| Plan Review Stops For Permit 03111080 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2004-07-15 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2004-07-15 |
Time |
13:56 |
Rev Time |
0.50 |
| Received By |
alange |
Date |
2004-07-15 |
Time |
13:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2004-07-02 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2004-07-02 |
Time |
15:08 |
Rev Time |
0.50 |
| Received By |
alange |
Date |
2004-07-02 |
Time |
15:08 |
Sent To |
|
|
| Notes |
| 2004-07-02 00:00:00 | DENIED | | | SEE SAME NOTES FROM 1ST AND 2ND | | | REVIEW: | | | PRODUCT APPROVALS FOR EXTERIOR DOORS AND | | | WINDOWS NOT SUBMITTED. SUBMIT 2 COPIES. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | ANY QUESTIONS CALL ME | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2004-06-15 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2004-06-15 |
Time |
14:08 |
Rev Time |
0.50 |
| Received By |
alange |
Date |
2004-06-15 |
Time |
14:08 |
Sent To |
|
|
| Notes |
| 2004-06-15 00:00:00 | DENIED | | | NOTE FROM SECOND REVIEW: | | | PRODUCT APPROVALS FOR EXTERIOR DOORS AND | | | WINDOWS NOT SUBMITTED. | | | SUBMIT 2 COPIES. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | ANY QUESTIONS CALL ME. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2004-05-10 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2004-05-10 |
Time |
15:22 |
Rev Time |
0.50 |
| Received By |
alange |
Date |
2004-05-10 |
Time |
15:22 |
Sent To |
|
|
| Notes |
| 2004-05-10 00:00:00 | DENIED | | | NOTE FROM FIRST REVIEW. | | | PRODUCT APPROVALS NOT SUBMITTED. | | | SUBMIT 2 COPIES FOR EXTERIOR WINDOWS AND | | | DOORS. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | ANY QUESTIONS CALL ME. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-12-22 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2003-12-22 |
Time |
08:03 |
Rev Time |
1.00 |
| Received By |
alange |
Date |
2003-12-22 |
Time |
08:03 |
Sent To |
|
|
| Notes |
| 2003-12-22 00:00:00 | 1. SUBMIT WINDOW PRODUCT APPROVALS. | | | 2.WINDOW BUCKS TO COMPLY WITH | | | FBC 1707.4.4.2 | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
P |
Date |
2005-09-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-09-20 |
Time |
10:01 |
Rev Time |
0.40 |
| Received By |
dpalmer |
Date |
2005-09-20 |
Time |
10:01 |
Sent To |
|
|
| Notes |
| 2005-09-20 00:00:00 | 210.8A6 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
F |
Date |
2005-08-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-08-10 |
Time |
18:42 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2005-08-10 |
Time |
18:42 |
Sent To |
|
|
| Notes |
| 2005-08-10 00:00:00 | ****** REVISION UNSAT ********* | | | | | | | | | 1)NOTE: PLEASE SEE 220.3B4. | | | PLEASE SHOW ALL RECESSED LTS BASED ON | | | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT | | | BE FIGURED IN W/ 3W/PER SQ FT. | | | PLEASE PROVIDE FIXTURE INFORMATION ON | | | LEGEND. | | | PLEASE NOTICE THERE ARE MORE THAN 75 | | | RECESSED LT FIXTURES. | | | | | | 2)NOTE: PLEASE CORRELATE ALL CIRCUITING | | | ON PLANS WITH THE REVISED SUBMITTED | | | PANEL SCHEDULE. | | | PLEASE SEE DINING RM CIRCUIT NOT ON | | | PLANS? ETC. | | | 215.5 | | | | | | 3)NOTE: PLEASE SEE 210.52B1, WHICH | | | REQUIRES DINING RM TO BE ON THE ONE OR | | | MORE 20, #12, SMALL APPLIANCE CIRCUITS. | | | PLEASE SEE DINING RM CIRCUIT ON PANEL | | | SCHEDULE IS SHOWN AS #14 AWG AND 15A? | | | | | | 4)NOTE: PLEASE SHOW ALL ROOM/AREA | | | DESIGNATIONS TO PLANS. | | | 215.5 | | | | | | 5)NOTE: PLEASE SEE 410.8 FOR MIN | | | CLEARENCE REQUIRED FOR RECESSED LTS IN | | | CLOSETS. PLEASE SEE SOME APPEAR TO BE | | | LOCATED TOO CLOSE TO POSSIBLE SHLEVING | | | AREAS. THIS IS ONLY A NOTE AS NO | | | SHELVING IS SHOWN. PLEASE SEE A MIN OF | | | 18" IS TO BE PROVIDED FOR SHELVING AND | | | THEN MIN CLEARENCE IS REQUIRED AFTER THE | | | 18". PLEASE VERIFY THESE MIN AREAS. | | | | | | 6)NOTE: PLEASE SEE MISSING GFI RECEPT | | | ALONG KITCHEN COUNTERSPACE. 