Plan Review Details - Permit 03111080
Plan Review Stops For Permit 03111080
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-07-15 Cont ID  
Sent By alange Date 2004-07-15 Time 13:56 Rev Time 0.50
Received By alange Date 2004-07-15 Time 13:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-07-02 Cont ID  
Sent By alange Date 2004-07-02 Time 15:08 Rev Time 0.50
Received By alange Date 2004-07-02 Time 15:08 Sent To  
Notes
2004-07-02 00:00:00DENIED
 SEE SAME NOTES FROM 1ST AND 2ND
 REVIEW:
 PRODUCT APPROVALS FOR EXTERIOR DOORS AND
 WINDOWS NOT SUBMITTED. SUBMIT 2 COPIES.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-06-15 Cont ID  
Sent By alange Date 2004-06-15 Time 14:08 Rev Time 0.50
Received By alange Date 2004-06-15 Time 14:08 Sent To  
Notes
2004-06-15 00:00:00DENIED
 NOTE FROM SECOND REVIEW:
 PRODUCT APPROVALS FOR EXTERIOR DOORS AND
 WINDOWS NOT SUBMITTED.
 SUBMIT 2 COPIES.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-05-10 Cont ID  
Sent By alange Date 2004-05-10 Time 15:22 Rev Time 0.50
Received By alange Date 2004-05-10 Time 15:22 Sent To  
Notes
2004-05-10 00:00:00DENIED
 NOTE FROM FIRST REVIEW.
 PRODUCT APPROVALS NOT SUBMITTED.
 SUBMIT 2 COPIES FOR EXTERIOR WINDOWS AND
 DOORS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-12-22 Cont ID  
Sent By alange Date 2003-12-22 Time 08:03 Rev Time 1.00
Received By alange Date 2003-12-22 Time 08:03 Sent To  
Notes
2003-12-22 00:00:001. SUBMIT WINDOW PRODUCT APPROVALS.
 2.WINDOW BUCKS TO COMPLY WITH
 FBC 1707.4.4.2
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2005-09-20 Cont ID  
Sent By dpalmer Date 2005-09-20 Time 10:01 Rev Time 0.40
Received By dpalmer Date 2005-09-20 Time 10:01 Sent To  
Notes
2005-09-20 00:00:00210.8A6

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2005-08-10 Cont ID  
Sent By dpalmer Date 2005-08-10 Time 18:42 Rev Time 0.75
Received By dpalmer Date 2005-08-10 Time 18:42 Sent To  
Notes
2005-08-10 00:00:00****** REVISION UNSAT *********
  
  
 1)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 PLEASE NOTICE THERE ARE MORE THAN 75
 RECESSED LT FIXTURES.
  
 2)NOTE: PLEASE CORRELATE ALL CIRCUITING
 ON PLANS WITH THE REVISED SUBMITTED
 PANEL SCHEDULE.
 PLEASE SEE DINING RM CIRCUIT NOT ON
 PLANS? ETC.
 215.5
  
 3)NOTE: PLEASE SEE 210.52B1, WHICH
 REQUIRES DINING RM TO BE ON THE ONE OR
 MORE 20, #12, SMALL APPLIANCE CIRCUITS.
 PLEASE SEE DINING RM CIRCUIT ON PANEL
 SCHEDULE IS SHOWN AS #14 AWG AND 15A?
  
 4)NOTE: PLEASE SHOW ALL ROOM/AREA
 DESIGNATIONS TO PLANS.
 215.5
  
 5)NOTE: PLEASE SEE 410.8 FOR MIN
 CLEARENCE REQUIRED FOR RECESSED LTS IN
 CLOSETS. PLEASE SEE SOME APPEAR TO BE
 LOCATED TOO CLOSE TO POSSIBLE SHLEVING
 AREAS. THIS IS ONLY A NOTE AS NO
 SHELVING IS SHOWN. PLEASE SEE A MIN OF
 18" IS TO BE PROVIDED FOR SHELVING AND
 THEN MIN CLEARENCE IS REQUIRED AFTER THE
 18". PLEASE VERIFY THESE MIN AREAS.
  
