Plan Review Details - Permit 03111280
Plan Review Stops For Permit 03111280
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-11-05 Cont ID  
Sent By jwitmer Date 2004-11-05 Time 14:32 Rev Time 0.55
Received By jwitmer Date 2004-11-05 Time 14:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-05-07 Cont ID  
Sent By jwitmer Date 2004-05-07 Time 11:59 Rev Time 0.55
Received By jwitmer Date 2004-05-07 Time 11:59 Sent To PC
Notes
2004-05-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03111280
 ADD: 1806 OKEECHOBEE ROAD
 CONT: WINFREE
 TEL: (561)###-####
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 REVISION: PROVISO
  
 PLANS ARE CODE COMPLIANT, AS STATED BY
 ELEC & PLUMB FL S S REQUIRE ARCHITECT
 SIGNATURE REQUIRED SEE FL S S 61G-16/
 FL ADMINISTRATIVE CODE 481.221.
 NEXT SUBMITTAL CORRECT!
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-04-02 Cont ID  
Sent By jwitmer Date 2004-04-02 Time 13:02 Rev Time 1.10
Received By jwitmer Date 2004-04-02 Time 13:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-01-28 Cont ID  
Sent By jwitmer Date 2004-01-28 Time 15:08 Rev Time 2.75
Received By jwitmer Date 2004-01-28 Time 15:08 Sent To  
Notes
2004-01-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03111280
 ADD: 1806 OKEECHOBEE ROAD
 CONT: WINFREE CONTRACTING
 TEL: (561)744-6939
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 NOTE: ALL CORRESPONDANCE ABOUT THIS
 PARCEL SHOULD BE ADDRESSED AS OKEECHOBEE
 ROAD, THERE IS NO " OLD OKEECHOBEE ROAD"
 WITHIN THE COPARATE CITY LIMITS. THIS
 SAME ROAD WES1)OF FLORIDA MANGO (COUNTY)
 IS NAMED OLD OKEECHOBEE ROAD.
 WHEN THE REFRENCE OF OLD OKEECHOBEE
 IS USED IN 9-1-1 RESPONCE THEY WILL
 RESPOND TO THE ROAD WEST OF FLORIDA
 MANGO.!
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) MULLIONS
 C) EXTERIOR SWING DOORS
 D) OVERHEAD GARAGE DOORS
 E) STORM SHUTTERS
 *************IMPORTANT******************
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 WINDOWS AND DOORS EVEN IF SHUTTERED
 SHALL SUPPLY PRODUCT TESTING REPORTS
 REQUIRED FOR WIND LOADS!!!!1606.2.4
 MAIN FORCE RESISTING SYSTEM.
  
 3)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 4)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 5)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-12-31 Cont ID  
Sent By jwitmer Date 2003-12-31 Time 11:27 Rev Time 1.55
Received By jwitmer Date 2003-12-31 Time 11:27 Sent To PC
Notes
2003-12-31 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 03111280
 ADD: 1806 OKEECHOBE ROAD
 CONT: WINFREE CONTRACTING
 TEL: (561)744-6939
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 FIRST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET 1 OF 7 INDICATES A NEW STORAGE
 ROOM, BUT SHEET2 NOR SHEET4 (PHASE 1 &
 2) INDICATE THIS AREA ON THEIR FLOOR
 PLANS?
  
 3) FLOOR PLANS DO NOT INDICATE WHAT OPEN
 INGS ARE EXISTING AND WHICH ARE NEW?
  
 4) SHEET 1 INDICATES THE NEW COLUMN AT
 DOOR"D", AT WHAT THEIGHT IS THE BEAM?
 THE DETAIL SHEET 4 INDICATES THE USE OF
 A LINTEL BUT NO MENTION OF BEARING ON
 THE EXISTING COLUMN?
 VARIOUS DOOR OR WINDOWS SHOW WHAT
 APPEARS TO BE BLOCK INFILL, NO MENTION
 OF HOW TO BE ATTACHED TO THE EXISTING
 STRUCTURE? NO MENTION OF FILLED CELLS?
  
