Plan Review Details - Permit 03111252
Plan Review Stops For Permit 03111252
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-11-03 Cont ID  
Sent By shill Date 2004-11-03 Time 11:38 Rev Time 0.50
Received By shill Date 2004-11-03 Time 11:38 Sent To PC
Notes
2004-11-03 00:00:00REVISED ENERGY CALC

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-04-15 Cont ID  
Sent By csiegber Date 2004-10-28 Time 15:51 Rev Time 1.00
Received By shill Date 2004-04-15 Time 15:40 Sent To  
Notes
2004-04-15 00:00:00PROVISO - 1)SEPARATE PERMIT FOR FRONT
 DOOR2)BCLL TO BE MIN 10 FBCTABLE1604.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-03-30 Cont ID  
Sent By pkrauss Date 2004-04-13 Time 07:22 Rev Time 2.00
Received By shill Date 2004-03-26 Time 15:24 Sent To  
Notes
2004-03-26 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 3.)SEPARATE PERMITS REQUIRED.
  
 4.)THE PRODUCT APPROVALS SUBMITTED
 WERE FOR INSWING DOORS; PLAN SPECIFIES
 OUTSWING.EITHER SUBMIT OUTSWING DOOR
 PRODUCT APPROVALS OR REVISE THE PLAN.
  
 5.)ONE MEANS OF ESCAPE (DOOR) TO BE
 PROVIDED IN THE EVENT OF A HURRICANE,
 FBC1005.4.5.SUBMIT PRODUCT APPROVAL
 FOR THE IMPACT GLASS DOOR.
  
 5.)PROVISO - BCLL TO BE MINIMUM OF
 10, FBC TABLE 1604.1.
  
 **NO RESUB FEE**

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-03-05 Cont ID  
Sent By kstevens Date 2004-03-26 Time 14:30 Rev Time 1.50
Received By shill Date 2004-03-05 Time 10:34 Sent To  
Notes
2004-03-05 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A NOTE WAS ENCLOSED INDICATING THAT
 YOU WANTED FOR THIS PROJECT TO BE A
 MASTER.THIS MUST BE DONE ON A SEPARATE
 APPLICATION.SUBMIT TWO COPIES OF
 DRAWINGS WITH AN APPLICATION.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 3.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 4.)GENZ ENGINEERING MUST HAVE AN
 AUTHORIZATION NUMBER FROM THE BOARD OF
 PROFESSIONAL ENGINEERS TO PRACTICE
 ENGINEERING.THIS NUMBER MUST BE ON
 EACH SHEET.
  
 5.)FLOOR PLAN NOTE 4 (4.1) SHOWS 4.2
 INSULATION; R5 REQUIRED PER ENERGY CALC.
  
 6.)ATTIC ACCESS MINIMUM SIZE IS 20X36
 FBC2309.6.
  
 7.)THE SIMONTON 435 WINDOW IS NOT
 LISTED ON FLORIDA PRODUCT APPROVAL
 NUMBER 204.
  
 8.)PROVIDE A COPY OF THE TEST REPORT
 FOR THE MASONITE DOORS.
  
 9.)SEPARATE PERMITS REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-06 Cont ID  
Sent By dpalmer Date 2004-03-02 Time 13:57 Rev Time 3.50
Received By shill Date 2004-01-03 Time 21:12 Sent To  
Notes
2004-01-05 00:00:00*****CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A NOTE WAS ENCLOSED INDICATING THAT
 YOU WANTED FOR THIS PROJECT TO BE A
 MASTER.THIS MUST BE DONE ON A SEPARATE
 APPLICATION.SUBMIT TWO COPIES OF
 DRAWINGS WITH AN APPLICATION.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO
 THE APPLICATION.233-5025
  
 3.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 4.)THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT (GENZ) AND LICENSE
 NUMBER IS TO BE INCLUDED ON THE PLAN,
 AUTHORIZATION NUMBER FOR GENZ
 ENGINEERING TO BE ON THE TITLE BLOCK,
 FAC61G15-23.002(2).
  
