Plan Review Details - Permit 03110954
Plan Review Stops For Permit 03110954
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-12-08 Cont ID  
Sent By kstevens Date 2004-01-26 Time 18:06 Rev Time 0.50
Received By lsmith Date 2003-12-08 Time 08:18 Sent To  
Notes
2003-12-08 00:00:00SUBMIT CONTRACT TO VERIFY VALUE
 SEE PLUMBING NOTES
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-11-26 Cont ID  
Sent By csiegber Date 2003-11-25 Time 07:41 Rev Time 0.25
Received By btrobaug Date 2003-11-26 Time 07:49 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-12-23 Cont ID  
Sent By csiegber Date 2003-12-23 Time 13:27 Rev Time 0.00
Received By csiegber Date 2003-12-23 Time 13:27 Sent To P
Notes
2003-12-23 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-11-25 Cont ID  
Sent By csiegber Date 2003-11-25 Time 07:40 Rev Time 0.00
Received By csiegber Date 2003-11-25 Time 07:40 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-11-19 Cont ID  
Sent By csiegber Date 2003-11-19 Time 15:07 Rev Time 0.00
Received By csiegber Date 2003-11-19 Time 15:07 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-01-26 Cont ID  
Sent By kstevens Date 2004-01-26 Time 18:05 Rev Time 0.33
Received By kstevens Date 2004-01-26 Time 18:05 Sent To B
Notes
2004-01-26 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 COMMENTS FROM THE FIRST REVIEW HAVE NOT
 BEEN ADDRESSED. ADDRESS COMMENTS ATTACH-
 ED TO APPLICATION AND RESUBMIT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-12-06 Cont ID  
Sent By csiegber Date 2003-12-23 Time 13:27 Rev Time 0.50
Received By kstevens Date 2003-12-06 Time 19:34 Sent To B
Notes
2003-12-06 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 2) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 3) SIGNATURE REQUIRED ON SEAL OF ENGIN-
 ER PER 61G15-23.002(1) & 471.025.
 INITALS NOT ACCEPTABLE PER FBPE AND BLDG
 OFFICIAL.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2003-11-24 Cont ID  
Sent By csiegber Date 2003-11-19 Time 15:07 Rev Time 0.00
Received By mmclean Date 2003-11-24 Time 12:18 Sent To P
Notes
***NONE***