Plan Review Details - Permit 03111290
Plan Review Stops For Permit 03111290
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-02-18 Cont ID  
Sent By rmcdouga Date 2004-02-18 Time 13:35 Rev Time 2.00
Received By rmcdouga Date 2004-02-18 Time 13:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-02-05 Cont ID  
Sent By csiegber Date 2004-02-17 Time 16:20 Rev Time 2.00
Received By rmcdouga Date 2004-02-05 Time 12:39 Sent To  
Notes
2004-02-05 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE PRINT ON THE REVISED SHEETS IS
 SMEARED AND HAS RUBBED OFF IN SEVERAL
 PLACES. THE INK DOES NOT APPEAR TO BE
 PERMANENT. PLEASE CORRECT.
  
 3) THE UPLIFT GIVEN FOR THE USP RT24T
 CONNECTOR ON A3 INCLUDES A ONE-THIRD
 INCREASE IN THE STEEL CALCULATION. THIS
 IS NOT ALLOWED BY FBC 1609.4.3. THE
 VALUE SHOULD BE 1125#, SEE CURRENT USP
 CATALOG.
  
 4) PROVIDE DRAWINGS AND DETAILS FOR THE
 CONSTRUCTION OF THE COVERED ENTRY PORCH
 BETWEEN THE MAIN HOUSE AND GUEST HOUSE.
  
 5) PROVIDE STRUCTURAL DETAILS OF THE
 CANTILEVERED TRUSSES AT THE COVERED
 PORCH AT THE FAMILY ROOM.
  
 6) SPECIFY THE ROOF SHEATHING FASTENING
 REQUIREMENTS. SEE CITY OF WPB AMENDMENTS
 TO FBC TABLE 2306.1. SEE FBC 1606.2.3
 AND 1606.2(C).
  
 7) SUBMIT PRODUCT APPROVALS FOR THE
 SINGLE HUNG WINDOWS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-06 Cont ID  
Sent By csiegber Date 2004-02-05 Time 10:18 Rev Time 2.50
Received By rmcdouga Date 2004-01-06 Time 07:40 Sent To  
Notes
2004-01-06 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE GLASS BLOCK IN THE MASTER BATH
 SHOWER AND TUB ARE REQUIRED TO BE SAFETY
 GLASS PER FBC 2405.2.1. GLASS BLOCK WITH
 A UNIFORM FACE THICKNESS OF 0.25INCH IS
 EXEMPT PER FBC 2405.2.2. PLEASE SPECIFY
 THIS ON PLANS AND SUBMIT THE PROPER
 G.B. PRODUCT APPROVAL.
  
 3) REVISE THE NUMBER OF NAILS SPECIFIED
 FOR THE RT24T CONNECTOR ON A3. THE
 CORRECT AMOUNT OF NAILS IS (12) AND (14)
 EQUALLY DISTRIBUTED TO BOTH SIDES OF THE
 CONNECTION.
  
 4) SPECIFY THE LENGTH/EMBED DEPTH OF THE
 1/2" EXP. ANCHOR BOLTS FOR THE BEARING
 WALL ON A6.
  
 5) REVISE THE ROOF SHEATHING NOTES ON
 SHEET A6. THE MINIMUM THICKNESS FOR ROOF
 SHEATHING IS 19/32" PER CITY AMENDMENTS
 TO FBC TABLE 2309.3A.
  
 6) REVISE THE ROOF SHEATHING NOTES ON
 SHEETS A3 AND A6. THE CORNERS OF HIP
 ROOFS ARE ZONE 3 PER CITY AMENDMENTS TO
 FBC TABLE 2306.1. ALSO SEE FBC 1606.2.3
 AND 1606.2(C). THE ROOF SHEATHING IS
 REQUIRED TO BE NAILED AT 4"OC AT THE
 EDGES IN ZONE 3.
  
 7)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL FORM PER
 RULE 9B-72. SEE THE FORM ATTACHED.
  
 8) SUBMIT PRODUCT APPROVALS FOR THE
 GLASS BLOCK.
  
 9) REVISE SHEET A1 TO INDICATE THAT THE
 FRENCH DOORS W/SIDELITES AT THE LIVING
 ROOM IS AN ASSEMBLY AS INDICATED BY THE
 PRODUCT APPROVAL AND NOT A PAIR OF
 FRENCH DOORS WITH FIXED FRENCH DOORS ON
 EACH SIDE AS SHOWN ON THE PLAN.
 THERE ARE THREE SETS OF WINDLOAD
 PRESSURES LISTED ON THE PLANS. THERE
 SHOULD BE ONLY ONE SET OF PRESSURES IF
 THIS IS ONE OPENING. PLEASE CLARIFY.
  
 10) THE PRODUCT APPROVAL SUBMITTED FOR
 THE 2" HEAVY MULLIONS IS ONLY GOOD FOR
 + OR - 44PSF FOR THE MULLION ABOVE THE
 FRENCH DOOR W/SIDELITES AT THE L.R.
 WHICH SPANS 140". THIS DOES NOT MEET THE
 -45PSF LISTED ON THE PLANS FOR THIS
 OPENING. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-12-10 Cont ID  
Sent By dpalmer Date 2003-12-10 Time 12:27 Rev Time 0.50
Received By dpalmer Date 2003-12-10 Time 12:27 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-17 Cont ID  
Sent By csiegber Date 2004-02-17 Time 16:20 Rev Time 0.00
Received By csiegber Date 2004-02-17 Time 16:20 Sent To B
Notes
2004-02-17 00:00:00TO RM DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-05 Cont ID  
Sent By csiegber Date 2004-02-05 Time 10:18 Rev Time 0.00
Received By csiegber Date 2004-02-05 Time 10:18 Sent To B
Notes
2004-02-05 00:00:00TO RM DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date 2004-01-06 Cont ID  
Sent By mmclean Date 2003-12-03 Time 09:28 Rev Time 0.00
Received By rmcdouga Date 2003-11-26 Time 11:06 Sent To  
Notes
2003-12-04 00:00:00TO SFD RACK/E
2003-11-26 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-12-16 Cont ID  
Sent By dpalmer Date 2003-12-10 Time 12:31 Rev Time 0.50
Received By rregueir Date 2003-12-16 Time 17:54 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-02-18 Cont ID  
Sent By rmcdouga Date 2004-02-18 Time 13:35 Rev Time 0.00
Received By rmcdouga Date 2004-02-18 Time 13:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-01-03 Cont ID  
Sent By rregueir Date 2003-12-16 Time 17:54 Rev Time 0.33
Received By jleech Date 2004-01-03 Time 05:48 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-12-03 Cont ID  
Sent By mmclean Date 2003-12-03 Time 09:28 Rev Time 0.00
Received By mmclean Date 2003-12-03 Time 09:28 Sent To I
Notes
***NONE***