 5) SHEET 1 DESIGN CRITERIA FOR NEW
 STORAGE ROOM:ASCE 7-98 IMPORTANCE FACTOR
 INDICATES THE WIND IMPORTANCE FACTOR OF
 .77 TO BE USED ON CATEGORY I (BUILDINGS)
 NOT ADDITONS. TYPE I BUILDINGS BEING:
 A) AGRICULTURE FACILITIES
 B) CERTAIN TEMPORARY FACILITIES
 C) MINOR STORAGE FACILITIES- STORAGE
 SHEDS NOT ATTACHED TO BUILDINGS
 RE-EVALUATE STORAGE SHED WITH AN IMPORT-
 ANCE FACTOR 0F 1.00.
  
 6) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) MULLIONS
 C) EXTERIOR SWING DOORS BOTH GLAZED OR
 NON-GLAZED
 D) OVERHEAD GARAGE DOOR
 E) STORM SHUTTERS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 7)SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL
 OF RECORD.SITE SPECIFIC ENGINEERING
 WILL BE REQUIRED IF THE MANUFACTURER HAS
 NOT LISTED THEIR PRODUCT WITH THE STATE!
  
 8) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 9)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 10)1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE.
  
 11) PLAN DO NOT INDICATE WHAT TYPE OF
 BUCKS ARE TO BE USED, CAUTION:
 1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 12) THE DESIGN PROFESSIONAL DOES NOT
 INDICATE THE ANCHORING OF THE BUCKS NOR
 THE WINDOWS AND DOORS:
 1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
 13) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 14) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 15) RAMP: 11-4.8.5(HANDRAILS) IF A RAMP
 RUN HAS A RISE GREATER THAN 6" OR A
 HORIZONTAL PROJECTION GREATER THAN 72",
 THEN IT SHALL HAVE HANDRAILS ON BOTH
 SIDES.
  
 16)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL. SEE ROOMS 124 & 125.
  
 17) THERE IS NO DETAILS OF THE STAFF
 LOUNGE, 11-4.24.2 SINKS REQUIRED TO BE
 ACCESSIBLE TO BE MOUNTED WITH THE
 COUNTER NO HIGHER THAN 34 INCHES.
  
 18) 1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2004-12-20 Cont ID  
Sent By btrobaug Date 2004-12-20 Time 14:51 Rev Time 0.50
Received By btrobaug Date 2004-12-20 Time 12:20 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2004-11-01 Cont ID  
Sent By dpalmer Date 2004-11-01 Time 14:42 Rev Time 1.00
Received By dpalmer Date 2004-11-01 Time 14:42 Sent To  
Notes
2004-11-01 00:00:00******* UNSAT ***************
  
 1)NOTE: PLEASE SEE OCP FOR AHU'S PER
 424.3B. SHOWS 50A ON 10+KW UNITS WITH
 #8.
 SOME SHOW #6, YET STILL HAVE 50A OCP.
  
 2)NOTE: PLEASE SEE SOME BRANCH CIRCUITS
 ARE SHOWN W/ 25A OCP ON #12.
 PLEASE SEE MAX OCP IS TO BE 20A.
 310.16/ NOTES ETC. 110.14/ 240.4
  
  
 *** PLEASE SEE PLUMB REVIEW COMMENTS
 FOR
 SEALED PHOTOCOPIES. (8 1/2X 11'S)
 ATTACHED TO PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-04-23 Cont ID  
Sent By dpalmer Date 2004-04-23 Time 06:10 Rev Time 0.33
Received By dpalmer Date 2004-04-23 Time 06:08 Sent To  
Notes
2004-04-23 00:00:00*********** UNSAT ****************
  
 1)NOTE: PANEL SCHEDULE(S) NOT SUBMITTED
 TO VERIFY CIRCUITING AS PREVIOUSLY
 REQUESTED/PROVISO.
  
