| Plan Review Stops For Permit 03110607 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
15 |
Status |
P |
Date |
2005-10-11 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2005-10-11 |
Time |
07:54 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2005-10-11 |
Time |
07:54 |
Sent To |
|
|
| Notes |
| 2005-10-11 00:00:00 | BUILDING PLAN REVIEW | | | ******PROVISO******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | ARCHITECTURAL SUBMITTAL ON 10/7/05 FOR | | | LETTER DATED 9/29/05 REFERING TO | | | INSULATION ON SUSPENDED CEILING. | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | F.S.= FLORIDA (STATE) STATUTE | | | | | | --PROVISO-- | | | FBC 13-404.1.ABCD.2 PLENUMS.SUPPLY AND | | | RETURN AIR PLENUMS MUST HAVE AN | | | INSULATED ROOF. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
14 |
Status |
P |
Date |
2005-07-26 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2005-07-26 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2005-07-26 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2005-07-26 00:00:00 | REVISION SUBMITTED 7/12/05 CHANGING THE | | | STOREFRONT DOORS FOR THE EXISTING | | | MASONRY BUILDING TO IMPACT RATED ARCXH | | | ALUMINUM AND GLASS CO. DOORS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
13 |
Status |
P |
Date |
2005-07-14 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2005-07-14 |
Time |
12:07 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2005-07-14 |
Time |
12:07 |
Sent To |
|
|
| Notes |
| 2005-07-14 00:00:00 | REVISION SUBMITTED 7/7/05 CHANGING THE | | | WINDOWS FOR THE EXISTING MASONRY | | | BUILDING TO FIXED IMPACT RATED WINDOWS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
12 |
Status |
P |
Date |
2005-07-14 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2005-07-14 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2005-07-14 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2005-07-14 00:00:00 | SUBMITTAL ON 7/7/05 FOR RODUCT APPROVAL | | | AND ATTACHMENT DETAILS FOR STORM PANELS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
11 |
Status |
P |
Date |
2005-06-30 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2005-06-30 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2005-06-30 |
Time |
12:00 |
Sent To |
|
|
| Notes |
| 2005-06-30 00:00:00 | ARCHITECTURAL REVISION TO USE | | | WINTECH WINDOWS INSTEAD OF PGT. | | | NOTE:THE QUALITY ASSURANCE USED FOR | | | LOCAL PRODUCT APPROVAL OF THE WINTECH | | | WINDOWS IS GOOD FOR USE BY MARION | | | CONSTRUCTION INC ONLY. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
10 |
Status |
P |
Date |
2005-06-09 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2005-06-09 |
Time |
19:16 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2005-06-09 |
Time |
19:15 |
Sent To |
|
|
| Notes |
| 2005-06-09 00:00:00 | STRUCTURAL SUBMITTAL ON 5/4/05 FOR FRONT | | | ENTRY. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
P |
Date |
2005-02-18 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2005-02-18 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2005-02-18 |
Time |
11:41 |
Sent To |
|
|
| Notes |
| 2005-02-18 00:00:00 | BUTLER MANUFACTURING METAL BUILDING | | | SHOP DRAWINGS SUBMITTED ON 2/2/05 AND | | | RE-SUBMITTED ON 2/14/05 (PLUS ARCHITECT | | | OF RECORD LETTER DATED 2/17/05). |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
F |
Date |
2005-02-15 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2005-02-15 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2005-02-15 |
Time |
11:54 |
Sent To |
|
|
| Notes |
| 2005-02-15 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | BUTLER MANUFACTURING METAL BUILDING | | | SHOP DRAWINGS SUBMITTED ON 2/2/05 AND | | | RE-SUBMITTED ON 2/14/05. | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | F.S.