Plan Review Details - Permit 03111027
Plan Review Stops For Permit 03111027
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-08-09 Cont ID  
Sent By rbrown Date 2004-08-09 Time 09:59 Rev Time 0.00
Received By rbrown Date 2004-08-09 Time 09:59 Sent To  
Notes
2004-08-09 00:00:00REVISION SUBMITTED 7/28/04 FOR SHEETS
 A-1.0, A-1.1, A-3.0

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-06-28 Cont ID  
Sent By rbrown Date 2004-06-28 Time 14:17 Rev Time 0.00
Received By rbrown Date 2004-06-28 Time 14:17 Sent To  
Notes
2004-06-28 00:00:00REVISION SUBMITTED ON 6/11/04.SHEETS
 A-1.0, A-2.0 AND TI-1 STAMPED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-06-02 Cont ID  
Sent By rbrown Date 2004-06-02 Time 08:55 Rev Time 0.00
Received By rbrown Date 2004-06-02 Time 08:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-04-29 Cont ID  
Sent By rbrown Date 2004-04-29 Time 15:51 Rev Time 0.00
Received By rbrown Date 2004-04-29 Time 15:51 Sent To  
Notes
2004-04-29 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 BEFORE A PERMIT CAN BE ISSUED:
  
 A) IT IS NOTED THAT THE GENERAL
 CONTRACTOR WILL HAVE THE NOTICE OF
 COMMENCEMENT RECORDED.
 THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 B) THE OWNER SHALL CONFIRM WHAT THE
 ADDRESS IS FOR THIS PROJECT.THE PLANS
 AND ENERGY CODE COMPLIANCE FORM STATE
 '221 CLEMATIS ST' WHICH IS NOT A VALID
 'TENANT ADDRESS' AT 225 CLEMATIS ST.
 225 CLEMATIS ST IS THE ADDRESS THAT
 IS REFERENCED FOR THIS PROPERTY CONTROL
 NUMBER ON PALM BEACH COUNTY PROPERTY
 APPRAISERS RECORDS.OUR RECORDS SHOW A
 NUMBER OF 'TENANT ADDRESSES' FOR THIS
 PROPERTY CONTROL NUMBER (SEE ATTACHED
 SHEET).CONFIRM WHICH IS THE CORRECT
 ADDRESS FOR THIS PROJECT AND AMEND THE
 DOCUMENTS ACCORDINGLY.
  
 C) FBC* F102.2.7FIRE DISTRICT.SHEET
 A-1.1, KEYED NOTE 2 REFERS TO TWO
 OPTIONS FOR THE OBSERVATION DECK
 CONSTRUCTION.ARCHITECTURAL TRIM ON
 BUILDINGS IN THE FIRE DISTRICT SHALL BE
 CONSTRUCTED OF APPROVED NON-COMBUSTIBLE
 MATERIALS OR FIRE RETARDANT TREATED WOOD
 ANNOTATE THE PLANS ACCORDINGLY.
  
 D) FBC* F102.2.4ROOF COVERING IN THE
 FIRE DISTRICT.SHEET A-1.1, ROOFING
 SPECIFICATION SHALL INCLUDE THE
 REQUIREMENT FOR THE ROOFING TO CONFORM
 TO CLASS A OR B AS DEFINED IN FBC 1505.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-12-23 Cont ID  
Sent By rbrown Date 2003-12-23 Time 09:42 Rev Time 0.00
Received By rbrown Date 2003-12-23 Time 09:42 Sent To  
Notes
2003-12-23 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) FBC 1004.1.5EGRESS FROM OBSERVATION
 DECK.THE TRAVEL DISTANCE FROM THE MOST
 REMOTE POINT ON THE OBSERVATION DECK TO
 DOOR E1 IS APPROX. 70 FT.ANNOTATE THE
 PLANS TO STATE THAT THE EXISTING STAIR
 BEYOND DOOR E1 IS A PROTECTED 'EXIT'
 STAIR WITH 2-HOUR FIRE-RATED WALLS AND
 90-MINUTE RATED DOORS ALONG THE ENTIRE
 ROUTE TO EXIT DISCHARGE.
  