 2)NOTE: PLEASE SEE FS 481.221, A FULL
 SIGNATURE IS REQ'D CONTAINING A MIN
 OF FIRST AND LAST, OR AS SHOWN ON
 RAISED SEAL. INITIALS ARE NOT PERMITTED
 PER FS/ FAC 61G1-16
  
 3)NOTE: CODE COMPLIANCE FOR PLANS CAN
 NOT BE VERIFIED AT THIS TIME DUE TO
 INFORMATION MISSING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-04-09 Cont ID  
Sent By btrobaug Date 2004-04-07 Time 16:40 Rev Time 1.00
Received By btrobaug Date 2004-04-07 Time 14:54 Sent To  
Notes
2004-04-07 00:00:00PROVISO
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW PRIOR TO ROUGH INSPECTION.
  
 1} SEE 700.12(E). EMERGENCY LIGHTS
 STILL DO NOT COMPLY. MUST BE ON THE
 SAME CIRCUIT THAT SERVES NORMAL LIGHTING
 IN THE AREA. SEE SHEET #3.
  
 2} THERE ARE BRANCH CIRCUIT NUMBERS
 MISSING FROM SOME LIGHTING, SEE HALL ON
 SHEET #5, ROOM 102 ALSO.
  
 3} THE WATER COOLER AND COPIER CIRCUITS
 ARE NOT MARKED CORRECTLY, SHEET #4.
 PLEASE CHECK ALL BRANCH CIRCUIT #'S
  
 4} INDICATE THE LOCATION OF PANEL "A".
  
 SEE FS 553.80(2)(B), ATTACHED. FEES DUE
 BY STATUTE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-01-29 Cont ID  
Sent By dpalmer Date 2004-01-29 Time 12:27 Rev Time 1.00
Received By dpalmer Date 2004-01-29 Time 12:26 Sent To  
Notes
2004-01-29 00:00:00************** UNSAT **************
  
 ** PLEASE SEE NOTES ON PREVIOUS REVIEW**
  
 1)NOTE: PLEASE SHOW CIRCUITING FOR ALL
 EM/EXT LTS PER 700.12E.
 SOME NOT CORRECTED AND PANEL SCHEDULES
 ARE THE SAME SUBMITTED FIRST TIME.
  
 2)NOTE: PLEASE SEE THAT SIGN(S) CIRCUITS
 REQ'D PER 600.5 ARE NOW SHOWN ON PLANS,
 HOWEVER, PANEL SCHEDULES DO NOT REFLECT
 CHANGES.
  
 3)NOTE: PLEASE SEE THAT LICENSE #'(S)
 REQ'D ON TITLE BLOCKS PER 61G1-16
 ARE MISSING FROM ORIG SHEETS.
  
 ** PLEASE SEE BLDG REVIEW COMMENTS. PLAN
 -S STILL SHOW AN ADDRESS OF "OLD" OKEE-
 -CHOBEE. PLEASE CORRECT. PLANS ARE REQ'D
 TO LIST ADDRESS PER 61G1-16.004
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-08 Cont ID  
Sent By dpalmer Date 2003-12-08 Time 13:51 Rev Time 1.50
Received By dpalmer Date 2003-12-08 Time 12:51 Sent To  
Notes
2003-12-08 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF EM/EXT LTS .
 CIRCUITING NOT SHOWN.
  
 2)NOTE: PLEASE SEE THAT THERE IS SOME
 OTHER CIRCUITING MISSING. (RM 110)
  
 3)NOTE: PLEASE CLARIFY/SHOW MISSING
 SIGN CIRCUIT PER 600.5
  
 4)NOTE: PLEASE SEE FS 481 AND FAC 61G1-
 16.004. PLEASE INCLUDE LICENSE # FOR
 ARCH OF RECORD ON TITLE BLOCK ASA REQ'D
 PER ABOVE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWERS THAT MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
 ****************************************
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEWING AND STAMPING.
 ****************************************

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-11-16 Cont ID  
Sent By nmccray Date 2004-11-16 Time 12:05 Rev Time 0.00
Received By nmccray Date 2004-11-16 Time 12:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-04-23 Cont ID  
Sent By mcarsill Date 2004-04-23 Time 14:01 Rev Time 0.00
Received By mcarsill Date 2004-04-23 Time 14:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-12-12 Cont ID  
Sent By mcarsill Date 2003-12-12 Time 14:03 Rev Time 0.00
Received By mcarsill Date 2003-12-12 Time 14:03 Sent To  
Notes
2003-12-12 00:00:001) DEMOLITION, RENOVATION, AND
 CONSTRUCTION SHALL COMPLY WITH NFPA 241.
  
