Plan Review Details - Permit 03111103
Plan Review Stops For Permit 03111103
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-01-22 Cont ID  
Sent By rbrown Date 2004-01-22 Time 10:19 Rev Time 0.00
Received By rbrown Date 2004-01-22 Time 10:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-12-23 Cont ID  
Sent By hmoser Date 2004-01-21 Time 16:29 Rev Time 0.00
Received By rbrown Date 2003-12-23 Time 16:31 Sent To  
Notes
2003-12-23 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) FBC 704 & FBC 705WALL AND DOOR FIRE
 RESISTANCE.SHEET A.2.THE WALLS AT
 DOORS 01, 27 AND 31 SHALL BE 1-HOUR
 FIRE-RESISTANT. AMEND THE LEGEND.ALSO,
 DOORS 01, 27 AND 31 (AND DOOR 26) ARE
 NOT SHOWN ON THE DOOR SCHEDULE
 (SHEET A-11) AS FIRE-RATED.AMEND THE
 DOOR SCHEDULE.
  
 3) FBC 2405.2SAFETY GLAZING. REFERENCE
 NOTE K, ON SHEET A-11, SPECIFYING
 TEMPERED GLASS IN DOORS, SIDELIGHTS AND
 VISION PANELS IS NOTED.THE GLAZING IN
 THE SEMINAR AND CONFERENCE ROOM WALLS IS
 ALSO IN A 'HAZARDOUS LOCATION' AND IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 4) FBC 11-4.24.3PANTRY SINK
 ACCESSIBILTY.SHEET A-8, ELEVATION 6
 AND SHEET A-10, SECTION 1.KNEE
 CLEARANCE THAT IS AT LEAST 27" HIGH,
 30" WIDE AND 19" DEEP SHALL BE PROVIDED
 UNDERNEATH THE SINK.AMEND THE PLANS.
  
 5) FBC 11-4.13.6MANEUVERING CLEARANCES
 AT DOOR 27. ANNOTATE SHEET A-2 TO ENSURE
 18" CLEARANCE BETWEEN THE STRIKE EDGE OF
 THE DOOR AND THE ADJACENT WALL, ON THE
 PULL-SIDE OF THE DOOR.
  
 6) FBC 11.4.1.3(10)DRINKING FOUNTAIN.
 DOES THE PROPOSED WORK AFFECT THE
 DRINKING FOUNTAIN PROVISION FOR THIS
 FLOOR?AMEND THE PLAND TO SHOW THE
 LOCATION OF THE DRINKING FOUNTAIN(S).
 IF A NEW DRINKING FOUNTAIN IS TO BE
 PROVIDED, SUBMIT DETAILD TO DEMONSTRATE
 COMPLIANCE WITH FBC 11-4.15.
  
 7 ) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-01-26 Cont ID  
Sent By dpalmer Date 2004-01-26 Time 15:47 Rev Time 0.33
Received By dpalmer Date 2004-01-26 Time 15:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-01-09 Cont ID  
Sent By dpalmer Date 2004-01-09 Time 15:26 Rev Time 0.25
Received By dpalmer Date 2004-01-09 Time 15:24 Sent To  
Notes
2004-01-09 00:00:00******** UNSAT *******
  
 1)NOTE: PLEASE SEE E4.1, FA 0.1,2.1
 NEEDS SIGNATURE.
 PLEASE SIGN BOTH SETS.
 471.025/61G15-23.002
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-11-26 Cont ID  
Sent By jleahy Date 2003-11-26 Time 10:56 Rev Time 1.00
Received By jleahy Date 2003-11-26 Time 10:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-01-29 Cont ID  
Sent By mcarsill Date 2004-01-29 Time 14:53 Rev Time 0.00
Received By mcarsill Date 2004-01-29 Time 14:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-01-09 Cont ID  
Sent By mcarsill Date 2004-01-09 Time 12:51 Rev Time 0.00
Received By mcarsill Date 2004-01-09 Time 12:51 Sent To  
Notes
2004-01-09 00:00:00APPROVED PROVISO:
  
 FIRE ALARM NOTES # 17 IS STILL
 INCORRECT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-12-08 Cont ID  
Sent By mcarsill Date 2003-12-08 Time 12:18 Rev Time 0.00
Received By mcarsill Date 2003-12-08 Time 12:18 Sent To  
Notes
2003-12-08 00:00:001) FIRE ALARM NOTES # 17 IS INCORRECT.
 FIRE ALARM CIRCUITS SHALL BE CLASS A,
 STYLE D, NOT CLASS B, STYLE C.
  
 2) ANY CHANGES TO FIRE SPRINKLER
 SYSTEM. SEPARATE PLANS AND PERMITS.
  
 3) DOORS IN RECEPTION SWING IN. WHY
 DONT THEY SWING OUT DUE TO OCCUPANT
 LOAD.
  
 4) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-01-23 Cont ID  
Sent By csiegber Date 2004-01-23 Time 11:59 Rev Time 0.00
Received By csiegber Date 2004-01-23 Time 11:59 Sent To  
Notes
2004-01-23 00:00:00TO COMM BD#39

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-08 Cont ID  
Sent By csiegber Date 2004-01-08 Time 15:11 Rev Time 0.00
Received By csiegber Date 2004-01-08 Time 15:11 Sent To  
Notes
2004-01-08 00:00:00TO COMM BD#56

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-12-23 Cont ID  
Sent By rbrown Date 2004-01-30 Time 12:34 Rev Time 0.00
Received By rbrown Date 2003-11-24 Time 14:19 Sent To  
Notes
2003-11-24 00:00:00TO COMM BD#51

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-01-29 Cont ID  
Sent By pkrauss Date 2004-01-29 Time 08:09 Rev Time 0.40
Received By pkrauss Date 2004-01-29 Time 07:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-21 Cont ID  
Sent By hmoser Date 2004-01-21 Time 16:29 Rev Time 1.00
Received By hmoser Date 2004-01-21 Time 16:29 Sent To  
Notes
2004-01-21 00:00:00PASS PRIVISO
 REFER TO SECTION 307.2.4 SECONDARY DRAIN
 SYSTEM.WHERE AN AUXILIARY DRAIN CANNOT
 BE INSTALLED UNDER UNITS.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-01-21 Cont ID  
Sent By pkrauss Date 2003-12-15 Time 07:54 Rev Time 0.55
Received By hmoser Date 2003-12-15 Time 07:39 Sent To  
Notes
2003-12-15 00:00:00DENIED:
 EQUIPMENT ROOM #126 AND THE ALCOVE NEAR
 CORRIDOR #147 ARE INDICATED AS A NEW
 FIRE RATED PARTITION.PLANS DO NOT
 INDICATE FIRE DAMPERS ON THE MECHANICAL
 PLANS.
  
 2001 FBC(M) 607.6, SPECIFIC LOCATIONS
 AND INSTALLATION DETAILS SHALL BE
 SHOWN AND IDENTIFIED ON THE BUILDING
 PLANS.PLEASE PROVIDE A NOTE SHOULD
 ANY OF THE PENETRATIONS COMPLY WITH
 THE EXCEPTIONS UNDER 607.1.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-01-28 Cont ID  
Sent By kstevens Date 2004-01-28 Time 18:53 Rev Time 0.25
Received By kstevens Date 2004-01-28 Time 18:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-01-17 Cont ID  
Sent By kstevens Date 2004-01-17 Time 15:03 Rev Time 0.25
Received By kstevens Date 2004-01-17 Time 15:03 Sent To  
Notes
2004-01-17 00:00:00DENIED
 REFERENCE: FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1) - PER FBPE
 RULING, INITIALS ARE NOT ACCEPTABLE.
 SIGNATURE REQUIRED ON ALL SHEETS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-12-13 Cont ID  
Sent By kstevens Date 2003-12-13 Time 13:11 Rev Time 0.50
Received By kstevens Date 2003-12-13 Time 12:51 Sent To  
Notes
2003-12-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) SHT P0.1 WATER ISOMETRIC, WATER HAM-
 MER ARRESTOR SHALL BE LOCATED NEAR THE
 FIXTURE IN AN "EFFECTIVE RANGE" NOT IN
 THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALL. INSTRUC. (SEE NOTE #13)
 2) ENGINEERS SIGNATURE REQUIRED ON SEAL.
 61G15-23.002(1) & FS 471.025 PER FBPE &
 BLDG OFFICIAL.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]