Plan Review Details - Permit 03111164
Plan Review Stops For Permit 03111164
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-06-02 Cont ID  
Sent By jwitmer Date 2005-06-02 Time 15:25 Rev Time 1.55
Received By jwitmer Date 2005-06-02 Time 15:25 Sent To PC
Notes
2005-06-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03111164
 ADD: 131 CORTEZ
 CONT: MARION CONSTRUCTION
 TEL: (561)662-3814
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISION
  
 ACTION: DENIED
  
 1) SABANA WINDOWS IS NOT LISTED ON THE
 FL STATE WEB SITE,
 WWW,"FLORIDABUILDING.ORG", A LOCAL
 PRODUCT APPROVAL WILL BE REQUIRED .
  
 2) THERE IS CUT SHEETS INDICATING USE OF
 A HORIZONTAL MULLION. THERE IS NO
 INDICATION OF MULLIONS BEING TESTED IN
 EITHER THE WINDOW OR DOOR REPORT.
  
 3) MULLIONS:
 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 4)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-02-09 Cont ID  
Sent By jwitmer Date 2004-02-09 Time 13:44 Rev Time 2.00
Received By jwitmer Date 2004-02-09 Time 13:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-02-02 Cont ID  
Sent By jwitmer Date 2004-02-02 Time 10:37 Rev Time 2.50
Received By jwitmer Date 2004-02-02 Time 10:37 Sent To  
Notes
2004-02-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03111164
 ADD: 131 CORTEZ RD
 CONT: MARION CONSTRUCTION
 TEL: (561)662-3814
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL
 OF RECORD.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-09 Cont ID  
Sent By pkrauss Date 2004-01-28 Time 07:41 Rev Time 10.00
Received By jwitmer Date 2004-01-08 Time 07:03 Sent To PC
Notes
2004-01-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03111164
 ADD: 131 CORTEZ RD
 CONT: MARION CONSTRUCTION
 TEL: (561)###-####
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 NOTE:
  
 1) PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUTION WITH
 BASE FLOOD ELEVATION, CITY CODE REQUIRES
 AN ADDITIONAL 6".
  
 2) NOTE: FUTURE POOL VS FOUNDATION
 1803.1.3 EXCAVATION FOR ANY PURPOSE
 SHALL NOT EXTEND WITHIN 1 FT OF THE
 ANGLE OF REPOSE OR NARURAL SLOPE OF THE
 SOIL UNDER ANY FOOTING OR FOUNDATION,
 UNLESS SUCH FOOTING OR FOUNDATION IS
 FIRST PROPERLY UNDERPINNED OR PROTECTED
 AGAINST SETTLEMENT.
  
 3) ICYNENE INSULATION:
 2309.7.1 VENTILATION OF ATTIC SPACE
 103.7 ALTERNATE MATERIALS & METHODS
 PALM BEACH COUNTY ADVISORY BOARD RECON-
 IZES THE APPLICABILITY AND USE OF UNVENT
 ED ATTIC SYSTEMS IN HOT, HUMID CLIMATES
 SUCH AS PALM BEACH COUNTY, UNDER THE
 FOLLOWING MINIMUM RECOMMMENDED CONDI-
 TIONS:
 A) UNVENTED ATTIC SYSTEMS/ ASSEMBLIES
 ARE DESIGNED BY A FLORIDA REGISTERED
 DESIGN PROFESSIONAL.
 B) INSULATION MUST BE INSTALLED CONTIN_
 UOUSLY IN THE UPPER PLAN OF THE ROOF ASS
 EMBLY"S DECK/SHEATHING WITH SPECIFIED,
 APPROVED INSULATION PRODUCTS, AND THE
 CEILING PLANE (SPACE) IS NOT SEPERATED
 FROM CONDITIONED HABITABLE SPACE BELOW,
 WITH INSULATION.
 C) WHEN UNVENTED ATTIC SYSTEMS ARE SPEC
 IFIED IN CONJUNCTION WITH ASPHALT BASED
 ROOFING PRODUCTS, THE ROOFING MATERIAL/
 SYSTEM MANUFACTURER SHALL PROVIDE AN AFF
 IDAVIT CERTIFYING USE OF THEIR PRODUCT
 OVER AN UNVENTED ATTIC SYSTEM.
  
 4)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A-11, MASTER BEDROOM FLOOR BELOW
 IS EXTERIOR SPACE, ICYNENE IS INDICATED
 AS THE TYPE OF INSULATION TO BE USED.
 TO THE RIGHT, ON THE 1ST FLOOR THERE IS
 A CBS EXTERIOR WALL, BUT THE INSULATION
 BETWEEN THE FIRST FLOOR CEILING CONDITIO
 NED SPACE AND SECOND FLOOR IS THE SAME
 SYMBLE FOR INSULATION, TYPE OF INSULA-
 TION IS NOT CALLED OUT. NOTE COMMENT 3-C
  
 5)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A-13 SCHEDULE NOT COMPLETE.
  