 2) DEBRIS IS TO BE REMOVED DAILY FROM
 THE SITE AND THE BUILDING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-12-20 Cont ID  
Sent By ptjomsto Date 2004-12-20 Time 11:00 Rev Time 0.00
Received By ptjomsto Date 2004-12-20 Time 10:59 Sent To  
Notes
2004-12-20 00:00:00REVISION GIVEN TO BILL TROBAUGH

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-11-08 Cont ID  
Sent By csiegber Date 2004-11-08 Time 12:16 Rev Time 0.00
Received By csiegber Date 2004-11-08 Time 12:16 Sent To M
Notes
2004-11-08 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-10-27 Cont ID  
Sent By csiegber Date 2004-10-29 Time 13:56 Rev Time 0.00
Received By csiegber Date 2004-10-27 Time 13:56 Sent To  
Notes
2004-10-29 00:00:00TO COMM BD#23/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-04-22 Cont ID  
Sent By alange Date 2004-04-22 Time 12:33 Rev Time 0.00
Received By alange Date 2004-04-22 Time 12:33 Sent To  
Notes
2004-04-22 00:00:00TO COMM BD. #31

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-03-29 Cont ID  
Sent By alange Date 2004-03-29 Time 15:02 Rev Time 0.00
Received By alange Date 2004-03-29 Time 15:02 Sent To  
Notes
2004-03-29 00:00:00TO COMMERCIAL BD. #11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-23 Cont ID  
Sent By csiegber Date 2004-01-23 Time 10:53 Rev Time 0.00
Received By csiegber Date 2004-01-23 Time 10:53 Sent To  
Notes
2004-01-23 00:00:00TO COMM BD#42

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-01 Cont ID  
Sent By csiegber Date 2003-12-01 Time 10:18 Rev Time 0.00
Received By csiegber Date 2003-12-01 Time 10:18 Sent To  
Notes
2003-12-01 00:00:00TO COMM BD#17

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-11-10 Cont ID  
Sent By pkrauss Date 2004-11-10 Time 16:52 Rev Time 0.00
Received By pkrauss Date 2004-11-10 Time 10:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-04-27 Cont ID  
Sent By pkrauss Date 2004-04-27 Time 09:21 Rev Time 0.45
Received By pkrauss Date 2004-04-27 Time 08:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-12-19 Cont ID  
Sent By pkrauss Date 2003-12-19 Time 07:04 Rev Time 0.40
Received By pkrauss Date 2003-12-19 Time 07:04 Sent To  
Notes
2003-12-19 00:00:00PROVISO:
 DUCT SMOKE DETECTORS REQUIRED.PLEASE
 PROVIDE DUCT SMOKE DETECTORS IN THE
 SUPPLY AIR DUCT PER 2001 FBC(M) 606.2.1.
  
 FAN SHUTDOWN SHALL HAVE NOTIFICATION TO
 ALARM/STROBE IN NORMALLY OCCUPIED AREAS
 PER NFPA 90A 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 6 Status P Date 2004-12-30 Cont ID  
Sent By kstevens Date 2004-12-30 Time 15:27 Rev Time 0.75
Received By kstevens Date 2004-12-30 Time 15:27 Sent To  
Notes
2004-12-30 00:00:00REVISION OK - SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 5 Status P Date 2004-11-16 Cont ID  
Sent By pschmitz Date 2004-11-16 Time 11:51 Rev Time 0.00
Received By pschmitz Date 2004-11-16 Time 11:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2004-04-29 Cont ID  
Sent By kstevens Date 2004-04-29 Time 09:26 Rev Time 0.50
Received By kstevens Date 2004-04-29 Time 09:26 Sent To  
Notes
2004-04-29 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SIGNATURE REQUIRED ON SEAL PER FAC
 61G1-16 & FS 481.221 - INITIALS ARE NOT
 ACCEPTABLE. MINIMUM FIRST & LAST NAME.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-04-01 Cont ID  
Sent By kstevens Date 2004-04-01 Time 17:26 Rev Time 0.50
Received By kstevens Date 2004-04-01 Time 17:26 Sent To  
Notes
2004-04-01 00:00:00PASSED/PROVISO - WATER HEATER IN LOUNGE
 SHALL BE ACCESSIBLE.