210.52C1 | | | | | | 7)NOTE: PLEASE SEE MISSING RECEPTS PER | | | 210.52, WITH IN 6' OF DOOR WAY? DINING | | | AREA? BEDRM? | | | | | | 8)NOTE: PLEASE SEE GEN LT/RECEPT CIRCUIT | | | SHOWN WITH A #10 EQUIPMENT GROUNDING | | | CONDUCTOR?? MISPRINT? | | | 250.122 | | | | | | | | | PLEASE SEE MANY OF THE ABOVE ITEMS HAVE | | | BEEN REDLINEDS ON PLANS AT LOCATION SOF | | | THE ABOVE COMMENTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL THIS | | | OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2004-07-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-07-15 |
Time |
13:46 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-07-15 |
Time |
13:46 |
Sent To |
|
|
| Notes |
| 2005-08-10 00:00:00 | REDLINED AHU 424.3B |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2004-07-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-07-06 |
Time |
14:20 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2004-07-06 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2004-07-06 00:00:00 | ************ UNSAT 5TH TIME ********* | | | | | | 1)NOTE: PLEASE SEE 2002 NEC 210.12 | | | PLEASE LIST THE REQUIRED ARC FAULT | | | PROTECTED CIRCUITS. | | | THIS IS REQUIRED FOR ALL "OUTLETS" IN | | | BEDROOMS, INCLUDING SD'S, LTS, RECEPTS, | | | FANS. | | | THIS HAS BEEN REQUESTED ON THE PREVIOUS | | | FOUR REVIEWS. | | | | | | 2)NOTE: PLEASE SEE THERE ARE A FEW | | | RECEPTS WITH CIRCUIT #'S MISSING. | | | PLEASE SEE # OF RECEPTS ON CIRCUIT #5 | | | 180 VA PER RECEPT.? | | | | | | | | | ** PLEASE SEE ATTACHED BZ RECEIPT, | | | A 4X FEE HAS NOW BEEN ACCESSED FOR PLAN | | | REVIEW COMMENTS AS SET FORTH FOR BLDG | | | AND ELECTRICAL COMMENTS. | | | A NOTICE WAS GIVEN ON PREVIOUS REVIEWS, | | | PER FS 553.80(2)(B). | | | THIS FEE IF $1,218.00 IS REQUIRED TO BE | | | PAID BEFORE RESUBMITTING PLANS. | | | ONCE MORE, ONE SET OF PLANS ARE BEING | | | RETAINED AND MAY BE SENT TO FBPE'S FOR | | | REVIEW OF CODE COMPLIANCE ON PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | AS TO DATE NO PHONE CALLS HAVE BEEN | | | RECIEVED FROM DESIGN PROFESSIONAL TO GO | | | OVER COMMENTS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2004-06-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-06-10 |
Time |
16:12 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2004-06-10 |
Time |
16:08 |
Sent To |
|
|
| Notes |
| 2004-06-10 00:00:00 | ************ UNSAT 4TH TIME *********** | | | | | | PLEASE SEE NOTES FROM PREVIOUS REVIEWS. | | | PLEASE SEE ONLY TWO OF THE PREVIOUS | | | 6 NOTES WERE ADDRESSED. | | | | | | 1)NOTE: | | | NOTE #1OK. TURQUOISE ENG NAME WAS | | | REMOVED. | | | | | | 2)NOTE: | | | NOTE #2 NO. PLEASE SHOW "ALL" CIRCUITING | | | ON PLANS AND CORRELATE WITH THE SUBMITT- | | | -ED PANEL SCHEDULE. PLEASE SEE 2002 NEC | | | FOR ALL MIN CIRCUITS REQUIRED IN A | | | DWELLING UNIT. WASHER? DRYER? 