 3) FBC 1007.3.1 (EXCEPTION 1)STAIR
 TREADS AND RISERS.IT IS NOTED THAT THE
 THE NEW STAIR HAS 9.47" TREADS AND
 7.625" RISERS. ANNOTATE/DETAIL THE PLANS
 TO ENSURE THAT THE TREADS (LESS THAN
 10") HAVE AN EFFECTIVE PROJECTION OF
 APPROX. 1" OVER THE TREAD BELOW.NOTE
 THAT FIRE PLAN REVIEWER HAS ALSO
 COMMENTED ON THE STAIR.
  
 4) FBC 1603OBSERVATION DECK DEAD LOAD.
 SHEET A-4.0 SHOWS THE SAME DEAD LOAD
 (25 PSF) FOR BOTH THE 'ROOFTOP DECK
 LOAD' AND THE 'ROOF LOAD'.SHEET A-1.1,
 KEYED NOTE 2 SPECIFIES TWO DECKING
 OPTIONS FOR THE OBSERVATION DECK AREA,
 BUT THE ABOVE DEAD LOADS DO NOT SHOW ANY
 DIFFERENCE BETWEEN 'ROOF' AND 'ROOFTOP
 DECK' TO ACCOUNT FOR THE WORST CASE DECK
 SYSTEM LOAD.AMEND/ANNOTATE THE PLANS.
  
 5) FBC 1608.2.1THE HANDRAIL SHALL BE
 DESIGNED AND CONSTRUCTED FOR A
 CONCENTRATED LOAD OF 200 LB APPLIED AT
 ANY POINT, AND IN ANY DIRECTION, TO
 PRODUCE MAXIMUM STRESS IN EACH OF THE
 COMPONENTS OR SUPPORTS.AMEND/ANNOTATE
 THE PLANS.THE GUARDRAIL DESIGN
 CRITERIA STATED ON SHEET A-4.0 HAS
 ALREADY BEEN NOTED.
  
 6) 61G15-23.002(2)FL. ADMIN. CODE.
 PLANS SIGNED & SEALED BY A PROFESSIONAL
 ENGINEER SHALL INCLUDE EITHER THE NAME,
 AND LICENSE NUMBER OF THE ENGINEER.
 UNDER THE ENGINEER'S SEAL ON THE
 MECHANICAL, ELECTRICAL AND PLUMBING
 SHEETS IN THE BOX PROVIDED FOR THE SEAL,
 THE NAME AND LICENSE NUMBER OF
 MICHAEL J. KRAVIT SHALL BE STRUCK OUT,
 AND THE NAME AND LICENSE NUMBER OF THE
 ENGINEER SEALING THE MECHANICAL AND
 PLUMBING SHEETS OR THE ELECTRICAL SHEETS
 SHALL BE PRINTED.
  
 7) FBC 13-103.1.1.1SHEET 2 OF THE
 SUBMITTED ENERGY CODE COMPLIANCE FORM
 SHALL INCLUDE THE NAME AND LICENSE #
 OF THE ARCHITECT, AND THE ENGINEERS
 RESPONSIBLE FOR THE DESIGN OF THE
 ELECTRICAL, LIGHTING, MECHANICAL AND
 PLUMBING SYSTEMS, TO CERTIFY COMPLIANCE.
  
