6 FEET IN HEIGHT AND
 ROLLING GATE IS DETAIL AS 6 FEET IN
 HEIGHT.

Review Stop Z ZONING
Rev No 2 Status P Date 2003-12-17 Cont ID  
Sent By agiannio Date 2003-12-17 Time 10:23 Rev Time 0.25
Received By kstevens Date 2003-12-19 Time 10:27 Sent To  
Notes
2003-12-17 00:00:00PROVISO:GATE IS NOT INCLUDED IN PERMIT
 APPLICATION OR APPROVAL

Review Stop Z ZONING
Rev No 1 Status P Date 2004-03-10 Cont ID  
Sent By csiegber Date 2003-12-01 Time 09:28 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2004-03-10 00:00:00APPROVED 12/17/03 PER SEE SITE PLAN


Account Summary | Usage Policy | Privacy Policy