215.5, | | | 220.16,220.18, | | | | | | 3)NOTE: | | | NOTE #3OK | | | | | | 4)NOTE: | | | NOTE #4NO, SOME RECEPTS STILL MISSING | | | FOR 2' OF WALL SPACE. | | | | | | 5)NOTE: | | | NOTE #5 NO, PLEASE LIST THE REQUIRED | | | ARC FAULT PROTECTED CIRCUITS PER 2002 | | | NEC 210.12 | | | PLEASE SEE 2002 NEC REQUIRES THIS FOR | | | LTS/SD'S RECEPTS/FANS ETC. ALL "OUTLETS" | | | IN SLEEPING RMS. | | | | | | 6)NOTE: | | | NOTE #6NO, PLEASE SEE 220.3B4. | | | PLEASE SHOW ALL RECESSED LTS BASED ON | | | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT | | | BE FIGURED IN W/ 3W/PER SQ FT. | | | PLEASE PROVIDE FIXTURE INFORMATION ON | | | LEGEND. | | | | | | PLEASE SEE ONE OF THESE SETS ARE NOW | | | BEING RETAINED ALSO DUE TO REPEAT | | | COMMENTS. | | | PLEASE ALSO SEE ATTACHED COPY OFTHE | | | FS 553.80(2)(B). IF ANY OF THE COMMENTS | | | FOR CODE COMPLIANCE ARE NOT ADDRESSED | | | ON NEXT REVIEW A 4X FEE WILL BE ACCESSED | | | TO THE DESIGN PROFESSIONAL. | | | ****PLEASE SEE ATTACHED COPY***** | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | ONCE AGAIN, PLEASE DO NOT HESITATE TO | | | CALL. AS OF THIS REVIEW, DESIGNER OF | | | RECORD HAS NOT CONTACTED ELECTRICAL | | | PLAN REVIEW STAFF FOR ANY QUESTIONS. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2004-05-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-05-08 |
Time |
16:48 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2004-05-08 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2004-05-08 00:00:00 | ******** UNSAT ********** | | | | | | PLEASE SEE NOTES FROM FIRST TWO | | | REVIEWS HAVE STILL NOT BEEN ADDRESSED. | | | PLEASE SEE THE FOLLOWING. | | | | | | 1)NOTE: PLANS MUST CONTAIN ALL LICENSE | | | #'S ON TITLE BLOCK AS REQ'D UNDER FAC | | | 61G15-23.002. PLEASE SEE FS 471.023 | | | TURQUOIUSE INC. MUST HAVE A CA#. | | | THERE IS NO CA# FOUND WITH DBPR/ FBPE'S | | | THIS COMMENT HAS BEEN MADE ON PREVIOUS | | | REVIEWS ON THIS PROJECT AND OTHER | | | PROJECTS SUBMITTED TO THE CITY OF WPB | | | FOR PERMIT. | | | PLEASE ALSO SEE FS 471.025, DATE MUST | | | ALSO BE SIGNED ON PLANS WHEN ENGINEER | | | SIGNS HIS/HER SIGNATURE. | | | WE ARE NOW RETAINING ONE SET OF PLANS | | | TO BE TURNED OVER TO FBPE'S FOR REVIEW | | | FOR ABOVE MENTIONED. | | | | | | 2)NOTE: PLANS MUST SHOW ALL MIN CIRCUIT- | | | -ING AS SET FORTH PER 2002 NEC. | | | PLEASE SHOW CIRCUITS ON PLANS AND | | | CORRELATE WITH THE SUBMITTED PANEL | | | SCHEDULE. | | | | | | 3) NOTE: PLEASE LIST ALL THE REQ'D | | | DEDICATED BATH(S) CIRCUIT(S) ON PANEL | | | SCHEDULE. PER 210.52D, 210.11C3 | | | | | | 4)NOTE: PLEASE SHOW OUTLET SPACING PER | | | 210.52. 2',6`,12` RULE. MISSING SOME. | | | | | | 4 )NOTE: PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CURCUIT(S) ON PANEL | | | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" | | | IN BEDROOMS ARE TO BE PROTECTED , | | | INCLUDING, LTS, RECEPTS, SD'S ETC. | | | | | | 5 )NOTE: PLEASE SEE 220.3B4. | | | PLEASE SHOW ALL RECESSED LTS BASED ON | | | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT | | | BE FIGURED IN W/ 3W/PER SQ FT. | | | PLEASE PROVIDE FIXTURE INFORMATION ON | | | LEGEND. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2003-12-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-12-02 |
Time |
05:15 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2003-12-02 |
Time |
05:13 |
Sent To |
|
|
| Notes |
