Plan Review Details - Permit 03111170
Plan Review Stops For Permit 03111170
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-09 Cont ID  
Sent By hmoser Date 2003-12-10 Time 17:01 Rev Time 2.50
Received By lsmith Date 2004-01-09 Time 14:54 Sent To  
Notes
2004-01-09 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE
 WEBSITEAT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3. A NOTICE OF COMMENCEMENT MUST BE
 FILED AT THE COUNTY CLERK OFFICE AND A
 COPYOF THE RECORDED NOC SUBMITTED TO
 THE CITY BEFORE A PERMT CAN BE ISSUED.
  
 4. THE "SITE SPECIFIC" PRODUCT APPROVAL
 SIGNED BY SCOTT B. DISHER IS MISSING A
 SIGNATURE AT #9.(DESIGN PROFESSIONAL OF
 RECORD. SPECIFY WHERE THE SINGLE
 INSWINGDOOR IS BEING INSTALLED.
  
 5. HIGHLIGHT THE GLASS BLOCK
 INFORMATION FOR THE KIND OF GLASS BLOCK
 BEING INSTALLED TO ASSURE FIRERATING (1
 HOUR).
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-12-04 Cont ID  
Sent By btrobaug Date 2003-12-04 Time 13:10 Rev Time 0.50
Received By btrobaug Date 2003-12-04 Time 12:54 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By mmclean Date 2003-11-25 Time 14:53 Rev Time 0.00
Received By csiegber Date 2003-11-21 Time 16:54 Sent To  
Notes
2003-11-26 00:00:00TO SFD RACK/E
2003-11-21 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-12-10 Cont ID  
Sent By jleech Date 2003-12-06 Time 09:12 Rev Time 0.50
Received By hmoser Date 2003-12-10 Time 17:01 Sent To B
Notes
2003-12-10 00:00:00PLAN DENIED
 1) REFER TO SECTION 307.2.3 AUXILIARY
 DRAIN PAN.AUXILIARY DRAIN PANS SHALL BE
 INSTALLED UNDER ALL COILS ON WITCH
 CONDENSATION WILL OCCUR.
 2) RETURN AIR REQUIREMENTS TO COMPLY
 WITH THE FLORIDA BUILDING CODE (M) 2003
 CHANGES.CHANGES WENT INTO EFFECT JULY 1
 2003
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-12-06 Cont ID  
Sent By jleech Date 2003-12-06 Time 09:11 Rev Time 0.33
Received By jleech Date 2003-12-06 Time 09:11 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-11-25 Cont ID  
Sent By mmclean Date 2003-11-25 Time 14:53 Rev Time 0.00
Received By mmclean Date 2003-11-25 Time 14:53 Sent To I
Notes
***NONE***