Plan Review Details - Permit 03110799
Plan Review Stops For Permit 03110799
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-03-25 Cont ID  
Sent By rbrown Date 2004-03-25 Time 18:34 Rev Time 0.00
Received By rbrown Date 2004-03-25 Time 18:34 Sent To  
Notes
2004-03-25 00:00:00STRUCTURAL REVISION SUBMITTED 3/22/04
 FOR SOIL STABILIZATION PROCEDURE AND
 PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-01-22 Cont ID  
Sent By csiegber Date 2004-03-23 Time 08:48 Rev Time 0.00
Received By rbrown Date 2004-01-22 Time 16:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-01-13 Cont ID  
Sent By rbrown Date 2004-01-13 Time 16:45 Rev Time 0.00
Received By rbrown Date 2004-01-13 Time 16:45 Sent To  
Notes
2004-01-13 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 A) EACH CORRECTION/ALTERATION ADDED TO
 THE PLANS AFTER PRINTING, SIGNING AND
 SEALING MUST BE SIGNED AND DATED BY THE
 ARCHITECT OF RECORD.ALTERNATIVELY,
 THE CORRECTIONS SHOULD BE ADDED TO THE
 PLANS PRIOR TO PRINTING, SIGNING AND
 SEALING.
  
 B) 61G1-16.004FL. ADMIN. CODE.PLANS
 PREPARED BY A REGISTERED ARCHITECT SHALL
 INCLUDE THE FIRM'S LICENSE NUMBER ON
 EACH SHEET.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-12-16 Cont ID  
Sent By rbrown Date 2003-12-16 Time 18:28 Rev Time 0.00
Received By rbrown Date 2003-12-16 Time 18:28 Sent To  
Notes
2003-12-16 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) 61G1-16.004FL. ADMIN. CODE.THE
 ARCHITECTURAL SHEETS MUST BE SIGNED,
 DATED AND SEALED BY KERMIT C. WHITE.
  
 2) FBC 2405.2SHEET A1.1, KEY NOTE 2.
 THE VIEW PANEL IN THE NEW KITCHEN DOOR
 WILL BE A 'HAZARDOUS LOCATION' AND IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS OR ANNOTATE
 THE PLANS TO DEMONSTRATE COMPLIANCE.
  
 3) FBC 11-5.1RESTAURANT SEATING.AT
 LEAST 5% OF THE SEATING SHALL BE
 ACCESSIBLE AND SHALL COMPLY WITH 11-4.32
 WITH RESPECT TO CLEAR FLOOR SPACE, KNEE
 CLEARANCES AND TABLE HEIGHT.AMEND/
 ANNOTATE THE PLANS TO DEMONSTRATE
 COMPLIANCE.
  
 4) FBC 11-5.2SERVICE BAR.A MINIMUM
 60" LENGTH OF THE BAR SHALL BETWEEN 28"
 AND 34" ABOVE FINISHED FLOOR, TO COMPLY
 WITH 11-4.32.4, OR SERVICE SHALL BE
 AVAILABLE AT ACCESSIBLE TABLES WITHIN
 THE SAME AREA.AMEND/ANNOTATE THE PLANS
 TO DEMONSTRATE COMPLIANCE.
  
 5)FBC 1010EXIT DISCHARGE.ANNOTATE
 THE PLANS TO CLARIFY WHAT KIND OF SPACE
 (ALLEY ETC) CORRIDOR 103 PROVIDES EXIT
 TO, THROUGH THE EXISTING DOORS.
  
 6) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-01-20 Cont ID  
Sent By dpalmer Date 2004-01-20 Time 09:12 Rev Time 0.33
Received By dpalmer Date 2004-01-20 Time 09:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-01-05 Cont ID  
Sent By dpalmer Date 2004-01-05 Time 06:18 Rev Time 0.50
Received By dpalmer Date 2004-01-05 Time 06:18 Sent To  
Notes
2004-01-05 00:00:00****************** UNSAT **************
  
 PLEASE SEE COMMENTS FROM FIRST REVIEW.
 SAME NOTES.
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002.
 PLEASE INCLUDE ALL LICENSE INFORMATION
 ON TITLE BLOCKS PER FS 471
 PLEASE ALSO SEE THAT PLANS MAY HAVE ORIG
 SEAL , HOWEVER SIGNATURE IS NOT ORIG AND
 PLANS ARE SEALED COPIES. FS 471.025
 ONE SET IS BEING KEPT FOR RECORD FOR
 ABOVE SAID VIOLATION. PLANS MAY BE KEPT
 AND TURNED INTO THE FBPE'S FOR REVIEW.
  