| 2003-12-02 00:00:00 | ********** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE ELECTRICAL REVIEW | | | NOTES FROM JAKE LEAHY DATED 11/24/03 | | | | | | 2)NOTE: PLEASE SEE THAT BOTH SETS OF | | | PLANS ARE REQ'D TO BE SIGNED, DATED AND | | | SEALED WITH ORIGINAL SIGNATURE ETC. | | | PLEASE SEE THAT INITIALS ARE NOT PERMITT | | | -ED. PLEASE SIGN WITH COMPLETE SIGNATURE | | | THE ABOVE IS PER FS 471.025 AND FAC | | | 61G15-23.002, AND FBPE'S.FS 471.023 | | | TITLE BLOCK PRINTED NAME AND LICENSE #'S | | | | | | PLEASE ADDRESS ABOVE COMMENTS AND | | | COMMENTS FROM OTHER REVIEWER. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-11-24 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2003-11-24 |
Time |
09:03 |
Rev Time |
1.00 |
| Received By |
jleahy |
Date |
2003-11-24 |
Time |
08:28 |
Sent To |
|
|
| Notes |
| 2003-11-24 00:00:00 | 1) BEDROOMS NEED TO BE ON ARC FAULT | | | CIRCUIT BREAKERS | | | 2)SWITCH BY SLIDING DOOR NEAR KITCHEN | | | HAS NO LOAD. | | | 3) SWITCH LEG FOR LIVING ROOM LIGHTS | | | LOOK INCOMPLETE. ALSO THERE IS THREE | | | FIXTURES THAT HAVE NO SWITCH LEG SHOWN. | | | 4) DISCONNECTS REQUIRED FOR THE | | | WATERHRT & A/C | | | 5) CLOSET FOR WATER HEATER AND A/C | | | NEEDS LIGHT AND RECEPTACLE FOR | | | SERVICING. | | | 6) NO TVS OR TELE. SHOWN ON DRAWINGS IF | | | NOT SHOWN A SEPERATE PERMIT WILL BE | | | REQUIRED FOR BOTH. | | | 7) NO CIRCUITS SHOWN ON DRAWINGS. | | | 8) NO CIRCUITS SHOWN FOR SMOKE | | | DETECTORS9) OUTLET SPACING BY KITCHEN | | | IN LIVING | | | ROOM IS NOT TO CODE. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2004-05-07 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-05-07 |
Time |
09:07 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-05-07 |
Time |
09:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2003-12-24 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-12-24 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-12-24 |
Time |
15:32 |
Sent To |
|
|
| Notes |
| 2003-12-24 00:00:00 | 1) MORE DETAILS REQUIRED ON SMOKE | | | DETECTORS. ALL NEW SMOKE DETECTORS | | | SHALL BE ELECTRIC. THESE DEVICES SHALL | | | BE INSTALLED A MINIMUM OF THREE FEET | | | FROM AIR CONDITIONER DIFFUSERS. S.D. | | | NOT ON LABEL. | | | | | | 2) ENTRY DOOR IS REQUIRED TO BE FIRE | | | RATED.NO INFORMATION PROVIDED ABOUT | | | RATING. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2005-09-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-16 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-16 |
Time |
16:11 |
Sent To |
E |
|
| Notes |
| 2005-09-16 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2005-08-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-08 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-08 |
Time |
16:02 |
Sent To |
E |
|
| Notes |
| 2005-08-08 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2004-07-14 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-07-14 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-07-14 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2004-07-14 00:00:00 | TO COMM BD#50 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2004-07-02 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-07-02 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-07-02 |
Time |
08:52 |
Sent To |
|
|
| Notes |
| 2004-07-02 00:00:00 | TO COMM BD#52 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-06-07 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-06-07 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-06-07 |
Time |
14:20 |
Sent To |
|
|
| Notes |
| 2004-06-07 00:00:00 | TO COMM BD#24 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-05-06 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-05-06 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-05-06 |