 5.)ROOF SHEATHING, 3.1, CITY OF WEST
 PALM BEACH AMENDMENTS TO THE FBC
 TABLE 2306.1, THE 5' EDGE OF THE GABLE
 END IS ZONE 3.
  
 6.)ROOF NOTE 03, SHEET 3.1, ROOF
 SHEATHING IS TO BE A MINIMUM OF 19/22 IN
 SPANS OVER 16", CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC, REVISED PANEL
 SPAN TABLE 2307.6B.DETAILS ON THE
 PLAN SHOW 5/8.
  
 7.)FLOOR PLAN NOTE, 4 (4.1) SHOWS
 R4.2 INSULATION; R5 REQUIRED PER EN CALC
 WALL LEGEND SHOWS R3.
  
 8.)SHOW SIZE FOR ATTIC ACCESS, FBC
 2309.6.
  
 9.)FIREBLOCKING FOR STAIRS ARE TO BE
 FULL DEPTH AND AT THE TOP AND BOTTOM
 STRINGERS OF EACH RUN (STAIR SECTIONS).
 FBC2305.1.4.
  
 10.)SHEET 1.1, SITE PLAN SHOWS PART OF
 THE IMPROVEMENT ON LOT 23.SHOULD BE
 LOTS 7 AND 8.ALSO LEGAL REFERS TO
 "LOTS 7 AND 5", SHOULD BE "7 AND 8".
  
 11.)SEPARATE PERMITS REQUIRED.
  
 12.)THE BOTTOM CHORD LIVE LOAD FOR THE
 TRUSSES IS SHOWN AS 0.REFER TO FBC TABLE
 1604.1, RESIDENTIAL, DWELLINGS, ATTICS.
 (TRUSS SHOP DRAWINGS).
  
 13.)STATEWIDE PRODUCT APPROVALS ARE
 REQUIRED EFFECTIVE OCTOBER 1, 2003.
 SEE WWW.FLORIDABUILDING.ORG.I HAVE
 OBTAINED STATE PRODUCT APPROVAL NUMBERS
 FOR SOME PRODUCTS.PLEASE SUPPLY
 STATEWIDE APPROVALS FOR THE DOORS,
 TRACO WINDOWS, SHUTTERS.
  
 IN THE FUTURE, WHEN SUBMITTING FOR
 PERMITS, INCLUDE STATEWIDE PRODUCT
 APPROVAL NUMBERS WITH ALL TEST REPORTS.
 IF A PRODUCT DOES NOT HAVE A STATEWIDE
 PRODUCT APPROVAL, A SITE SPECIFIC WILL
 BE REQUIRED.IF IT IS DIFFICULT TO
 DETERMINE WHETHER A PRODUCT IS
 APPROVED (SUCH AS THE JELDWEN DOORS),
 PRINT THE COVER SHEET WITH APPROPRIATE
 PDF FILE CIRCLED FOR VERIFICATION.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-03-28 Cont ID  
Sent By dpalmer Date 2005-03-28 Time 14:51 Rev Time 0.30
Received By dpalmer Date 2005-03-28 Time 14:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-03-03 Cont ID  
Sent By dpalmer Date 2005-03-03 Time 08:01 Rev Time 0.25
Received By dpalmer Date 2005-03-03 Time 07:51 Sent To  
Notes
2005-03-03 00:00:00***UNSAT/NOTES ***
  
 1)NOTE: PLEASE SEE PLANS APPEAR TO BE
 REVISED FOR "FINAL" CO".
 PLEASE SEE KITCHEN STILL SHOWS AN
 OPTIONAL ISLAND WITH ELECTRICAL.
 IF THIS IS FOR FINAL PLANS NEED TO
 REFLECT WHEATHER OR NOT THAT "OPTION" IS
 INSTALLED.
  
 2)NOTE: PLEASE VERIFY IF PANELIS IN
 HALL.
 PANEL MENTIONS PANEL AS HALL/UTILITY.
 AS SHOWN ON PLANS, IF PANEL IS IN
 UTILITY CLOSET THEN CLEARENCE SOES NOT
 MEET 110.26.
  