 6)NOTE: PLEASE SEE MISSING GFI RECEPT
 ALONG KITCHEN COUNTERSPACE. 210.52C1
  
 7)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52, WITH IN 6' OF DOOR WAY? DINING
 AREA? BEDRM?
  
 8)NOTE: PLEASE SEE GEN LT/RECEPT CIRCUIT
 SHOWN WITH A #10 EQUIPMENT GROUNDING
 CONDUCTOR?? MISPRINT?
 250.122
  
  
 PLEASE SEE MANY OF THE ABOVE ITEMS HAVE
 BEEN REDLINEDS ON PLANS AT LOCATION SOF
 THE ABOVE COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL THIS
 OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2004-07-15 Cont ID  
Sent By dpalmer Date 2004-07-15 Time 13:46 Rev Time 0.33
Received By dpalmer Date 2004-07-15 Time 13:46 Sent To  
Notes
2005-08-10 00:00:00REDLINED AHU 424.3B

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2004-07-06 Cont ID  
Sent By dpalmer Date 2004-07-06 Time 14:20 Rev Time 1.00
Received By dpalmer Date 2004-07-06 Time 14:10 Sent To  
Notes
2004-07-06 00:00:00************ UNSAT 5TH TIME *********
  
 1)NOTE: PLEASE SEE 2002 NEC 210.12
 PLEASE LIST THE REQUIRED ARC FAULT
 PROTECTED CIRCUITS.
 THIS IS REQUIRED FOR ALL "OUTLETS" IN
 BEDROOMS, INCLUDING SD'S, LTS, RECEPTS,
 FANS.
 THIS HAS BEEN REQUESTED ON THE PREVIOUS
 FOUR REVIEWS.
  
 2)NOTE: PLEASE SEE THERE ARE A FEW
 RECEPTS WITH CIRCUIT #'S MISSING.
 PLEASE SEE # OF RECEPTS ON CIRCUIT #5
 180 VA PER RECEPT.?
  
  
 ** PLEASE SEE ATTACHED BZ RECEIPT,
 A 4X FEE HAS NOW BEEN ACCESSED FOR PLAN
 REVIEW COMMENTS AS SET FORTH FOR BLDG
 AND ELECTRICAL COMMENTS.
 A NOTICE WAS GIVEN ON PREVIOUS REVIEWS,
 PER FS 553.80(2)(B).
 THIS FEE IF $1,218.00 IS REQUIRED TO BE
 PAID BEFORE RESUBMITTING PLANS.
 ONCE MORE, ONE SET OF PLANS ARE BEING
 RETAINED AND MAY BE SENT TO FBPE'S FOR
 REVIEW OF CODE COMPLIANCE ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
 AS TO DATE NO PHONE CALLS HAVE BEEN
 RECIEVED FROM DESIGN PROFESSIONAL TO GO
 OVER COMMENTS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-06-10 Cont ID  
Sent By dpalmer Date 2004-06-10 Time 16:12 Rev Time 1.00
Received By dpalmer Date 2004-06-10 Time 16:08 Sent To  
Notes
2004-06-10 00:00:00************ UNSAT 4TH TIME ***********
  
 PLEASE SEE NOTES FROM PREVIOUS REVIEWS.
 PLEASE SEE ONLY TWO OF THE PREVIOUS
 6 NOTES WERE ADDRESSED.
  
 1)NOTE:
 NOTE #1OK. TURQUOISE ENG NAME WAS
 REMOVED.
  
 2)NOTE:
 NOTE #2 NO. PLEASE SHOW "ALL" CIRCUITING
 ON PLANS AND CORRELATE WITH THE SUBMITT-
 -ED PANEL SCHEDULE. PLEASE SEE 2002 NEC
 FOR ALL MIN CIRCUITS REQUIRED IN A
 DWELLING UNIT. WASHER? DRYER? 215.5,
 220.16,220.18,
  
 3)NOTE:
 NOTE #3OK
  
 4)NOTE:
 NOTE #4NO, SOME RECEPTS STILL MISSING
 FOR 2' OF WALL SPACE.
  