 PLEASE SEE THAT ALL ELECTRICAL SHEETS
 WERE AND ARE VOIDED. THIS ALSO IS NOTED
 FOR OTHER TRADES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-12-15 Cont ID  
Sent By dpalmer Date 2003-12-15 Time 14:03 Rev Time 0.50
Received By dpalmer Date 2003-12-15 Time 14:03 Sent To  
Notes
2003-12-15 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE INCLUDE ALL LICENSE #
 INFORMATION ON TITLE BLOCK FOR ENGINEER
 OF RECORD. PLEASE ALSO INCLUDE CA #
 FOR ENG FIRM. PER FS 471.0025 AND FAC
 61G15-23.002
 PLEASE ALSO SEE PLANS ARE COPIES AND
 NOT ORIGINAL SIGNED, DATED AND SEALED.
  
 PLEASE SEE THAT THIS PERTAINS TO ALL
 TRADES AND NOT ONLY ELECTRICAL .
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-11-19 Cont ID  
Sent By jleahy Date 2003-11-19 Time 10:01 Rev Time 0.30
Received By jleahy Date 2003-11-19 Time 10:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-01-16 Cont ID  
Sent By mcarsill Date 2004-01-16 Time 15:59 Rev Time 0.00
Received By mcarsill Date 2004-01-16 Time 15:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-01-08 Cont ID  
Sent By mcarsill Date 2004-01-08 Time 17:33 Rev Time 0.00
Received By mcarsill Date 2004-01-08 Time 17:33 Sent To  
Notes
2004-01-08 00:00:001) SEPARATE PLANS AND PERMITS REQUIRED
 FOR HOOD, DUCT, AND SUPPRESSION
 SYSTEMS.
  
 2) INTERIOR FINISH IN EXITS SHALL BE
 CLASS A OR B.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-11-26 Cont ID  
Sent By mcarsill Date 2003-11-26 Time 17:31 Rev Time 0.00
Received By mcarsill Date 2003-11-26 Time 17:31 Sent To  
Notes
2003-11-26 00:00:001) PLEASE INDICATE EXIT DISCHARGE
 LOCATIONS FROM THE EXISTING DOORS
 FROM CORRIDOR 103.
  
 2) THE OCCUPANT LOAD IS TO BE DETERMINED
 BY FIRE RESCUE.
  
 3) PROVIDE SEPARATE PLANS AND PERMITS
 FOR THE REQUIRED HOOD, DUCT, AND
 FIRE SUPPRESSION SYSTEM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-03-23 Cont ID  
Sent By csiegber Date 2004-03-23 Time 08:48 Rev Time 0.00
Received By csiegber Date 2004-03-23 Time 08:48 Sent To B
Notes
2004-03-23 00:00:00TO RB DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-03-01 Cont ID  
Sent By csiegber Date 2004-03-01 Time 09:02 Rev Time 0.00
Received By csiegber Date 2004-03-01 Time 09:02 Sent To P
Notes
2004-03-01 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-01-15 Cont ID  
Sent By csiegber Date 2004-01-15 Time 16:13 Rev Time 0.00
Received By csiegber Date 2004-01-15 Time 16:13 Sent To  
Notes
2004-01-15 00:00:00TO COMM BD#11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-12-23 Cont ID  
Sent By csiegber Date 2003-12-23 Time 15:17 Rev Time 0.00
Received By csiegber Date 2003-12-23 Time 15:17 Sent To  
Notes
2003-12-23 00:00:00TO COMM BD#44

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-16 Cont ID  
Sent By csiegber Date 2003-11-17 Time 15:54 Rev Time 0.00
Received By rbrown Date 2003-11-17 Time 15:54 Sent To  
Notes
2003-11-17 00:00:00TO COMM BD#61