= FLORIDA (STATE) STATUTE | | | | | | 1) FBC 1804.4FOOTING DESIGN.THE | | | FOUNDATION REACTION TABLE FOR THE FRAME | | | AT SIDEWALL GRIDS 2 & 4 (BUTLER DRAWING | | | NO. D05-124126-01A) GIVES A MAXIMUM | | | POSITIVE REACTION OF 46.2 KIPS FOR THE | | | COLUMNS AT GRIDS A AND E.STRUCTURAL | | | SHEET S-1 SPECIFIES A 4'-0" X 4'-0" PAD | | | FOOTING AT EACH OF THESE FOUR COLUMN | | | LOCATIONS.THE GROUND BEARING PRESSURE | | | WILL EXCEED THE SOIL BEARING CAPACITY OF | | | 2500 PSF, STATED ON SHEET A-1.AMEND | | | THE PLANS OR SUBMIT CALCULATIONS TO | | | DEMONSTRATE COMPLIANCE. | | | | | | 2) FBC 1804.4FOOTING DESIGN.SIMILAR | | | TO THE ABOVE COMMENT, THE FOUNDATION | | | REACTION TABLE FOR THE ENDWALL FRAME AT | | | SIDEWALL GRID 6 (BUTLER DRAWING NO. | | | D05-124126-01A) GIVES A MAXIMUM POSITIVE | | | REACTION OF 11.6 KIPS FOR THE COLUMN AT | | | GRID E.STRUCTURAL SHEET S-1 SPECIFIES | | | A 2'-0" X 2'-0" PAD FOOTING FOR THIS | | | COLUMN LOCATION.THE GROUND BEARING | | | PRESSURE WILL EXCEED THE SOIL BEARING | | | CAPACITY OF 2500 PSF, STATED ON SHEET | | | A-1.AMEND THE PLANS OR SUBMIT | | | CALCULATIONS TO DEMONSTRATE COMPLIANCE. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | TELEPHONE: (561) 805 6716ROBERT BROWN | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2005-02-04 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2005-02-04 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2005-02-04 |
Time |
10:27 |
Sent To |
|
|
| Notes |
| 2005-02-04 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | BUTLER MANUFACTURING METAL BUILDING | | | SHOP | | | DRAWINGS SUBMITTED ON 2/2/05. | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | F.S.= FLORIDA (STATE) STATUTE | | | | | | 1) STRUCTURAL SHOP DRAWINGS SHALL BE | | | REVIEWED AND STAMPED BY THE | | | ENGINEER/ARCHITECT OF RECORD, FOR THE | | | PROJECT, BEFORE SUBMITTAL. | | | | | | 2) 471.025 F.S.ENGINEER'S SIGNATURE | | | ON | | | THE PLANS.THE SUBMITTED SHEETS HAVE A | | | RAISED SEAL BUT THE SIGNATURE IS A | | | PHOTOCOPY.THE COPY SHALL BE SIGNED | | | WITH THE ORIGINAL 'WET' SIGNATURE OF | | | THE | | | RESPONSIBLE ENGINEER. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2005-02-04 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2005-02-04 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2005-02-04 |
Time |
10:09 |
Sent To |
|
|
| Notes |
| 2005-02-04 00:00:00 | ARCHITECT OF RECORD LETTER DATED 2-2-05 | | | AND REVISED SHEETS A-3 AND S-1 | | | SUBMITTED ON 2-3-05 COVERING PROPOSED | | | REVISIONS TO THE SLAB. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2005-02-02 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2005-02-02 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2005-02-02 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2005-02-02 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | ARCHITECT OF RECORD LETTER SUBMITTED ON | | | 1-26-05 COVERING PROPOSED REVISIONS TO | | | THE SLAB. | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | F.S.= FLORIDA (STATE) STATUTE | | | | | | 1) FBC* 104.2.1THE SUBMITTAL OF A | | | LETTER COVERING NUMEROUS PROPOSED | | | REVISIONS IS NOTED BUT REVISED PLANS | | | MUST BE SUBMITTED TO REFLECT THE | | | PROPOSED REVISIONS. | | | | | | 2) FBC* 104.6 FEES.A REVISION FEE OF | | | $50.00 PLUS $10.00 PER REVISED SHEET IS | | | PAYABLE. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL | | | INFO | | | TELEPHONE: (561) 805 6716ROBERT | | | BROWN | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2004-12-15 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2004-12-15 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2004-12-15 |
Time |
16:10 |
Sent To |
|
|
| Notes |
| 2004-12-15 00:00:00 | BUILDING PLAN REVIEW | | | ******PROVISO******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | --PROVISO-- | | | A SEPARATE PERMIT APPLICATION AND | | | PRODUCT APPROVAL PACKAGE WILL BE | | | REQUIRED FOR THE BUILT-UP ROOFING. | | | | | | --PROVISO-- | | | SUBMIT STRUCTURAL SHOP DRAWINGS FOR THE | | | METAL BUILDING FOR REVIEW. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2004-12-10 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2004-12-10 |
Time |
17:06 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2004-12-10 |
Time |
17:06 |
Sent To |
|
|
| Notes |