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-02-03 Cont ID  
Sent By kstevens Date 2004-02-03 Time 09:40 Rev Time 0.50
Received By kstevens Date 2004-02-03 Time 09:40 Sent To  
Notes
2004-02-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) ALL TOILET ROOM SHALL SHOW CLEAR
 FLOOR SPACE PER SECTIONS 11-4.16.3,
 11-4.19.3, 11-4.22.3 & 11-4.24.5.
 2) DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE REQUIRED FOR ANY FIXTURE.
 11-4.22.2
 3) SHT 4 OF 7 ROOM 103 TOILET SHALL NOT
 ENTER INTO UNOBSTRUCTED TURNING AREA FOR
 TOILET ROOM.
 4) SHT 3 OF 7 SANITARY RISER DIAGRAM,
 SHOW ALL PIPE SIZE RISER. INFORMATIONAL
 NOTE: 5" PIPE IS NOT A COMMON PIPE SIZE.
 UP TO 36 FIXTURE UNITS CAN BE DRAINED ON
 3" SANITARY PIPE.
 5) SHT 3 OF 7 WATER RISER DIAGRAM. WATER
 HAMMER ARRESTORS SHALL BE INSTALLED AT
 THE DISHWASHER AND ICE MAKER, (IF INSTA-
 LLED), PER SECTION 604.9 LOCATED NEAR
 THE FIXTURE IN AN "EFFECTIVE RANGE" NOT
 IN CEILING. PDI-WH 201 AND MANUF. IN-
 STALLATION INSTRUCTIONS.
 6) SHT 3 OF 7 WATER RISER DIAGRAM, WATER
 HEATERS WILL REQUIRE THERMAL EXPANSION
 CONTROL PER 607.3.2 AND A VACUUM RELIEF
 VALVE PER 504.2.
 7) SHT 2 OF 7 ROOM 128 STAFF LOUNGE, THE
 WATER HEATER SHALL BE ACCESSIBLE. PROVI-
 DE DETAILS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-12-15 Cont ID  
Sent By kstevens Date 2003-12-15 Time 09:06 Rev Time 1.25
Received By kstevens Date 2003-12-15 Time 09:06 Sent To  
Notes
2003-12-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) ALL CAPPED PLUMBING PIPES SHALL BE
 INSPECTED PRIOR TO COVERING. SEC 105.6
 2) IF TOILET FACILITIES ARE PROVIDED ON
 A SITE, THEN EACH SUCH PUBLIC OR COMMON
 USE TOILET FACILITY SHALL COMPLY WITH
 11-4.22. SECTION 11-4.1.1(6). SUBMIT A
 DETAIL FOR TOILET ROOMS SHOWING COMPLI-
 ANCE WITH 11-4.16, 11-4.19, 11-4.22 AND
 ALL SUBSECTIONS
 3) SHT 3 OF 7, ONLY THE FIXTURES WITHIN
 THE BATHROOM GROUPS SHALL CONNECT TO THE
 WET-VENTED HORIZONTL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. 909.1 - THE
 SINK FROM ROOM 128 SHALL CONNECT DOWN-
 STREAM OF THE TOILET ROOM FIXTURES.
 4) SINKS IN ROOMS 111 & 128 SHALL COMPLY
 WITH 11-4.24 AND ALL SUBSECTIONS. PROVI-
 DE DETAIL.
 5) 61G1-16.004(2) FIRM LICENSE NUMBER
 REQUIRED ON TITLE BLOCK. FS481.2055
 6) PROVIDE A WATER RISER DIAGRAM. SEC
 104.3.1.1(3).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-07-01 Cont ID  
Sent By mmclean Date 2004-07-01 Time 15:12 Rev Time 0.00
Received By mmclean Date 2004-07-01 Time 15:12 Sent To  
Notes
2004-07-01 00:00:00APPROVE PROPOSED CARPORT STORAGE.