 5)NOTE:
 NOTE #5 NO, PLEASE LIST THE REQUIRED
 ARC FAULT PROTECTED CIRCUITS PER 2002
 NEC 210.12
 PLEASE SEE 2002 NEC REQUIRES THIS FOR
 LTS/SD'S RECEPTS/FANS ETC. ALL "OUTLETS"
 IN SLEEPING RMS.
  
 6)NOTE:
 NOTE #6NO, PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 PLEASE SEE ONE OF THESE SETS ARE NOW
 BEING RETAINED ALSO DUE TO REPEAT
 COMMENTS.
 PLEASE ALSO SEE ATTACHED COPY OFTHE
 FS 553.80(2)(B). IF ANY OF THE COMMENTS
 FOR CODE COMPLIANCE ARE NOT ADDRESSED
 ON NEXT REVIEW A 4X FEE WILL BE ACCESSED
 TO THE DESIGN PROFESSIONAL.
 ****PLEASE SEE ATTACHED COPY*****
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 ONCE AGAIN, PLEASE DO NOT HESITATE TO
 CALL. AS OF THIS REVIEW, DESIGNER OF
 RECORD HAS NOT CONTACTED ELECTRICAL
 PLAN REVIEW STAFF FOR ANY QUESTIONS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-05-08 Cont ID  
Sent By dpalmer Date 2004-05-08 Time 16:48 Rev Time 0.75
Received By dpalmer Date 2004-05-08 Time 16:48 Sent To  
Notes
2004-05-08 00:00:00******** UNSAT **********
  
 PLEASE SEE NOTES FROM FIRST TWO
 REVIEWS HAVE STILL NOT BEEN ADDRESSED.
 PLEASE SEE THE FOLLOWING.
  
 1)NOTE: PLANS MUST CONTAIN ALL LICENSE
 #'S ON TITLE BLOCK AS REQ'D UNDER FAC
 61G15-23.002. PLEASE SEE FS 471.023
 TURQUOIUSE INC. MUST HAVE A CA#.
 THERE IS NO CA# FOUND WITH DBPR/ FBPE'S
 THIS COMMENT HAS BEEN MADE ON PREVIOUS
 REVIEWS ON THIS PROJECT AND OTHER
 PROJECTS SUBMITTED TO THE CITY OF WPB
 FOR PERMIT.
 PLEASE ALSO SEE FS 471.025, DATE MUST
 ALSO BE SIGNED ON PLANS WHEN ENGINEER
 SIGNS HIS/HER SIGNATURE.
 WE ARE NOW RETAINING ONE SET OF PLANS
 TO BE TURNED OVER TO FBPE'S FOR REVIEW
 FOR ABOVE MENTIONED.
  
 2)NOTE: PLANS MUST SHOW ALL MIN CIRCUIT-
 -ING AS SET FORTH PER 2002 NEC.
 PLEASE SHOW CIRCUITS ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULE.
  
 3) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 4)NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE. MISSING SOME.
  
 4 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 5 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-12-02 Cont ID  
Sent By dpalmer Date 2003-12-02 Time 05:15 Rev Time 0.25
Received By dpalmer Date 2003-12-02 Time 05:13 Sent To  
Notes
2003-12-02 00:00:00********** UNSAT *****************
  
 1)NOTE: PLEASE SEE ELECTRICAL REVIEW
 NOTES FROM JAKE LEAHY DATED 11/24/03
  
 2)NOTE: PLEASE SEE THAT BOTH SETS OF
 PLANS ARE REQ'D TO BE SIGNED, DATED AND
 SEALED WITH ORIGINAL SIGNATURE ETC.
 PLEASE SEE THAT INITIALS ARE NOT PERMITT
 -ED. PLEASE SIGN WITH COMPLETE SIGNATURE
 THE ABOVE IS PER FS 471.025 AND FAC
 61G15-23.002, AND FBPE'S.FS 471.023
 TITLE BLOCK PRINTED NAME AND LICENSE #'S
  