| 2004-12-14 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | IGNORE COMMENT #2 BELOW.ARCHITECT OF | | | RECORD REDLINED, SIGNED AND DATED A | | | HANDWRITTEN NOTE, GIVING WINDOW TYPE | | | AND SIZE. THE OTHER COMMENTS STILL | | | APPLY | | | | | | | | 2004-12-10 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | F.S.= FLORIDA (STATE) STATUTE | | | | | | THE MARION CONSTRUCTION COMMENT RESPONSE | | | LETTER DATED 11/22/04 IS NOTED WITH THE | | | FOLLOWING COMMENTS: | | | | | | 1) THE DOORS AND WINDOWS IN THE NEW | | | METAL BUILDING ARE STATED TO BE PART OF | | | THE METAL BUILDING DESIGN SUBMITTAL | | | PACKAGE BUT AS OF 12/10/04 THAT PACKAGE | | | HAS NOT BEEN SUBMITTEDTO THIS OFFICE. | | | THE DOOR AND WINDOW PRODUCT APPROVALS | | | ARE REQUIRED BEFORE THE PERMIT CAM BE | | | ISSUED. | | | | | | 2) SUBMITTAL OF A PRODUCT APPROVAL FOR | | | PGT SINGLE HUNG WINDOWS IS NOTED, BUT | | | THE PLANS DO NOT STATE THE SIZE OR TYPE | | | OF WINDOWS SO THAT THE DESIGN WIND | | | PRESSURES GIVEN IN THE PRODUCT APPROVAL | | | MAY BE VERIFIED. | | | | | | --PROVISO-- | | | A SEPARATE PERMIT APPLICATION AND | | | PRODUCT APPROVAL PACKAGE WILL BE | | | REQUIRED FOR THE BUILT-UP ROOFING. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | TELEPHONE: (561) 805 6716ROBERT BROWN | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2004-10-25 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2004-10-25 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2004-10-25 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2004-10-25 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | | | FOR CONSISTENCY, THE FOLLOWING COMMENTS | | | ARE NUMBERED AS PER THE BUILDING PLAN | | | REVIEW OF 12/18/03: | | | | | | 1) THE SUBMITTED NOTICE OF COMMENCEMENT | | | HAS EXPIRED AND SHOULD BE RE-RECORDED AT | | | PALM BEACH COUNTY COURTHOUSE AND A COPY | | | SUBMITTED TO THIS OFFICE BEFORE A PERMIT | | | CAN BE ISSUED. | | | | | | 2) IMPACT FEES. THE PLANS SHALL BE TAKEN | | | TO PALM BEACH COUNTY BUILDING DEPARTMENT | | | FOR IMPACT FEE ASSESSMENT. THEY SHALL BE | | | STAMPED AT THAT OFFICE AND A COPY OF THE | | | PAID RECEIPT SUBMITTED TO THE CITY OF | | | WEST PALM BEACH DEPT OF CONSTRUCTION | | | SERVICES BEFORE A PERMIT CAN BE ISSUED. | | | | | | 3) FBC 13-103.1.1.1ONLY ONE COPY OF | | | THE SUBMITTED ENERGY CODE COMPLIANCE | | | FORMS WAS SIGNED BY THE PROFESSIONAL | | | RESPONSIBLE FOR THE DESIGN OF THE | | | BUILDING SHELL AND THE ELECTRICAL, | | | LIGHTING, MECHANICAL AND PLUMBING | | | SYSTEMS.SIGN THE SECOND COPY. | | | | | | 18) THIS COMMENT HAS NOT BEEN ADDRESSED. | | | SUBMIT PRODUCT APPROVALS FOR THE | | | ROOFING, NEW AND REPLACEMENT WINDOWS, | | | ROLL-UP DOOR, EXTERIOR DOOR AND STORM | | | SHUTTERS. | | | NOTE: FL. ADMIN CODE RULE 9B-72 (IN | | | EFFECT SINCE OCTOBER 1, 2003) REQUIRES | | | THAT PRODUCTS HAVE STATEWIDE, LOCAL OR | | | SITE-SPECIFIC PRODUCT APPROVAL.THE | | | SUBMITTAL SHOULD INCLUDE THE STATEWIDE | | | PRODUCT APPROVAL NUMBER (FL###), | | | AVAILABLE FROM THE DEPT OF COMMUNITY | | | AFFAIRS PRODUCT APPROVAL WEBSITE | | | WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | TELEPHONE: (561) 805 6716ROBERT BROWN | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-12-18 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2003-12-18 |
Time |
12:26 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2003-12-18 |
Time |
12:26 |
Sent To |
|
|
| Notes |
| 2003-12-18 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | | | 1) THE NOTICE OF COMMENCEMENT SHALL BE | | | RECORDED AT PALM BEACH COUNTY COURTHOUSE | | | AND A COPY SUBMITTED TO THIS OFFICE | | | BEFORE A PERMIT CAN BE ISSUED.BLANK | | | FORMS ARE AVAILABLE FROM THIS OFFICE. | | | | | | 2) IMPACT FEES. THE PLANS SHALL BE TAKEN | | | TO PALM BEACH COUNTY BUILDING DEPARTMENT | | | FOR IMPACT FEE ASSESSMENT. THEY SHALL BE | | | STAMPED AT THAT OFFICE AND A COPY OF THE | | | PAID RECEIPT SUBMITTED TO THE CITY OF | | | WEST PALM BEACH DEPT OF CONSTRUCTION | | | SERVICES BEFORE A PERMIT CAN BE ISSUED. | | | | | | 3) FBC 13-103.1.1.1ENERGY CODE | | | COMPLIANCE FORM.THE ELECTRICAL SYSTEM | | | DESIGNER, LIGHTING SYSTEM DESIGNER, | | | MECHANICAL SYTEM DESIGNER AND PLUMBING | | | SYSTEM DESIGNER ENTRIES ON SHEET 2 OF | | | FORM SHALL EACH BE COMPLETED BY THE | | | SYSTEM DESIGNER, IN THIS CASE THE | | | ARCHITECT, TO CERTIFY COMPLIANCE FOR | | | THOSE SYSTEMS. | | | | | | 4) FBC 303.1 ABD FBC 312.1WAREHOUSE: | | | STORAGE OCCUPANCY V HAZARDOUS OCCUPANCY. | | | ANNOTATE THE PLANS TO STATE WHAT TYPE | | | AND QUANTITIES OF MATERIALS ARE TO BE | | | STORED, SO THAT ANY HAZARDOUS (GROUP H) | | | OCCUPANCY CAN BE DETERMINED. | | | | | | 5) FBC* F102.2.4ROOF COVERINGS IN THE | | | FIRE DISTRICT SHALL CONFORM TO THE | | | REQUIREMENTS OF CLASS A OR B | | | (REF: FBC 1505).ANNOTATE THE PLANS TO | | | MEET THIS REQUIREMENT WITH RESPECT TO | | | THE NEW ROOF, AND THE NEW ROOFING | | | MATERIALS PROPOSED FOR THE EXISTING ROOF | | | | | | 6) FBC* F102.2.5FIRE RESISTANCE FOR | | | BUILDINGS IN THE FIRE DISTRICT. | | | BUILDINGS GREATER THAN ONE STOREY, WHICH | | | ARE NOT EITHER SPRINKLERED THROUGHOUT OR | | | SURROUNDED ON ALL SIDES BY A PERMANENTLY | | | OPEN SPACE OF LEAST 30 FT, SHALL HAVE | | | ALL WALLS, FLOORS, ROOFS AND THEIR | | | SUPPORTING STRUCTURAL MEMBERS AT LEAST | | | 1-HOUR FIRE RESISTANT.AMEND THE PLANS. | | | | | | 7) FBC* F102.2.6FIRE RESISTANCE FOR | | | EXTERIOR WALLS OF TYPE IV BUILDINGS IN | | | THE FIRE DISTRICT.FOR TYPE IV | | | BUILDINGS, EXTERIOR WALLS WITHIN 30 FT | | | OF A COMMON PROPERTY LINE SHALL BE AT | | | LEAST 2-HOUR FIRE-RESISTANT.AMEND THE | | | PLANS. | | | | | | 8) FBC TABLE 600NORTH EXTERIOR WALL. | | | THE 2ND FLOOR PLAN ON SHEET A-2 SHOWS AN | | | OPENING FOR AN EXHAUST FAN.A FIRE | | | DAMPER OR ALTERNATIVE APPROVED MEANS OF | | | PROTECTION SHALL BE PROVIDED IN | | | ACCORDANCE WITH FBC 705.1.1.2.AMEND/ | | | ANNOTATE THE PLANS. | | | | | | 9) FBC TABLE 600AND FBC* F102.2FOR | | | THOSE EXTERIOR WALLS REQUIRED TO BE FIRE | | | RESISTANT, THE COLUMNS, CLADDING RAILS, | | | RAFTERS AND PURLINS, THAT PROVIDE | | | SUPPORT AND LATERAL RESTRAINT TO THE | | | WALL SHALL ALSO BE FIRE-RATED/PROTECTED. | | | | | | 10) FBC* 104.2.1.2 SHEET S-1, FOUNDATION | | | PLAN.AMEND THE PLAN TO SHOW THE SIZE | | | AND DEPTH OF THE EXISTING FOOTINGS SHOWN | | | ON SECTION A-3/2 TO RECEIVE ADDITIONAL | | | LOAD FROM THE NEW MEZZANINE AND ROOF. | | | | | | 11) FBC 2207 SHEET A-3, SECTIONS 2,3 & 4 | | | ANNOTATE THE PLANS TO REFERENCE AISC | | | SPECIFICATIONS FOR FIELD WELDING, | | | WORKMANSHIP, TECHNIQUE AND INSPECTION, | | | AND THE QUALIFICATION OF THE WELDERS. | | | | | | 12) FBC 1027.1.1 AND FBC 1027.2 | | | SHEET A-1, GROUND FLOOR PLAN OF THE | | | STORAGE OCCUPANCY.THE ROLL-UP DOORS | | | CANNOT BE CONSIDERED AS CONTRIBUTING TO | | | THE EGRESS PROVISIONS SINCE EXIT DOORS | | | MUST BE SWING DOORS CONFORMING TO THE | | | REQUIREMENTS OF FBC 1012.1.2 | | | (REF: FBC 1027.2).A SINGLE EXIT IS NOT | | | ACCEPTABLE AS THE MAXIMUM TRAVEL | | | DISTANCE TO THE NEAREST EXIT WOULD | | | EXCEED 50 FT (REF: FBC 1027.1.1).AMEND | | | THE PLANS TO PROVIDE AT LEAST TWO EXIT | | | DOORS FROM THE STORAGE AREA. | | | | | | 13) FBC 1006.1.4THE SPACE UNDER THE | | | NORTH STAIR SHALL BE ENCLOSED AND NON- | | | USABLE, OR THE SOFFIT SHALL BE 1-HOUR | | | FIRE-RESISTANT. | | | | | | 14) FBC 1007.3SHEET A-1.THE NORTH | | | STAIR IS SHOWN ON THIS SHEET WITH 10" | | | TREADS.THE TREADS SHALL BE MIN 11". | | | AMEND THE PLAN. | | | | | | 15) FBC 1608.2HANDRAIL AND GUARDRAIL | | | STRENGTH.AMEND THE PLANS TO STATE THE | | | HANDRAIL AND GUARDRAIL STRENGTH | | | REQUIREMENTS TO RESIST EACH OF THE | | | CONCENTRATED LOADS AND LINEAR | | | DISTRIBUTED LOADS REQUIRED BY THE CODE. | | | THE 50 PLF STATED ON THE SHEET A-2, | | | HANDRAIL DETAIL IS NOTED BUT DOES NOT | | | COVER THE OTHER LOADING REQUIREMENTS | | | REFERENCED ABOVE. | | | | | | 16) FBC 11-4.26.3SHEET A-2.AMEND THE | | | PLAN TO STATE THE REQUIREMENT FOR THE | | | GRAB BARS AND THEIR MOUNTING AND | | | FASTENERS TO RESIST A FORCE OF 250 LB | | | APPLIED IN ANY DIRECTION WITHOUT | | | EXCEEDING THE ALLOWABLE STRESS FOR THE | | | MATERIAL. | | | | | | 17) FBC 11-4.15SHEET A-2. WHAT APPEARS | | | TO BE DETAILS OF DRINKING FOUNTAIN | | | HEIGHTS AND CLEARANCES ARE INCORRECTLY | | | TITLED "GRAB BARS AT WATER CLOSETS". | | | AMEND THE TITLE. | | | | | | 18) SUBMIT PRODUCT APPROVALS FOR THE | | | ROOFING, NEW AND REPLACEMENT WINDOWS, | | | ROLL-UP DOOR, EXTERIOR DOOR AND STORM | | | SHUTTERS. | | | NOTE: FL. ADMIN CODE RULE 9B-72 (IN | | | EFFECT SINCE OCTOBER 1, 2003) REQUIRES | | | THAT PRODUCTS HAVE STATEWIDE, LOCAL OR | | | SITE-SPECIFIC PRODUCT APPROVAL.THE | | | SUBMITTAL SHOULD INCLUDE THE STATEWIDE | | | PRODUCT APPROVAL NUMBER (FL###), | | | AVAILABLE FROM THE DEPT OF COMMUNITY | | | AFFAIRS PRODUCT APPROVAL WEBSITE | | | WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP | | | | | | 19) IF NEW PLAN SHEETS ARE REQUIRED, IN | | | ORDER TO ADDRESS THE ABOVE COMMENTS, THE | | | OLD SHEETS SHALL BE REMOVED AND THE NEW | | | SHEETS INSERTED.ONE COPY OF EACH OLD | | | SHEET SHALL BE INCLUDED WITH THE | | | RESUBMITTAL FOR COMPARISON OF REVISIONS. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | TELEPHONE: (561) 805 6716ROBERT BROWN | | | E-MAIL: [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2005-01-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-01-07 |
Time |
16:07 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2005-01-07 |
Time |
16:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2004-12-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-12-28 |
Time |
10:30 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-12-28 |
Time |
10:30 |
Sent To |
|
|
| Notes |
| 2004-12-28 00:00:00 | *********** UNSAT 3RD REVIEW ********** | | | | | | **** PLEASE SEE NOTES #'S 3 AND 4 FROM | | | PREVIOUS REVIEW ARE STILL THE SAME. | | | PLEASE SEE ATTACHED PREVIOUS COMMENTS. | | | | | | 1)NOTE: PLEASE SEE 250.6,250.24, THERE | | | IS NO EQUIPMENT GROUNDING CONDUCTOR | | | FROM | | | METER TO MAIN(FIRST MEANS OF DISC). | | | | | | 2)NOTE: PLEASE CORRELATE RISER DIAGRAM | | | WITH FEEDER SCHEDULE ON PANEL | | | SCHEDULES. | | | 215.5 | | | | | | *** NEW NOTE*** | | | | | | 1)NOTE: PLEASE SEE PLANS ARE NOW | | | SIGNED, | | | DATED AND SEALED BY AN ENGINEER AS | | | BEING | | | RESPONSIBLE FOR PLANS. | | | PLEASE SEE FAC 61G15-23.002, A TITLE | | | BLOCK IS REQUIRED ON PLANS WITH | | | INFORMATION AS SETFORTH IN FAC/ FS. | | | | | | PLEASE SEE ATACHED COPY OF FS | | | 553.80(2)(B) WITH RESPECT TO DESIGN | | | PROFESSIONAL | | | WITH REPEAT COMMENTS. | | | THIS IS GIVEN ONLY AS A NOTICE AT THIS | | | TIME. | | | | | | PLEASE BE SURE TO REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS FOR REVIEW AND STAMPING. | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2004-11-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-11-30 |
Time |
06:36 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2004-11-30 |
Time |
06:25 |
Sent To |
|
|
| Notes |
| 2004-11-30 00:00:00 | *********** UNSAT ******** | | | | | | 1)NOTE: PLEASE SEE # OF CONDUCTORS | | | INDICATED ON RISER FROM METER TO MAIN. | | | THIS IS A 3-PHASE SERVICE, YET ONLY | | | SHOWS 3-CONDUCTORS. | | | | | | 2)NOTE: PLEASE ALSO SEE #OF CONDUCTORS | | | SHOWN IN A SINGLE 2" CONDUIT. PLEASE | | | SEE | | | TABLES IN CHAPTER 9 NEC FOR CONDUIT | | | FILL. | | | | | | 3)NOTE: PLEASE SEE AN EQUIPMENT | | | GROUNDING CONDUCTOR IS NOW SHOWN FROM | | | METER TO MAIN. AN EQUIPMENT GRND IS NOT | | | INSTALLED FROM METER TO THE FIRST MEANS | | | OF DISCONNECT. 250.6,250.24. | | | | | | 4)NOTE: PLEASE CORRELATE RISER WITH | | | PANEL "A" FEEDER SCHEDULE, AS ON NOTES | | | ABOVE. | | | | | | 5)NOTE: PLEASE SEE RE-SUB SHEET | | | MENTIONS | | | PERMIT APPLIACTION TO BE BROUGHT IN BY | | | THE 11/24. THIS IS REQUIRED WHEN | | | RE-SUBMITTING PLANS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | INSERT NEW SHEET(S) FOR COMPLETE SETS | | | FOR REVIEW AND STAMPING. | | | | | | PLEASE BE SURE ALL REVIEWS ARE DONE | | | BEFORE MAKING ANY CORRECTIONS, DUE TO | | | ANY POSSIBLE COMMENTS FROM OTHER | | | REVIEW(ERS). | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2004-10-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-10-15 |
Time |
13:21 |
Rev Time |
1.25 |
| Received By |
dpalmer |
Date |
2004-10-15 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2004-10-15 00:00:00 | ************* UNSAT ************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | THIS IS REQUIRED AT THIS TIME. | | | | | | 2)NOTE: PLEASE SEE 700.12E FOR CIRCUIT- | | | -ING OF EM/EXT LTS. | | | | | | 3)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR FROM MCB TO PANEL | | | "B".? 