 6) A SHEET OF LINED PAPER PART OF THE
 PRODUCT APPROVAL PACKAGE NOTING THAT THE
 FRONT DOOR AND GARAGE DOOR NOT PICKED
 OUT, WILL FOLLOW LATER. EITHER PRODUCT A
 PPROVALS ARE SUBMITTTED AT THE TIME OF
 APPLICATION OR AT TIME OF ISSUANCE THESE
 REPORTS ARE STILL MISSING, A SEPERATE
 PERMIT WITH ASSOCIATED FEES AND REVIEW
 WILL OCCUR.
  
 7) THE FRONT DOOR BEING A CUSTOM MAHOG-
 ANY SPECIALTY DOOR WOULD REQUIRE:
 SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL
 OF RECORD.
  
 8)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 DISCREPANCY, SHEET A-2 INDICATES WINDOW
 "Z" AS A DOUBLE CASEMENT WINDOW, SHEET
 A-15 "Z" INDICATES "3" WINDOWS MULLED
 TOGETHER?
  
 10)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) FIXED WINDOWS
  
 11) THERE ARE 2 COPIES OF STORM SHUTTER
 PRODUCT APPROVALS WHERE ARETHEY TO BE US
 ED?
  
 12)FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 13) 2305.2.2 FLOOR/CEILING ASSEMBLIES
 SINGLE FAMILY DWELLINGS. IN FLOOR/CEIL/
 ING ASSEMBLIES SEPERATING USEABLE SPACE
 INTO 2 OR MORE APPROXIMATE AREAS WITH NO
 AREA GREATER THAN 500 SQ FT. DRAFTSTOP-
 PING SHALL BE PROVIDED PARALLEL TO THE
 MAIN FRAMING MEMBERS.
  
 14)FL BLD CODE 2309.6 ATTIC ACCESS, PRO-
 VIDE ATTIC ACCESS 20"X36". WHERE IS THE
 ATTIC ACCESS FOR THE 2ND STORY ATTIC?
  
 15)SHEET A-8 FRONT ENTRY INDICATES THE
 USE OF 2X12 OUTLOOKERS, NO STRAPPING S-5
 DETAIL# 3 BACK TO COMMON TRUSSES?
  
 16) SHEET S-5 ADDITIONAL INFO:
 DETAILS:LEDGER, "SEE PLAN", SIZE, &
 SPACING OF ANCHOR BOLTS?
  
 17)1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 18)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-01-23 Cont ID  
Sent By csiegber Date 2004-02-06 Time 09:19 Rev Time 2.00
Received By dpalmer Date 2004-01-23 Time 12:05 Sent To P
Notes
2004-01-23 00:00:00************ PROVISO/ NOTES ************
 THE FOLLOWING IS ONLY BASED ON ALL
 OTHER REVIEWS PASSING. IF PLANS GO BACK
 FOR COMMENTS FOR ANY OTHER TRADES, PLANS
 NEED TO BE CORRETCED.
  
  
 1)NOTE: PLEASE SEE LOAD CALCULATIONS,
 SHOWS ALL AHU'S AT 10KW, HOWEVER PANEL
 SCHEDULE SHOWS AHU# 4 W/ 45A OCP.
 PLEASE SEE 424.3B FOR MIN OCP 125%.
  
 2)NOTE: PLEASE LIST THE REQ'D ARC FAULT
 ON PANEL SCHEDULE(S) AS REQUESTED ON
 PREVIOUS REVIEW. 210.12
  
 3)NOTE: PLEASE LIST REQ'D DEDICATED
 BATH(S) CIRCUIT(S) ON PANEL SCHEDULE.
 REQUESTED ON FIRST REVIEW. 210.11C3
 210.52D
  
 PLEASE SUBMIT THIS AND ALL OTHER
 REVISIONS BEFORE ROUGH INSPECTION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-10 Cont ID  
Sent By csiegber Date 2004-01-16 Time 16:37 Rev Time 4.00
Received By dpalmer Date 2003-12-09 Time 13:17 Sent To M
Notes
2003-12-10 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE SEE NFPA-72 8-1.4.2
 SD'S ARE REQD' IN SIDE AND OUTSIDE ALL
 SLEEPING ROOMS. EACH LEVEL OF A MULTI-
 -LEVEL DWELLING AND IN THE VICINITY OF
 STAIRWAYS.
  
 2)NOTE: PLEASE SEE 210.52 FOR A COUPLE
 OF MISSING RECEPTS.
  
 3)NOTE: PLEASE SEE 210.8A6 FOR ALL
 RECEPTS SERVING KITCHEN COUNTERSPACE TO
 BE GFI/GFI PROTECTED. PLEASE SHOW OR
 INDICATE.
  
 4)NOTE: PLEASE SUBMIT COMPLETE PANELS
 SCHEDULES SHOWING ALL MIN REQ'D CIRCUITS
 PER 210.52,210.11,210.12, ETC ETC.
 PLEASE SHOW OCP , AWG ALSO.
  
 5)NOTE: PLEASE HAVE PLANS SIGNED, DATED
 AND SEALED BY THE ARCH OF RECORD PER
 FS 481.221 AND FAC 61G1-16
  
 6)NOTE: PLEASE SHOW ALL CONDUCTOR SIZES
 ON RISER DIAGRAM. 310.16/215.5
  
 7)NOTE: PLEASE SEE THAT "SERVICE" SIZE
 IS INDICATED AT 450A'S AND ONLY SHOWS
 A 400A METERCAN. PLEASE ADJUST.
  
