Plan Review Details - Permit 03110709
| Plan Review Stops For Permit 03110709 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2004-04-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-04-23 |
Time |
15:07 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2004-04-23 |
Time |
15:07 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-12-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2003-12-10 |
Time |
16:36 |
Rev Time |
2.00 |
| Received By |
jwitmer |
Date |
2003-12-10 |
Time |
16:36 |
Sent To |
|
|
| Notes |
| 2003-12-10 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 03110709 | | | ADD: 4047 OKEECHOBEE BLVD SUITE 211 | | | CONT: HOBAN CONSTRUCTION | | | TEL: (561)631-0070 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | ACTION: DENIED | | | 1) 1021.4 DOORS THAT SWING INTO AN EXIT | | | CORRIDOR SHALL BE RECESSED TO PREVENT | | | INTERFERENCE WITH CORRIDOR TRAFFIC; ANY | | | DOORS NOT RECESSED SHALL OPEN 180 DEGREE | | | TO STOP AGAINST THEWALL. | | | | | | 2)1005.4 EMERGENCY ESCAPE AND RESCUE | | | OPENINGS, | | | (2) EVERY ROOM OR SPACE GREATER THAN | | | 250 FT USED FOR CLASSROOM OR OTHER ED- | | | UCATIONAL PURPOSES OR NORMALLY SUBJECT | | | TO STUDENT OCCUPANCY, AND EVERY ROOM | | | SUBJECT TO CLIENT OCCUPNCY SHALL NOT | | | HAVE NOT LESS THAN ONE OUTSIDE WINDOW | | | FOR EMERGENCY RESCUE, SEE EXCEPTIONS: | | | 1) FIRE SPRINKLERS, GIVE LOCATION OF | | | THE EXISTING FIRE SPRINKLERS. | | | | | | 3)FL BLD CODE 104.2.1.2 | | | ADDITIONAL INFORMATION REQUIRED, | | | PROVIDE FLOOR PLAN OF THE TOTAL SCHOOL. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2003-11-17 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2003-11-17 |
Time |
11:06 |
Rev Time |
0.45 |
| Received By |
jleahy |
Date |
2003-11-14 |
Time |
11:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2004-04-22 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2004-04-22 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2004-04-22 |
Time |
13:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2003-12-12 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-12-12 |
Time |
07:25 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-12-12 |
Time |
07:25 |
Sent To |
|
|
| Notes |
| 2003-12-12 00:00:00 | 1) PLANS DO NOT INDICATE WHAT TYPE OF | | | OCCUPANCY IS DEPICTED. IS IT | | | EDUCATIONAL OR BUSINESS. | | | | | | 2) PLANS MAKE NO REFERENCE ABOUT ANY | | | EMERGENCY LIGHTS. | | | | | | 3) PLANS MAKE NO MENTION OF INTERIOR | | | FINISH CLASSIFICATION. | | | | | | 4) EXISTING BATHROOM SWINGS DIRECTLY | | | INFRONT OF EXISTING EXIT DOOR. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-04-20 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-20 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-04-20 |
Time |
16:46 |
Sent To |
|
|
| Notes |
| 2004-04-20 00:00:00 | TO COMM BD#19 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-11-14 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-11-14 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-11-14 |
Time |
15:26 |
Sent To |
|
|
| Notes |
| 2003-11-14 00:00:00 | TO COMM BD#8 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2004-04-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-04-23 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|