 PLEASE VERIFY THE ABOVE INFORMATION, IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-03-02 Cont ID  
Sent By shill Date 2004-03-25 Time 11:27 Rev Time 0.50
Received By dpalmer Date 2004-03-02 Time 13:54 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-09 Cont ID  
Sent By pkrauss Date 2004-03-02 Time 12:22 Rev Time 0.75
Received By dpalmer Date 2003-12-09 Time 07:29 Sent To M
Notes
2003-12-09 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SEE PLANS, RISER SHOWS
 METER CAN FEEDING PANEL, HOWEVER PANEL
 IS SHOWN AS MLO? PLEASE CLARIFY WHERE
 MAIN IS?
  
 2)NOTE: PLEASE SUBMIT AIC RATING FOR
 MAIN. PANEL IS NOTED FOR BRANCH BRKRS.
 PER 110.9/ 215.5
  
 3)NOTE: PLEASE LIST THE REQ'D DEDICATED
 BATH CIRCUIT PER 210.11C3/210.52D. MUST
 BE 20A AND #12.
  
 4)NOTE: PLEASE SEE THAT PLANS MUST
 CONTAIN A COMPLETE SIGNATURE PER FS
 481.221 AND FAC 61G1-16.004
 THIS OFFICE HAS BEEN NOTIFIED BY THE
 STATE BOARD, A "SIGNATURE" SHOULD
 CONTAIN A MIN OF FIRST AND LAST NAME
 AND INITIALS ARE NOT ACCEPTABLE.
  
 5)NOTE: PLEASE SHOW RECEPT FOR ISLAND AS
 GFI/GFI PROTECTED. 210.8A6
  
 6)NOTE: PLEASE SEE THAT PANEL IS NOT
 PERMITTED IN WHAT APPEARS TO BE A
 STORAGE CLOSET. 384.7, 110.26 ETC.
 PLANS MUST SHOW THIS ROOM AS A DEDICATED
 MECH/ELEC RM. NO STORAGE PERMITTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-04-14 Cont ID  
Sent By adarroug Date 2005-04-14 Time 14:03 Rev Time 0.00
Received By adarroug Date 2005-04-14 Time 14:03 Sent To M
Notes
2005-04-14 00:00:00TO "M" BOX

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-03-23 Cont ID  
Sent By adarroug Date 2005-03-23 Time 15:54 Rev Time 0.00
Received By adarroug Date 2005-03-23 Time 15:54 Sent To E
Notes
2005-03-23 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-02-28 Cont ID  
Sent By adarroug Date 2005-02-28 Time 08:53 Rev Time 0.00
Received By adarroug Date 2005-02-28 Time 08:53 Sent To E
Notes
2005-02-28 00:00:00TO DPALMER DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-10-28 Cont ID  
Sent By csiegber Date 2004-10-28 Time 15:51 Rev Time 0.00
Received By adarroug Date 2005-02-28 Time 08:52 Sent To B
Notes
2004-10-28 00:00:00TO SH DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-04-07 Cont ID  
Sent By csiegber Date 2004-04-07 Time 11:22 Rev Time 0.00
Received By csiegber Date 2004-04-07 Time 11:22 Sent To M
Notes
2004-04-07 00:00:00TO PK BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-03-25 Cont ID  
Sent By shill Date 2004-03-25 Time 11:27 Rev Time 0.00
Received By shill Date 2004-03-25 Time 11:27 Sent To E
Notes
2004-03-25 00:00:00ROUTED TO WT FOR ELEC REVIEW OF MASTER
 #04031090 (SAME PLAN)