 8)NOTE: PLEASE SUBMIT SPECS/ MANF INFO
 ON TRANSFER SWITCH AND HOW SWITCHING
 WILL BE. 230.74,230.75,230.82 ETC.
  
 9)NOTE: PLEASE SEE THAT TRANSFER SWITCH,
 CONDUCTORS,GUTTER, AND MAINS MAY NOT BE
 INSTALLED AS SHOWN. IF SERVICE STAYS
 "AS-IS" THEN A MAIN W/ OCP WOULD BE
 REQ'D INFRONT OF TANSFER SW. IF THIS IS
 NOT GOING TO BE DONE THEN PLEASE ADJUST/
 RECONFIGURE SERVICE.
 240.21, 230.76, 230.79,230.42 ETC.
  
 10)NOTE: PLEASE AIC RATINGS FOR ALL NEW
 EQUIPMENT BBEING INSTALLED. MAINS, BRKRS
 PANELS ARE ALL TO BE RATED FOR THE AVAIL
 -ABLE FAULT CURRENT. 110.9/215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
2003-12-09 00:00:00NOTES TO FOLLOW

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-08-23 Cont ID  
Sent By adarroug Date 2005-08-23 Time 17:08 Rev Time 0.00
Received By adarroug Date 2005-08-23 Time 17:08 Sent To B
Notes
2005-08-23 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-06-01 Cont ID  
Sent By adarroug Date 2005-06-01 Time 08:08 Rev Time 0.00
Received By adarroug Date 2005-06-01 Time 08:08 Sent To B
Notes
2005-06-01 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-05-24 Cont ID  
Sent By adarroug Date 2005-05-24 Time 14:41 Rev Time 0.00
Received By adarroug Date 2005-05-24 Time 14:41 Sent To B
Notes
2005-05-24 00:00:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-02-06 Cont ID  
Sent By csiegber Date 2004-02-06 Time 09:19 Rev Time 0.00
Received By csiegber Date 2004-02-06 Time 09:19 Sent To E
Notes
2004-02-06 00:00:00TO JW DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-16 Cont ID  
Sent By csiegber Date 2004-01-16 Time 16:37 Rev Time 0.00
Received By csiegber Date 2004-01-16 Time 16:37 Sent To E
Notes
2004-01-16 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-09 Cont ID  
Sent By csiegber Date 2004-05-05 Time 16:12 Rev Time 0.00
Received By csiegber Date 2003-11-21 Time 09:28 Sent To  
Notes
2003-12-03 00:00:0011/24/03 TO Z
 12/3/03 TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-01-11 Cont ID  
Sent By pkrauss Date 2005-01-11 Time 15:37 Rev Time 0.35
Received By pkrauss Date 2005-01-11 Time 15:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-28 Cont ID  
Sent By pkrauss Date 2004-01-28 Time 07:41 Rev Time 0.35
Received By pkrauss Date 2004-01-28 Time 07:24 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-02 Cont ID  
Sent By kstevens Date 2004-01-24 Time 12:01 Rev Time 0.50
Received By hmoser Date 2003-12-15 Time 16:37 Sent To B
Notes
2003-12-15 00:00:00PLAN DENIED
 1) REFER TO SECTION 307.2.3 AUXILIARY
 DRAIN PAN.AUXILIARY DRAIN PANS SHALL BE
 INSTALLED UNDER ALL COILS ON WITCH
 CONDENSATION WILL OCCUR.
 2) RETURN AIR REQUIREMENTS TO COMPLY
 WITH THE FLORIDA BUILDING CODE (M) 2003
 CHANGES.CHANGES WENT INTO EFFECT JULY 1
 2003
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-01-24 Cont ID  
Sent By kstevens Date 2004-01-24 Time 12:00 Rev Time 0.50
Received By kstevens Date 2004-01-24 Time 12:00 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-01-02 Cont ID  
Sent By dpalmer Date 2004-01-23 Time 12:28 Rev Time 0.50
Received By hmoser Date 2003-12-10 Time 19:55 Sent To M
Notes
2003-12-10 00:00:00DENIED;
 1.RISER DIAGRAM DOESNOT FOLLOW FLOOR
 PLAN.
 2.BATH 1 CANNOT BE ON THE SAME STACK AS
 MASTER BATHROOM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status N Date 2003-12-02 Cont ID  
Sent By mmclean Date 2003-12-02 Time 16:51 Rev Time 0.00
Received By mmclean Date 2003-12-02 Time 16:51 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2003-12-02 Cont ID  
Sent By sgraham Date 2003-12-02 Time 11:47 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-11-25 Cont ID  
Sent By csiegber Date 2003-11-24 Time 13:48 Rev Time 0.00
Received By mmclean Date 2003-11-25 Time 15:50 Sent To  
Notes
2003-11-25 00:00:0011/25/03 DENIED, 7' OVER HEIGHT REQ
 SHOULD BE 33' CALLED CONTR FILE M MM