250.110,250.24,250.122 | | | | | | 4)NOTE: PLEASE SEE PANEL "B" IS SHOWN ON | | | A SP BRKR SPACE? #29 PLEASE SEE FEED TO | | | PANEL "B" IS SHOWN AS A 3P-200A BRKR TO | | | PANEL "B" WHICH IS INDICATED AS A SINGLE | | | PHASE PANEL ON PANEL SCHEDULE INFORMAT- | | | -ION?? WHICH ONE? | | | | | | 5)NOTE: PLEASE SEE SPACE #28 ON PANEL | | | SCHEDULE "A". THIS SHOWS AN ADDITIONAL | | | 2-P60A BRKR FOR SUB PANEL "B". | | | PLEASE CLARIFY?? | | | IF THERE IS INDEED AN ADDITIONAL 60A | | | SUB-PANEL, PLEASE ALSO INCLUDE THIS ON | | | RISER DIAGRAM. | | | | | | 6 )NOTE: PLEASE SHOW LOAD CALCULATIONS, | | | PLEASE SHOW PER | | | 220.3,220.10,220.11,220.13 ETC. | | | PLEASE ALSO SHOW ALL CONTINOUS LOADS | | | AT 125% PER 215.3,230.42 | | | PLEASE SEE PLAN S DO NOT INLCUDE ANY | | | LOAD CALCULATIONS? | | | PLEASE SEE 220.3 FOR SPECIFIC LIGHTING | | | LOADS FOR HIGH-BAY FIXTURES ETC. | | | | | | 7)NOTE: PLEASE SEE 600.5 FOR REQUIRED | | | SIGN CIRCUIT. EXISTING OR NEW?? | | | | | | PLEASE SEE POSSIBLE COMMENTS FROM OTHER | | | REVIEWERS WHICH MAY HAVE AN AFFECT ON | | | ELECTRICAL PLANS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW SHEETS INTO COMPLETE | | | SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2003-11-21 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2003-11-21 |
Time |
09:52 |
Rev Time |
1.00 |
| Received By |
jleahy |
Date |
2003-11-21 |
Time |
09:51 |
Sent To |
|
|
| Notes |
| 2003-11-21 00:00:00 | NEED AIC RATING FOR THE SERVICE | | | PROVIDE INFORMATION B4 ROUGH INSPECTION | | | JAKE805-6740 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2004-11-30 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2004-11-30 |
Time |
08:36 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2004-11-30 |
Time |
08:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2004-10-15 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2004-10-13 |
Time |
14:38 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2004-10-13 |
Time |
14:38 |
Sent To |
|
|
| Notes |
| 2004-10-13 00:00:00 | FAILED: | | | 1. A CLEAN-OUT WILL NEED TO BE INSTALLED | | | IN SANITARY SEWER LATERAL , ON THE | | | PROPERTY AND BACK OF SIDEWALK. | | | 2. A DOUBLE DETECTOR CHECK ASSEMBLY IN | | | FIRE LINE AFTER THE 4" GATE VALVE ON THE | | | PROPERTY AND AT BACK OF THE SIDEWALK IS | | | REQUIRED. | | | 3. PLEASE SUBMIT CIVIL PLANS ONLY TO THE | | | PUBLIC UTILITIES ATT: MANNY GONZALEZ, | | | 494-1085, ALL CONNECTIONS TO THE CITY | | | SERVICES MUST BE APPROVED BY THE | | | UTILITIES. | | | 4. IS THE EXISTING WATER METER ADEQUATE? | | | PLEASE VERIFY. | | | 5. INSTALLATION OF NEW OFF STREET | | | PARKING ON FERNWOOD DRIVE MAY CREATE | | | DRAINAGE PROBLEMS IN THIS SECTION OF | | | THE ROAD, PLEASE REVISIT. | | | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2004-12-16 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2004-12-16 |
Time |
11:59 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2004-12-16 |
Time |
11:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2004-09-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-09-28 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-09-28 |
Time |
15:42 |
Sent To |
|
|
| Notes |
| 2004-09-28 00:00:00 | 1) EMERGENCY LIGHTS AND EXIT SIGNAGE | | | IN MEZZANINE. | | | | | | 2) EMERGENCY LIGHTS IN WAREHOUSE. | | | | | | 3) PLEASE EXPLAIN EXITING RATIONALE | | | FROM WAREHOUSE. | | | | | | 4) SOME PREVIOUS COMMENTS DO NOT APPEAR | | | TO HAVE BEEN ADDRESSED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2003-11-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-11-26 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-11-26 |
Time |
16:59 |
Sent To |
|
|
| Notes |
| 2003-11-26 00:00:00 | 1) BUILDING ADDRESS REQUIRED. 6" HIGH | | | NUMBERS ARE REQUIRED. | | | | | | 2) 10" TREADS ARE NOT PERMITTED ON | | | STAIRS. EXIT STAIRS FROM SECOND FLOOR | | | THAT LEADS TO THE EXTERIOR DISPLAYS | | | 10" TREADS. | | | | | | 3) HOW DOES FIRE AND PARAMEDICAL | | | EQUIPMENT GAIN ACCESS THRU NEW GATE. | | | | | | 4) DEMOLITION ACTIVITIES TO COMPLY | | | WITH NFPA 241, THE STANDARD FOR | | | DEMOLITION, RENOVATION, AND CONSTRUCTION | | | | | | 5) SITE PLAN DOES NOT INDICATE ANY | | | EXISTING OR NEW FIRE HYDRANTS FOR THE | | | VICINITY. | | | | | | 6) PLEASE PROVIDE HEIGHTS OF THE | | | PROPOSED STORAGE RACKS. | | | | | | 7) THE 42" AISLE NEAR THE DISPATCH | | | AREA SHALL BE AT LEAST 44" WIDE. | | | | | | 8) WHAT IS PLANNED TO BE STORED ON | | | THE STORAGE RACKS. | | | | | | 9) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATIONS FOR