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-03-22 Cont ID  
Sent By csiegber Date 2004-03-22 Time 09:11 Rev Time 0.00
Received By csiegber Date 2004-03-22 Time 09:11 Sent To P
Notes
2004-03-22 00:00:00TO KS DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-20 Cont ID  
Sent By csiegber Date 2004-02-20 Time 14:37 Rev Time 0.00
Received By csiegber Date 2004-02-20 Time 14:37 Sent To P
Notes
2004-02-20 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-06 Cont ID  
Sent By mmclean Date 2003-11-25 Time 15:02 Rev Time 0.00
Received By shill Date 2003-11-25 Time 08:33 Sent To  
Notes
2003-11-26 00:00:00TO SFD RACK/E
2003-11-25 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-04-20 Cont ID  
Sent By prafter Date 2005-04-20 Time 07:42 Rev Time 0.45
Received By prafter Date 2005-04-20 Time 07:42 Sent To  
Notes
2005-04-20 00:00:00MECH. PLAN REVIEW.
 NEW ENERGY CALCULATIONS.
 PAT RAFTER 561/805/6728 OR 8056719
 PATTY KRAUSS.
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-04-13 Cont ID  
Sent By pkrauss Date 2004-04-13 Time 07:21 Rev Time 0.00
Received By prafter Date 2005-04-20 Time 07:40 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-03-02 Cont ID  
Sent By csiegber Date 2004-04-07 Time 11:25 Rev Time 0.33
Received By pkrauss Date 2004-03-02 Time 12:00 Sent To E
Notes
2004-03-02 00:00:00PROVISO:
 1.RETURN AIR TO THE MASTER BEDROOM IS
 NOT SIZED PROPERLY.ALL AIR TO THE
 MASTER SUITE TO BE INCLUDED FOR A TOTAL
 OF SUPPLY AIR TO THAT AREA.SEE THE
 ATTACHED SCHEDULE.REVISE MASTER SUITE
 TO REFLECT PROPER SIZE.
  
 2.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-12-10 Cont ID  
Sent By kstevens Date 2004-03-01 Time 11:34 Rev Time 0.50
Received By hmoser Date 2003-12-10 Time 19:34 Sent To P
Notes
2003-12-10 00:00:00PLAN DENIED
 1) REFER TO SECTION 307.2.3 AUXILIARY
 DRAIN PAN.AUXILIARY DRAIN PANS SHALL BE
 INSTALLED UNDER ALL COILS ON WITCH
 CONDENSATION WILL OCCUR.
 2) RETURN AIR REQUIREMENTS TO COMPLY
 WITH THE FLORIDA BUILDING CODE (M) 2003
 CHANGES.CHANGES WENT INTO EFFECT JULY 1
 2003
 3) NEED GRILL SIZES ON PLAN
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-03-26 Cont ID  
Sent By kstevens Date 2004-03-26 Time 14:30 Rev Time 0.33
Received By kstevens Date 2004-03-26 Time 14:30 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-03-01 Cont ID  
Sent By csiegber Date 2004-03-22 Time 09:11 Rev Time 0.50
Received By kstevens Date 2004-03-01 Time 11:34 Sent To M
Notes
2004-03-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) FROM THE PREVIOUS REVIEW. WASH
 MACHINE SHALL DISCHARGE DOWNSTREAM OF
 THE BATHROOM FIXTURES. SEE RED LINE
 CORRECTION. SECTION 909.1 WET VENT
 2) REMOVE ALL VOIDED SHEETS AND INSERT
 NEW SHEETS. SUBMIT ONE SET OF OLD PLANS
 FOR COMPARISON.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-12-10 Cont ID  
Sent By csiegber Date 2004-02-20 Time 14:43 Rev Time 0.33
Received By jleech Date 2003-12-10 Time 20:10 Sent To B
Notes
2003-12-10 00:00:00DENIED;
 SEE FBC PLUMBING SEC 909.1. W/M MUST
 HAVE IT'S OWN BRANCH DRAIN.
 KITCHEN SINK CANNOT RUN THRU BATHROOM 1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2003-11-25 Cont ID  
Sent By mmclean Date 2003-11-25 Time 15:02 Rev Time 0.00
Received By mmclean Date 2003-11-25 Time 15:02 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved