Plan Review Details - Permit 03110709
Plan Review Stops For Permit 03110709
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-04-23 Cont ID  
Sent By jwitmer Date 2004-04-23 Time 15:07 Rev Time 1.00
Received By jwitmer Date 2004-04-23 Time 15:07 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-12-10 Cont ID  
Sent By jwitmer Date 2003-12-10 Time 16:36 Rev Time 2.00
Received By jwitmer Date 2003-12-10 Time 16:36 Sent To  
Notes
2003-12-10 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03110709
 ADD: 4047 OKEECHOBEE BLVD SUITE 211
 CONT: HOBAN CONSTRUCTION
 TEL: (561)631-0070
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
 1) 1021.4 DOORS THAT SWING INTO AN EXIT
 CORRIDOR SHALL BE RECESSED TO PREVENT
 INTERFERENCE WITH CORRIDOR TRAFFIC; ANY
 DOORS NOT RECESSED SHALL OPEN 180 DEGREE
 TO STOP AGAINST THEWALL.
  
 2)1005.4 EMERGENCY ESCAPE AND RESCUE
 OPENINGS,
 (2) EVERY ROOM OR SPACE GREATER THAN
 250 FT USED FOR CLASSROOM OR OTHER ED-
 UCATIONAL PURPOSES OR NORMALLY SUBJECT
 TO STUDENT OCCUPANCY, AND EVERY ROOM
 SUBJECT TO CLIENT OCCUPNCY SHALL NOT
 HAVE NOT LESS THAN ONE OUTSIDE WINDOW
 FOR EMERGENCY RESCUE, SEE EXCEPTIONS:
 1) FIRE SPRINKLERS, GIVE LOCATION OF
 THE EXISTING FIRE SPRINKLERS.
  
 3)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PROVIDE FLOOR PLAN OF THE TOTAL SCHOOL.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-11-17 Cont ID  
Sent By jleahy Date 2003-11-17 Time 11:06 Rev Time 0.45
Received By jleahy Date 2003-11-14 Time 11:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-04-22 Cont ID  
Sent By nmccray Date 2004-04-22 Time 13:36 Rev Time 0.00
Received By nmccray Date 2004-04-22 Time 13:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-12-12 Cont ID  
Sent By mcarsill Date 2003-12-12 Time 07:25 Rev Time 0.00
Received By mcarsill Date 2003-12-12 Time 07:25 Sent To  
Notes
2003-12-12 00:00:001) PLANS DO NOT INDICATE WHAT TYPE OF
 OCCUPANCY IS DEPICTED. IS IT
 EDUCATIONAL OR BUSINESS.
  
 2) PLANS MAKE NO REFERENCE ABOUT ANY
 EMERGENCY LIGHTS.
  
 3) PLANS MAKE NO MENTION OF INTERIOR
 FINISH CLASSIFICATION.
  
 4) EXISTING BATHROOM SWINGS DIRECTLY
 INFRONT OF EXISTING EXIT DOOR.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-20 Cont ID  
Sent By csiegber Date 2004-04-20 Time 16:46 Rev Time 0.00
Received By csiegber Date 2004-04-20 Time 16:46 Sent To  
Notes
2004-04-20 00:00:00TO COMM BD#19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-11-14 Cont ID  
Sent By csiegber Date 2003-11-14 Time 15:26 Rev Time 0.00
Received By csiegber Date 2003-11-14 Time 15:26 Sent To  
Notes
2003-11-14 00:00:00TO COMM BD#8

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-04-23 Cont ID  
Sent By jwitmer Date 2004-04-23 Time 15:07 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***