 PLEASE ADDRESS ABOVE COMMENTS AND
 COMMENTS FROM OTHER REVIEWER.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-11-24 Cont ID  
Sent By jleahy Date 2003-11-24 Time 09:03 Rev Time 1.00
Received By jleahy Date 2003-11-24 Time 08:28 Sent To  
Notes
2003-11-24 00:00:001) BEDROOMS NEED TO BE ON ARC FAULT
 CIRCUIT BREAKERS
 2)SWITCH BY SLIDING DOOR NEAR KITCHEN
 HAS NO LOAD.
 3) SWITCH LEG FOR LIVING ROOM LIGHTS
 LOOK INCOMPLETE. ALSO THERE IS THREE
 FIXTURES THAT HAVE NO SWITCH LEG SHOWN.
 4) DISCONNECTS REQUIRED FOR THE
 WATERHRT & A/C
 5) CLOSET FOR WATER HEATER AND A/C
 NEEDS LIGHT AND RECEPTACLE FOR
 SERVICING.
 6) NO TVS OR TELE. SHOWN ON DRAWINGS IF
 NOT SHOWN A SEPERATE PERMIT WILL BE
 REQUIRED FOR BOTH.
 7) NO CIRCUITS SHOWN ON DRAWINGS.
 8) NO CIRCUITS SHOWN FOR SMOKE
 DETECTORS9) OUTLET SPACING BY KITCHEN
 IN LIVING
 ROOM IS NOT TO CODE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-05-07 Cont ID  
Sent By mcarsill Date 2004-05-07 Time 09:07 Rev Time 0.00
Received By mcarsill Date 2004-05-07 Time 09:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-12-24 Cont ID  
Sent By mcarsill Date 2003-12-24 Time 15:32 Rev Time 0.00
Received By mcarsill Date 2003-12-24 Time 15:32 Sent To  
Notes
2003-12-24 00:00:001) MORE DETAILS REQUIRED ON SMOKE
 DETECTORS. ALL NEW SMOKE DETECTORS
 SHALL BE ELECTRIC. THESE DEVICES SHALL
 BE INSTALLED A MINIMUM OF THREE FEET
 FROM AIR CONDITIONER DIFFUSERS. S.D.
 NOT ON LABEL.
  
 2) ENTRY DOOR IS REQUIRED TO BE FIRE
 RATED.NO INFORMATION PROVIDED ABOUT
 RATING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-09-16 Cont ID  
Sent By adarroug Date 2005-09-16 Time 16:11 Rev Time 0.00
Received By adarroug Date 2005-09-16 Time 16:11 Sent To E
Notes
2005-09-16 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-08-08 Cont ID  
Sent By adarroug Date 2005-08-08 Time 16:02 Rev Time 0.00
Received By adarroug Date 2005-08-08 Time 16:02 Sent To E
Notes
2005-08-08 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-07-14 Cont ID  
Sent By csiegber Date 2004-07-14 Time 16:17 Rev Time 0.00
Received By csiegber Date 2004-07-14 Time 16:17 Sent To  
Notes
2004-07-14 00:00:00TO COMM BD#50

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-07-02 Cont ID  
Sent By csiegber Date 2004-07-02 Time 08:52 Rev Time 0.00
Received By csiegber Date 2004-07-02 Time 08:52 Sent To  
Notes
2004-07-02 00:00:00TO COMM BD#52

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-07 Cont ID  
Sent By csiegber Date 2004-06-07 Time 14:23 Rev Time 0.00
Received By csiegber Date 2004-06-07 Time 14:20 Sent To  
Notes
2004-06-07 00:00:00TO COMM BD#24

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-06 Cont ID  
Sent By csiegber Date 2004-05-06 Time 16:22 Rev Time 0.00
Received By csiegber Date 2004-05-06 Time 16:22 Sent To  
Notes
2004-05-06 00:00:00TO COMM BD#57

