Plan Review Details - Permit 03111369
Plan Review Stops For Permit 03111369
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-12 Cont ID  
Sent By dpalmer Date 2003-12-12 Time 14:19 Rev Time 0.50
Received By dpalmer Date 2003-12-12 Time 13:51 Sent To M
Notes
2003-12-12 00:00:00************* UNSAT ************
  
 1)NOTE: PLEASE SEE FS 481.221 FOR ALL
 INFORMATION REQ'D ON TITLE BLOCK FOR
 ARCH OF RECORD. PLEASE ALSO SEE FAC
 61G1-16.004 FOR ADDITIONAL INFORMATION
 REQ'D. INCLUDING ADDRESS OF JOB.
 IMPRESSION OF SEAL SHOULD BE CLEAR AND
 VISABLE.
  
 2)NOTE: PLEASE SUBMIT AIC RATING FOR ALL
 NEW EUIPMENT BEING INSTALLED.
 MAINS/ BRKRS AND PANELS ARE ALLL TO BE
 RATED FOR THE AVAIABLE FAULT CURRENT.
 110.9/215.5
  
 PLEASE NOTE, INFORMATION FOR NOTE #1 IS
 REQ'D ON ALL SHEETS AND NOT JUST THE
 ELECTRICAL SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-11-26 Cont ID  
Sent By csiegber Date 2003-11-26 Time 16:20 Rev Time 0.00
Received By csiegber Date 2003-11-26 Time 16:20 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-12-11 Cont ID  
Sent By dpalmer Date 2003-12-12 Time 15:02 Rev Time 1.00
Received By pkrauss Date 2003-12-11 Time 11:33 Sent To E
Notes
***NONE***