WALLS AND | | | CEILINGS. | | | | | | 10) THE 2668 DOOR FOR THE STORAGE ROOM | | | UNDER THE STAIRS SHALL BE AT LEAST | | | 45 MINUTE FIRE RATED. | | | | | | 11) NO INDICATION THAT THE STORAGE | | | ROOM OR STAIR DOOR ARE RATED AT THE | | | SECOND FLOOR/MEZZANINE PLAN. | | | | | | 12) TACTILE SIGNAGE REQUIRED AT STAIRS. | | | | | | 13) PLEASE PROVIDE PRESCRIPTIVE STRENGTH | | | REQUIREMENTS FOR ALL HANDRAILS AND | | | GAURDRAILS. | | | | | | 14) ARE ANY EMERGENCY LIGHTS PRESENT | | | IN THE STAIRS. ALSO ARE ALL EXIT | | | SIGNS SHOWN ON E-1. NO EMERGENCY | | | LIGHTING IN WAREHOUSE. | | | | | | 15) WELDER NOTED ON PAGE E-3. ALL | | | WELDING MUST BE APPROVED BY THE | | | BUREAU OF FIRE PREVENTION. ALL | | | WELDING OPERATIONS TO COMPLY WITH | | | NFPA 51B. A CLEAR RADIUS OF 35 FEET | | | IS REQUIRED FROM WELDING TO COMBUSTIBLES | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
13 |
Status |
N |
Date |
2005-07-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-14 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-14 |
Time |
13:04 |
Sent To |
B |
|
| Notes |
| 2005-07-14 00:00:00 | TO "RBROWN" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2005-07-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-07-07 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-07-07 |
Time |
14:37 |
Sent To |
B |
|
| Notes |
| 2005-07-07 00:00:00 | TO "RBROWN" DESK/1 REV AND 1 SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2005-06-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-06-15 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-06-15 |
Time |
16:02 |
Sent To |
M |
|
| Notes |
| 2005-06-15 00:00:00 | TO MECH BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2005-05-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-04 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-04 |
Time |
16:16 |
Sent To |
B |
|
| Notes |
| 2005-05-04 00:00:00 | TO "RBROWN" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2005-02-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-18 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-18 |
Time |
09:21 |
Sent To |
B |
|
| Notes |
| 2005-02-18 00:00:00 | TO RBROWN DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2005-02-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-14 |
Time |
16:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-14 |
Time |
16:00 |
Sent To |
B |
|
| Notes |
| 2005-02-14 00:00:00 | TO RBROWN DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2005-02-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-03 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-03 |
Time |
16:22 |
Sent To |
B |
|
| Notes |
| 2005-02-03 00:00:00 | TO RBROWN DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2005-01-26 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-01-26 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-01-26 |
Time |
15:53 |
Sent To |
B |
|
| Notes |
| 2005-01-26 00:00:00 | TO "RB" DESK/SUBMITTALS. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-01-07 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-01-07 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-01-07 |
Time |
15:10 |
Sent To |
E |
|
| Notes |
| 2005-01-07 00:00:00 | TO "DP" DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2004-12-22 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2004-12-22 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-12-22 |
Time |
09:09 |
Sent To |
E |
|
| Notes |
| 2004-12-22 00:00:00 | SENT TO "DP" DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-11-23 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2004-11-23 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-11-23 |
Time |
15:25 |
Sent To |
|
|
| Notes |
| 2004-11-23 00:00:00 | SENT TO COMM BD#17 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-09-14 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-09-14 |
Time |
12:02 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-09-14 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2004-09-14 00:00:00 | TO COMM BD#41 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-12-18 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2003-12-18 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2003-11-12 |
Time |
15:30 |
Sent To |