 8) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-01-18 Cont ID  
Sent By dpalmer Date 2005-01-18 Time 09:15 Rev Time 0.25
Received By dpalmer Date 2005-01-18 Time 09:15 Sent To  
Notes
2005-01-18 00:00:00SUB LTRS.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-08-02 Cont ID  
Sent By dpalmer Date 2004-08-02 Time 16:54 Rev Time 0.33
Received By dpalmer Date 2004-08-02 Time 16:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-06-17 Cont ID  
Sent By jleahy Date 2004-06-17 Time 08:34 Rev Time 0.00
Received By jleahy Date 2004-06-17 Time 10:46 Sent To  
Notes
2004-06-17 00:00:00SEAL ON DRAWINGS IS NOT LEGALPER DP JL

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-06-01 Cont ID  
Sent By dpalmer Date 2004-06-01 Time 13:46 Rev Time 0.33
Received By dpalmer Date 2004-06-01 Time 13:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-05-03 Cont ID  
Sent By dpalmer Date 2004-05-03 Time 11:50 Rev Time 0.50
Received By dpalmer Date 2004-05-03 Time 11:35 Sent To  
Notes
2004-05-03 00:00:00**********UNSAT **************
  
 1)NOTE: PLEASE SEE NOTE FOR ARC FAULT
 PROTECTION IS FROM THE 99 NEC.
 PLEASE SEE 210.12 2002 NEC FOR CORRECT-
 -ION OF NOTE. PLEASE ALSO SEE NOTE
 PERTAINING TO SD'D BEING WIRED FROM
 KIT/BATH LTS. IS THIS IS DONE AFCI WILL
 BE REQ'D ON THOSE ITEMS ALSO.
  
 2)NOTE: PLEASE CORRELATE ADDRESS ON PLAN
 -S/ APPLICATION W/ WHAT SHOWS AS PARCEL
 FILE. ONE SHOWS 219,221, 225, ETC.
 PLEASE SEE BLDG REVIEW COMMENTS FOR
  
 3)NOTE: PLEASE PROVIDE COPY OF ENGINEERS
 SIGNATURE FROM LICENSE/DRIVERS LICENSE.
 THESE WILL BE HELD IN FILE FOR ANY
 FUTURE REFERENCE.
 ANY PERSONEL INFORMATION MAY BE CROSSED
 OUT/ADDRESS ETC.
 FS 471.025, COMPLETE SIGNATURE IS REQ'D
 PLEASE CALL FOR ANY QUESTIONS.
  
 4)NOTE: PLEASE SEE LOADS FOR A/C UNITS
 ARE SHOWN AS XXX. ?? PLEASE SHOW AND
 CORRELATE WITH A/C MECH PLANS. MECH PLAN
 -S SHOW 5.3 KW??
  
 5)NOTE: PLEASE CLARIFY METHOD OF CONTROL
 FOR LTS TO ROOF AREA FROM BOTH LEVELS?
 210.70/ LS 101 5-8
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-11-24 Cont ID  
Sent By jleahy Date 2003-11-24 Time 13:25 Rev Time 1.00
Received By jleahy Date 2003-11-24 Time 13:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2004-08-12 Cont ID  
Sent By mcarsill Date 2004-08-12 Time 16:39 Rev Time 0.00
Received By mcarsill Date 2004-08-12 Time 16:39 Sent To  
Notes
2004-08-12 00:00:001) NEW METAL PAN STAIRS WILL BE
 UNDER SEPARATE PERMIT. THEY ARE TO
 BE BUILT TO CODE AND THE OBSERVATION
 DECK WILL ALSO BE UNDER SEPARATE
 PERMIT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-06-21 Cont ID  
Sent By nmccray Date 2004-06-21 Time 15:17 Rev Time 0.00
Received By nmccray Date 2004-06-21 Time 15:17 Sent To  
Notes
2004-06-21 00:00:00REVISION DATED 6-09-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-04-29 Cont ID  
Sent By mcarsill Date 2004-04-29 Time 12:23 Rev Time 0.00
Received By mcarsill Date 2004-04-29 Time 12:23 Sent To  
Notes
2004-04-29 00:00:001) BE ADVISED THAT THE LOCATION IS
 LOCATED WITHIN THE CITY FIRE LIMTS.
 CERTAIN RESTRICTIONS WILL APPLY.
 PLEASE SEE APPENDIX F, LOCAL AMENDMENTS
 TO THE FLORIDA BUILDING CODE. THE TYPES
 OF WOOD ALLOWED IN THE FIRE LIMTS
 IS RESTRICTED.
  