Time |
16:22 |
Sent To |
|
|
| Notes |
| 2004-05-06 00:00:00 | TO COMM BD#57 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-11-20 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-11-20 |
Time |
17:13 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-11-20 |
Time |
17:13 |
Sent To |
|
|
| Notes |
| 2003-11-20 00:00:00 | TO COMM BD#34 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
N |
Date |
2004-07-16 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-07-16 |
Time |
11:04 |
Rev Time |
0.15 |
| Received By |
pkrauss |
Date |
2004-07-16 |
Time |
11:02 |
Sent To |
|
|
| Notes |
| 2004-07-16 00:00:00 | MECHANICAL CONTRACTOR TO APPLY FOR | | | SEPARATE PERMIT.PROVIDE PLANS & CALCS | | | WITH MECHANICAL PERMIT APPLICATION. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2004-07-06 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-07-06 |
Time |
15:50 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
2004-07-06 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2004-07-06 00:00:00 | DENIED: | | | 3RD REQUEST: | | | PLEASE PROVIDE ENERGY, MANUAL J CALCS OR | | | A COMPLETED FROM 600C. | | | | | | NEW COMMENT: | | | PLANS WERE NOT PREVIOUSLY SUBMITTED. | | | PLANS SUBMITTED ARE SEALED BY ENGINEER | | | WITH NO TITLE BLOCK.PER FS 471.023 & | | | FAC 61G15.23.002 (2), TITLE BLOCK | | | REQUIRED.PLEASE NOTE, PLANS ARE NOT | | | REQUIRED TO BE "ENGINEERED" DRAWINGS PER | | | THE FS 553.79 (6)(D). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2004-06-18 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-06-18 |
Time |
07:52 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
2004-06-18 |
Time |
07:44 |
Sent To |
|
|
| Notes |
| 2004-06-18 00:00:00 | NO NEW MECHANICAL PLANS SUBMITTED FOR | | | REVIEW.MECHANICAL CONTRACTOR INDICATED | | | ON PERMIT APPLICATION.PLEASE PROVIDE | | | PLANS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2004-05-12 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-05-12 |
Time |
07:49 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2004-05-12 |
Time |
07:44 |
Sent To |
|
|
| Notes |
| 2004-05-12 00:00:00 | PLANS ARE TECHINCALLY CODE COMPLIANT. | | | SEE COMMENTS FROM ELECTRICAL PLAN REVIEW | | | PLANS SHALL BE DATED BY THE ENGINEER | | | PER 471.025 OF THE FS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2003-12-23 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2003-12-22 |
Time |
08:24 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2003-12-23 |
Time |
06:56 |
Sent To |
|
|
| Notes |
| 2003-12-23 00:00:00 | DENIED: | | | NO MECHANICAL PLANS OR FORM 600C | | | SUBMITTED FOR REVIEW.PER 2001 FBC | | | CHAPTER 13 SUB-CHAPTER 600 METHOD C, | | | RENOVATIONS TO EXISTING RESIDENCE ARE | | | TO COMPLY WITH THIS METHOD. | | | | | | PLANS NEED TO INCLUDE DUCT/GRILLE SIZE, | | | LAYOUT AND MATERIAL.RETURN OR TRANSFER | | | AIR REQUIRED FROM BEDROOM AREAS PER 2001 | | | FBC(M) 601.4 (SEE ATTACHED FOR SIZING | | | REQUIREMENTS). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2003-12-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-12-13 |
Time |
15:23 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2003-12-13 |
Time |
15:23 |
Sent To |
|
|
| Notes |
| 2003-12-13 00:00:00 | NO PLUMBING PLANS SUBMITTED - IF FIXTURE | | | CHANGE OUT IN ORIGINAL LOCATION NONE | | | REQUIRED. - PLUMBING PERMIT REQUIRED. |
|
|