|
|
| Notes |
| 2003-11-18 00:00:00 | 11/12/03TO Z | | | TO COMM BD#19 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2005-09-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-09-23 |
Time |
07:38 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2005-09-23 |
Time |
06:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2005-06-23 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-06-23 |
Time |
10:47 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2005-06-23 |
Time |
10:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2004-10-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-10-05 |
Time |
06:45 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2004-10-05 |
Time |
06:37 |
Sent To |
|
|
| Notes |
| 2004-10-05 00:00:00 | PROVISO: | | | 1.FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | | REQUIRED WITH NOTIFICATION TO ALARM & | | | STROBE IN NORMALLY OCCUPIED AREAS 2001 | | | FBC(M) 606.2.1 & 606.4.1. | | | | | | 2.NO COMBUSTIBLES ALLOWED ABOVE THE | | | CEILING IN THE RETURN AIR PLENUM PER | | | 2001 FBC(M) 602.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2003-12-15 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-12-15 |
Time |
09:21 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2003-12-15 |
Time |
08:54 |
Sent To |
|
|
| Notes |
| 2003-12-15 00:00:00 | DENIED: | | | 1.FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | | REQUIRED PER 2001 FBC(M) 606.2.1. | | | | | | 2.FAN SHUTDOWN SHALL HAVE NOTIFICATION | | | TO ALARM/STROBE IN NORMALLY OCCUPIED | | | AREAS PER 2001 FBC(M) 606.4.1 & NFPA 90A | | | 4-4.4.3. | | | | | | 3.PLEASE INDICATE WHAT TYPE OF WORK | | | WILL BE DONE IN THE WAREHOUSE (WELDING, | | | PREFAB OF PIPE?). | | | | | | 4.INDICATE IF ANY HAZARDOUS MATERIALS | | | OR GASES WILL STORED ON SITE. | | | | | | 5.CONDENSER UNITS LOCATED ON THE ROOF | | | SHALL COMPLY WITH 2001 FBC 1511.7. | | | | | | 6.PROVIDE OUTSIDE AIR CALCULATIONS PER | | | 2001 FBC(M) 403.3. | | | | | | 7.PLEASE NOTE, EQUIPMENT LOCATED ON | | | THE ROOFS WHERE ACCESS IS GREATER THAN | | | 16 FT, A PERMANENT MEANS OF ACCESS SHALL | | | BE PROVIDED. 2001 FBC(M) 306.5 | | | | | | 8.PLEASE PROVIDE INFORMATION ON THE | | | CONDENSATE.PLAN SHEET M-1 NOTE 15 | | | INDICATES CONDENSATE TO THE EXTERIOR. | | | PLEASE PROVIDE PIPE LAYOUT. CONDENSATE | | | SHALL TERMINATE A MINIMUM OF 12" FROM | | | THE BUILDING STRUCTURE PER 2001 FBC | | | 1503.4.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2004-10-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-10-09 |
Time |
12:18 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2004-10-09 |
Time |
12:18 |
Sent To |
|
|
| Notes |
| 2004-10-09 00:00:00 | PASSED/PROVISO | | | | | | BREAK AREA SINK TO COMPLY WITH SECTION | | | 11-4.24 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-12-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-12-13 |
Time |
15:55 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2003-12-13 |
Time |
15:54 |
Sent To |
|
|
| Notes |
| 2003-12-13 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT A-1 SANT. RISER DIAGRAM. SERVICE | | | SINK AND DRINKING FOUNTAIN SHALL NOT | | | DRAIN THROUGH THE WET VENT FOR THE BATH | | | ROOM FIXTURES. 909.1 - THE SERVICE SINK | | | AND DRINKING FOUNTAIN SHALL CONNECT | | | DOWNSTREAM OF THE BATHROOM FIXTURES. | | | 2) PROVISIONS SHALL BE MADE FOR THOSE | | | WHO HAVE DIFFICULTY BENDING OR STOOPING | | | SECTION 11-4.1.3(10)(A). (A DRINKING CUP | | | DISPENSER WILL MEET THIS REQUIREMENT) | | | 3) SUBMIT A DETAIL SHOWINC COMPLIANCE | | | WITH 11-4.24 FOR THE LOUNGE SINK. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2003-12-16 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2003-12-16 |
Time |
09:19 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2003-12-16 |
Time |
09:19 |
Sent To |
|
|
| Notes |
| 2003-12-16 00:00:00 | GRACE APPROVED HAVE INFORMAL SITE PLAN M | | | M |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2003-11-18 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-11-12 |
Time |
15:30 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2003-11-18 |
Time |
09:59 |
Sent To |
I |
|
| Notes |
| 2003-11-18 00:00:00 | 11/17/03 NEED TO APPLY FOR LEVEL 1 | | | CALLED CONTR MM |
|
|