 2) A PORTABLE FIRE EXTINGUISHER WILL
 BE REQUIRED IN THE LIVE/WORK LOFT.
 A MINIMUM OF A 2A 10BC FIRE EXTINGUISHER
 WITH A CURRENT SERVICE TAG WILL BE
 REQUIRED.
  
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE FIRE SPRINKLER AND FIRE ALARM
 SYSTEM REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-04-29 Cont ID  
Sent By mcarsill Date 2003-12-11 Time 14:12 Rev Time 0.00
Received By mcarsill Date 2003-12-11 Time 14:12 Sent To  
Notes
2003-12-11 00:00:001) NO EMERGENCY LIGHTING SHOWN IN
 STAIRWAY.
  
 2) STAIR SECTION INDICATES 9 TREADS
 @ 9.47". STAIR TREADS SHALL BE AT
 LEAST 11". RISERS ARE AT 7 5/8". RISERS
 SHALL NOT EXCEED 7".
  
 3) PLEASE PROVIDE PRESCRIPTIVE
 REQUIREMENTS FOR HANDRAILS AND
 GUARDRAILS.
  
 4) PLANS INDICATE FIRE SPRINKLER
 PROTECTION, HOWEVER NO FIRE SPRINKLER
 PLANS ARE PROVIDED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-01-14 Cont ID  
Sent By mjacobs Date 2005-01-14 Time 15:46 Rev Time 0.00
Received By mjacobs Date 2005-01-14 Time 15:46 Sent To E
Notes
2005-01-14 00:00:00TO "DP" DESK/LETTERS.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-08-25 Cont ID  
Sent By csiegber Date 2004-08-25 Time 10:27 Rev Time 0.00
Received By csiegber Date 2004-08-25 Time 10:27 Sent To M
Notes
2004-08-25 00:00:00TO HM DESK/PER KM

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-07-28 Cont ID  
Sent By csiegber Date 2004-07-28 Time 11:36 Rev Time 0.00
Received By csiegber Date 2004-07-28 Time 11:36 Sent To  
Notes
2004-07-28 00:00:00TO COMM BD#10

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-06-29 Cont ID  
Sent By csiegber Date 2004-06-29 Time 09:45 Rev Time 0.00
Received By csiegber Date 2004-06-29 Time 09:45 Sent To  
Notes
2004-06-29 00:00:00TO COMM BD#29

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-06-11 Cont ID  
Sent By csiegber Date 2004-06-11 Time 10:44 Rev Time 0.00
Received By csiegber Date 2004-06-11 Time 10:44 Sent To  
Notes
2004-06-11 00:00:00TO COMM BD#4

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-05-24 Cont ID  
Sent By alange Date 2004-05-24 Time 14:12 Rev Time 0.00
Received By alange Date 2004-05-24 Time 14:12 Sent To  
Notes
2004-05-24 00:00:00TO COMM BD. #13

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-16 Cont ID  
Sent By csiegber Date 2004-04-16 Time 16:28 Rev Time 0.00
Received By csiegber Date 2004-04-16 Time 16:28 Sent To  
Notes
2004-04-16 00:00:00TO COMM BD#

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-23 Cont ID  
Sent By rbrown Date 2003-12-23 Time 12:32 Rev Time 0.00
Received By rbrown Date 2003-11-19 Time 16:07 Sent To  
Notes
2003-11-19 00:00:00TO COMM BD#55