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-11-20 Cont ID  
Sent By csiegber Date 2003-11-20 Time 17:13 Rev Time 0.00
Received By csiegber Date 2003-11-20 Time 17:13 Sent To  
Notes
2003-11-20 00:00:00TO COMM BD#34

Review Stop M MECHANICAL (A/C)
Rev No 5 Status N Date 2004-07-16 Cont ID  
Sent By pkrauss Date 2004-07-16 Time 11:04 Rev Time 0.15
Received By pkrauss Date 2004-07-16 Time 11:02 Sent To  
Notes
2004-07-16 00:00:00MECHANICAL CONTRACTOR TO APPLY FOR
 SEPARATE PERMIT.PROVIDE PLANS & CALCS
 WITH MECHANICAL PERMIT APPLICATION.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2004-07-06 Cont ID  
Sent By pkrauss Date 2004-07-06 Time 15:50 Rev Time 0.20
Received By pkrauss Date 2004-07-06 Time 15:50 Sent To  
Notes
2004-07-06 00:00:00DENIED:
 3RD REQUEST:
 PLEASE PROVIDE ENERGY, MANUAL J CALCS OR
 A COMPLETED FROM 600C.
  
 NEW COMMENT:
 PLANS WERE NOT PREVIOUSLY SUBMITTED.
 PLANS SUBMITTED ARE SEALED BY ENGINEER
 WITH NO TITLE BLOCK.PER FS 471.023 &
 FAC 61G15.23.002 (2), TITLE BLOCK
 REQUIRED.PLEASE NOTE, PLANS ARE NOT
 REQUIRED TO BE "ENGINEERED" DRAWINGS PER
 THE FS 553.79 (6)(D).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2004-06-18 Cont ID  
Sent By pkrauss Date 2004-06-18 Time 07:52 Rev Time 0.20
Received By pkrauss Date 2004-06-18 Time 07:44 Sent To  
Notes
2004-06-18 00:00:00NO NEW MECHANICAL PLANS SUBMITTED FOR
 REVIEW.MECHANICAL CONTRACTOR INDICATED
 ON PERMIT APPLICATION.PLEASE PROVIDE
 PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-05-12 Cont ID  
Sent By pkrauss Date 2004-05-12 Time 07:49 Rev Time 0.35
Received By pkrauss Date 2004-05-12 Time 07:44 Sent To  
Notes
2004-05-12 00:00:00PLANS ARE TECHINCALLY CODE COMPLIANT.
 SEE COMMENTS FROM ELECTRICAL PLAN REVIEW
 PLANS SHALL BE DATED BY THE ENGINEER
 PER 471.025 OF THE FS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-12-23 Cont ID  
Sent By alange Date 2003-12-22 Time 08:24 Rev Time 0.40
Received By pkrauss Date 2003-12-23 Time 06:56 Sent To  
Notes
2003-12-23 00:00:00DENIED:
 NO MECHANICAL PLANS OR FORM 600C
 SUBMITTED FOR REVIEW.PER 2001 FBC
 CHAPTER 13 SUB-CHAPTER 600 METHOD C,
 RENOVATIONS TO EXISTING RESIDENCE ARE
 TO COMPLY WITH THIS METHOD.
  
 PLANS NEED TO INCLUDE DUCT/GRILLE SIZE,
 LAYOUT AND MATERIAL.RETURN OR TRANSFER
 AIR REQUIRED FROM BEDROOM AREAS PER 2001
 FBC(M) 601.4 (SEE ATTACHED FOR SIZING
 REQUIREMENTS).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-12-13 Cont ID  
Sent By kstevens Date 2003-12-13 Time 15:23 Rev Time 0.25
Received By kstevens Date 2003-12-13 Time 15:23 Sent To  
Notes
2003-12-13 00:00:00NO PLUMBING PLANS SUBMITTED - IF FIXTURE
 CHANGE OUT IN ORIGINAL LOCATION NONE
 REQUIRED. - PLUMBING PERMIT REQUIRED.