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-01-21 Cont ID  
Sent By pkrauss Date 2004-01-21 Time 15:28 Rev Time 0.45
Received By pkrauss Date 2004-01-21 Time 14:18 Sent To  
Notes
2004-01-21 00:00:00PROVISO:
 ADDITIONAL PERMITS REQUIRED FOR HOOD &
 FIRE SUPPRESSION.PLEASE PROVIDE PLANS
 WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2004-01-13 Cont ID  
Sent By hmoser Date 2004-01-13 Time 12:50 Rev Time 0.50
Received By hmoser Date 2004-01-13 Time 12:40 Sent To  
Notes
2004-01-13 00:00:00PLAN DENIED
 NEED FIRE DAMPERS IN RATED WALLS AT
 ADJACENT TENANT SPACE.SEE SECTION
 607.1.2 2001 FLORIDA BUILDING CODE (M)
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2003-12-19 Cont ID  
Sent By pkrauss Date 2003-12-19 Time 10:37 Rev Time 0.15
Received By pkrauss Date 2003-12-19 Time 10:37 Sent To  
Notes
2003-12-19 00:00:00CONVERSATION WITH MARK CONSOLIDATED
 METALWORKS (HOOD CONTRACTOR) PLANS TO BE
 SUBMITTED WITH THE BUILDING PLANS ON
 12-22-03.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-12-11 Cont ID  
Sent By pkrauss Date 2003-12-11 Time 07:54 Rev Time 0.55
Received By pkrauss Date 2003-12-11 Time 06:39 Sent To  
Notes
2003-12-11 00:00:00DENIED:
 1. 61G1-16.004FL. ADMIN. CODE.PLANS
 PREPARED BY A REGISTERED ARCHITECT SHALL
 INCLUDE THE FOLLOWING WITH HIS TITLE
 BLOCK:
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND
 DATED SEAL
 - INCLUDE THE PRINTED NAME OF THE
 ARCHITECT SEALING THE PLANS
  
 2.PLEASE CLARIFY DUCT REFERENCED IN
 KEY NOTE 1.INIDCATE WHAT TYPE OF DUCT
 THIS IS AND WHY DOES IT RUN THROUGH THE
 ADJACENT TENANT WITH NO FIRE DAMPER
 INDICATED.
  
 PLEASE NOTE ADDITIONAL PERMITS REQUIRED
 FOR HOOD AND FIRE SUPPRESSION.PLEASE
 PROVIDE THE FOLLOWING INFORMAITON ON
 THE HOOD/GREASE DUCT FOR A REVIEW AT
 THIS TIME OR PROVIDE COMPLETE PLANS WITH
 HOOD PERMIT APPLICATION.
 1.INDICATE DUCT LAYOUT AND SIZING.
 2.AIR VELOCITY WITHIN DUCT SYSTEM
 SHALL BE NOT LESS THAN 1,500 & NOT
 GREATER THAN 2,500.
 3.CLEANOUTS REQUIRED AT CHANGE OF
 DIRECTION.
 4.INDICATE CLEARANCE TO COMBUSTIBLES.
 5.EXHAUST OUTLETS SHALL BE LOCATED
 NOT LESS THAN 10 FT HORIZONTALLY FROM
 PROPERTY LINES AIR INTAKE OPENINGS OR
 PARTS OF THE SAME OR CONTIGUOUS BUILDING
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 5 Status P Date 2004-03-15 Cont ID  
Sent By kstevens Date 2004-03-15 Time 13:33 Rev Time 0.33
Received By kstevens Date 2004-03-15 Time 13:33 Sent To  
Notes
2004-03-15 00:00:00REVISION OK _ CHANGED W/H TO TANKLESS

Review Stop P PLUMBING
Rev No 4 Status F Date 2004-03-02 Cont ID  
Sent By kstevens Date 2004-03-02 Time 11:00 Rev Time 1.00
Received By kstevens Date 2004-03-02 Time 10:59 Sent To  
Notes
2004-03-02 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES.
 FBC-2001 FUEL GAS
  
  
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 MORE INFORMATION IS REQUIRED FOR THE
 VENTING OF THE RINNAI TANKLESS WATER
 HEATER. SUBMIT MANUF. INFO. FOR INSTALL-
 ATION OF VENT AND SHOW HOW VENT EXHAUSTS
 AND SUPPLIES COMBUSTION AIR. SECTION
 506.2.4
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-01-23 Cont ID  
Sent By csiegber Date 2004-03-01 Time 09:02 Rev Time 1.50
Received By kstevens Date 2004-01-22 Time 17:19 Sent To  
Notes
2004-01-23 00:00:00NEED W/HEATER CUT SHEET WITH LISTING FOR
 GAS PERMIT APPLICATION.

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-01-13 Cont ID  
Sent By kstevens Date 2004-01-13 Time 17:42 Rev Time 1.00
Received By kstevens Date 2004-01-13 Time 17:42 Sent To  
Notes
2004-01-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) FROM PREVIOUS REVIEW: PLANS ROUTED TO
 THE DEPT. OF BUSINESS REGULATION HOTEL
 AND RESTURANT DIV. SHALL BE STAMPED BY
 THEIR REVIEWER AND WORK SHEETS FROM RE-
 VIEWER ATTACHED TO PLANS SUBMITTED FOR
 REVIEW AT CITY OF WPB.
 2) FROM PREVIOUS REVIEW: FOR GAS REVIEW.
 A. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 3) ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER
 ON EACH SHEET. IF PRACTICING THORUGH A
 DULY AUTHORIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS, THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHOR-
 IZATION NUMBER OF THE ENGINEERING BUSIN-
 ESS ON EACH SHEET. 61G15-23.002(2) AND
 FS 471.
 4) SEE ATTACHED SHEET WITH STANDARD
 GREESE TRAP DETAIL APPROVED BY CITY OF
 WEST PALM BEACH. DETAIL ON SHEET P1.1
 NOT APPROVED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-12-13 Cont ID  
Sent By kstevens Date 2003-12-13 Time 08:23 Rev Time 2.00
Received By kstevens Date 2003-12-12 Time 17:04 Sent To  
Notes
2003-12-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) ROUTE PLANS TO THE DEPT. OF BUSINESS
 REGULATION HOTEL AND RESTURANT DIV. FOR
 REVIEW PRIOR TO RESUBMITTING PLANS.
 2) CONTACT RODNEY COMPO, INDUSTRIAL PRE-
 TREATMENT, ENVIRONMENTAL COMPLIANCE MGR.
 FOR SIZING OF GREASE INTECPTOR. WASTE
 ORD. 2938-96 - (561) 837-4074
 3) SHT P1.1 PLUMBING NOTES: #1 CODE
 ADOPTED AND IN AFFECT IS THE FLORIDA
 BUILDING CODE PLUMBING NOT THE BOCA CODE
 AMEND REFERNCE.
 4) SHT P1.1 PLUMBING NOTES: #3 AIR CHAM-
 BERS ARE NOT APPROVED. DELETE REFERENCE.
 SEC 604.9
 5) SHT P1.1 GAS WATER HEATER DETAIL, THE
 DRAINAGE PIPING FROM THE P/T (RELIEF)
 VALVE SHALL DRAIN TO A FLOOR SINK OR A
 HUB DRAIN. FLOOR SINKS ARE NOT APPROVED
 INDIRECT WASTE RECEPTORS. SEC 802.3 -
 ALL OTHER INDIRECT WASTE SHALL DRAIN TO
 A FLOOR SINK. (IN KITCHEN FOOD PREP AREA
 ECT.) - ALSO SEE SHEET P1.2
 6) SHT P1.2 DOMESTIC WATER RISER, AIR
 CHAMBERS NOT APPROVED. 604.9 DELETE
 FROM RISER. WATER HAMMER ARRESTORS RE-
 QUIRED BY SECTION 604.9 SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING. PDI-WH 201 AND MANUF
 INSTALL. INSTRUCT.
 7) FOLLOWING INFORMATION REQUIRED FOR
 GAS PERMIT.
 A. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES.
 B. TYPE OF GAS, (LP OR NATURAL)
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 G. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 H. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 I. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]