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2004-08-25 Cont ID  
Sent By hmoser Date 2004-08-25 Time 14:12 Rev Time 0.50
Received By hmoser Date 2004-08-25 Time 14:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-07-06 Cont ID  
Sent By csiegber Date 2004-08-25 Time 10:27 Rev Time 0.40
Received By pkrauss Date 2004-07-06 Time 07:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-06-23 Cont ID  
Sent By pkrauss Date 2004-06-23 Time 07:35 Rev Time 0.35
Received By pkrauss Date 2004-06-23 Time 07:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-05-05 Cont ID  
Sent By pkrauss Date 2004-05-05 Time 08:17 Rev Time 0.40
Received By pkrauss Date 2004-05-05 Time 07:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-12-02 Cont ID  
Sent By pkrauss Date 2003-12-02 Time 07:54 Rev Time 0.55
Received By pkrauss Date 2003-12-02 Time 07:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2004-08-09 Cont ID  
Sent By kstevens Date 2004-08-09 Time 16:24 Rev Time 0.50
Received By kstevens Date 2004-08-09 Time 16:24 Sent To  
Notes
2004-08-09 00:00:00REVISION OK - CHANGED W/H TO INSTA-HOT
 DOOR SWING - LAV. VANITY - VENT FOR W/M

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-07-09 Cont ID  
Sent By kstevens Date 2004-07-09 Time 15:07 Rev Time 0.50
Received By kstevens Date 2004-07-09 Time 15:07 Sent To  
Notes
2004-07-09 00:00:00SUBMITTAL FORM ENGINEER SHOWING APPROVAL
 FOR HANGING WATER HEATER FROM BOTTOM OF
 BAR JOISTS.

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-06-23 Cont ID  
Sent By kstevens Date 2004-06-23 Time 08:33 Rev Time 0.50
Received By kstevens Date 2004-06-23 Time 08:32 Sent To  
Notes
2004-06-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHTS A2.0 AND P-1 SHEET P-1 REVISION
 INDICATES THAT FIXTURES HAVE SHIFTED.
 REVIEW OF PLANS SHOWS NO CHANGE OR SHIFT
 SHT A2.O MEASURMENTS BETWEEN FIXTURES ON
 DETAIL 01 ELEVATION "C" ARE THE SAME AS
 THE STAMPED SET AND NO SHIFTING OF FIX-
 TURES IS EVIDENT. PLEASE CLARIFY AND
 CORRELATE DETAIL ON SHT A2.0 WITH SHT
 P-1 REVISION.
 2) SHT P-1 PROVISO INDICATES THAT A TRAP
 AND A STANDPIPE ARE REQUIRED AT THE WASH
 MACHINE. ALSO A VENT IS REQUIRED FOR THE
 WASH MACHINE. REVISE THE SANT. RISER
 DIAGRAM TO REFLECT THESE REQUIREMENTS.
 SECTION 104.2.1- SECTIONS 1002.1/802.4
 - SECTION 901.2.1 - SECTION 708.10
 SHOW CLEANOUT 4' ABOVE FLOOR AT WASH
 MACHINE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-04-28 Cont ID  
Sent By kstevens Date 2004-04-28 Time 18:04 Rev Time 0.50
Received By kstevens Date 2004-04-28 Time 18:04 Sent To  
Notes
2004-04-28 00:00:00PASSED/PROVISO
  
 P-TRAP AND STANDPIPE REQUIRED FOR W/M

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-12-13 Cont ID  
Sent By kstevens Date 2003-12-13 Time 10:37 Rev Time 1.25
Received By kstevens Date 2003-12-13 Time 10:27 Sent To  
Notes
2003-12-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FC-2001 CHAPTER 11
  
 1) SHT A-2.0 BATHROOM SHALL BE ACCESS-
 IBLE, SUBMIT DETAILS FOR W.C. 11-4.16,
 LAV 11-4.19, BATHTUB 11-4.20, AND BATH-
 ROOM 11-4.23 AND ALL SUBSECTIONS.
 2) PER TABLE 403.1 A DRINKING FOUNTAIN
 AND A WASH MACHINE CONNECTION ARE REQ-
 UIRED. (ALSO SEE SECTION 410.1).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy