Plan Review Details - Permit 03110910
Plan Review Stops For Permit 03110910
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-01-21 Cont ID  
Sent By jwitmer Date 2004-01-21 Time 09:56 Rev Time 0.50
Received By jwitmer Date 2004-01-21 Time 09:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-01-13 Cont ID  
Sent By jwitmer Date 2004-01-13 Time 11:11 Rev Time 0.55
Received By jwitmer Date 2004-01-13 Time 11:11 Sent To  
Notes
2004-01-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03110910
 ADD: 500 AUSTRALIAN AV
 CONT: H. KAHLERT
 TEL: (561)718-3799
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) SEE FIRE REVIEW COMMENTS, REVISION
 TO P-1 DRAWINGS NOT SEALED:
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-12-19 Cont ID  
Sent By jwitmer Date 2003-12-19 Time 11:22 Rev Time 3.00
Received By jwitmer Date 2003-12-19 Time 09:49 Sent To  
Notes
2003-12-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03110910
 ADD: 500 S AUSTRALIAN # 1000
 CONT: HERBERT F. KAHLERT
 TEL: (561)718-5569
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 BUILDING PROVISO:
  
 1) SHEET A-3.0 ALL BACKING IN WALLS TO
 BE FIRE RETARDANT TREATED WOOD.609.2.1
  
 2)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-01-12 Cont ID  
Sent By dpalmer Date 2004-01-12 Time 06:45 Rev Time 0.33
Received By dpalmer Date 2004-01-12 Time 06:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-11-21 Cont ID  
Sent By jleahy Date 2003-11-21 Time 14:17 Rev Time 1.00
Received By jleahy Date 2003-11-21 Time 14:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-01-20 Cont ID  
Sent By nmccray Date 2004-01-20 Time 09:54 Rev Time 0.00
Received By nmccray Date 2004-01-20 Time 09:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-01-12 Cont ID  
Sent By nmccray Date 2004-01-12 Time 11:05 Rev Time 0.00
Received By nmccray Date 2004-01-12 Time 11:05 Sent To  
Notes
2004-01-12 00:00:00************DENIED**********************
 THE ATTACH SHEET TO SHEET P-1 WITH THE
 CORRECTION TO DOMESTIC COLD WATER PIPING
 RUNNING THRU EXISTING STAIR # 1 IS NOT
 SIGNED AND SEALED.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-12-08 Cont ID  
Sent By mcarsill Date 2003-12-08 Time 12:22 Rev Time 0.00
Received By mcarsill Date 2003-12-08 Time 12:22 Sent To  
Notes
2003-12-08 00:00:001) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) DOMESTIC COLD WATER PIPING CANNOT
 RUN THRU EXISTING STAIR # 1.
  
 3) ELECTRICAL NOTES # 13 CONCERNING
 DUCT SMOKE DETECTORS IS INCORRECT.
 DUCT SMOKE DETECTORS WHEN ACTIVATED
 SHALL CAUSE THE FIRE ALARM SYSTEM
 TO SOUND NOT SUPERVISORY SIGNAL.
  
 4) SECURITY LOCKS, NOTE # 11 SHALL
 COMPLY WITH SPECIAL LOCKING ARRANGEMENTS
 PER CHAPTER 7 OF THE LIFE SAFETY CODE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-05 Cont ID  
Sent By csiegber Date 2004-01-05 Time 14:22 Rev Time 0.00
Received By csiegber Date 2004-01-05 Time 14:22 Sent To  
Notes
2004-01-05 00:00:00TO COMM BD#46

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By csiegber Date 2003-11-19 Time 09:37 Sent To  
Notes
2003-11-19 00:00:00TO COMM BD#6

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-03-03 Cont ID  
Sent By pkrauss Date 2004-03-03 Time 14:57 Rev Time 0.35
Received By pkrauss Date 2004-03-03 Time 14:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-12-19 Cont ID  
Sent By jwitmer Date 2003-12-19 Time 09:48 Rev Time 0.00
Received By jwitmer Date 2003-12-19 Time 09:47 Sent To  
Notes
2003-12-19 00:00:00OK PER P. H. KRAUSS SEE STAMPED PLAN JW

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-01-17 Cont ID  
Sent By kstevens Date 2004-01-17 Time 15:15 Rev Time 0.33
Received By kstevens Date 2004-01-17 Time 15:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-12-19 Cont ID  
Sent By kstevens Date 2003-12-19 Time 12:32 Rev Time 1.00
Received By kstevens Date 2003-12-19 Time 12:32 Sent To  
Notes
***NONE***