Plan Review Details - Permit 03110525
Plan Review Stops For Permit 03110525
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-03-08 Cont ID  
Sent By alange Date 2004-03-08 Time 09:34 Rev Time 0.66
Received By alange Date 2004-03-08 Time 09:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-02-27 Cont ID  
Sent By csiegber Date 2004-03-04 Time 13:29 Rev Time 0.66
Received By alange Date 2004-02-27 Time 15:23 Sent To  
Notes
2004-02-27 00:00:00PRODUCT APPROVAL FOR REVISION NOT LISTED
 ON THE FBC PRODUCT APPROVAL SITE.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-02-02 Cont ID  
Sent By csiegber Date 2004-02-19 Time 14:00 Rev Time 0.50
Received By alange Date 2004-02-02 Time 12:43 Sent To  
Notes
2004-02-02 00:00:00PROVISO
 SEPERATE ELECTRICAL PERMIT REQUIRED
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-01-15 Cont ID  
Sent By alange Date 2004-01-15 Time 09:29 Rev Time 0.50
Received By alange Date 2004-01-15 Time 09:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-07 Cont ID  
Sent By csiegber Date 2003-12-19 Time 16:28 Rev Time 0.00
Received By alange Date 2004-01-07 Time 10:44 Sent To  
Notes
2004-01-07 00:00:00DENIED
 1.2 X 10 FRAMING IS IT FLOOR OR
 CEILING.NEW OR EXISTING?
 2.WHAT ARE THE BEAMS SUPPORTING SHOW
 DETAILS.
 3.DRAWINGS TO VAGUE TO UNDERSTAND
 SCOPE OF WORK.
 4. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
 5.SPACE TO BE FULLY ACCESSABLE.
 6.PROVIDE BUILDING USE.
 7.SHOW BATHROOM LOCATION.
  
 ANY QUESTIONS PLEASE CALL.
 ART LANGE
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2004-01-30 Cont ID  
Sent By dpalmer Date 2004-01-30 Time 13:42 Rev Time 0.25
Received By dpalmer Date 2004-01-30 Time 13:42 Sent To  
Notes
2004-01-30 00:00:00ELECTRICAL PLANS VOIDED AND NOT FOR
 REVIEW PER CONTRACTORS REQUEST.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-01-15 Cont ID  
Sent By dpalmer Date 2004-01-15 Time 11:06 Rev Time 0.75
Received By dpalmer Date 2004-01-15 Time 11:06 Sent To  
Notes
2004-01-15 00:00:00***************** UNSAT ************
  
 1)NOTE: PLEASE PROVIDE INFORMATION ON
 USEAGE OF SPACE.
  
 2)NOTE: PLEASE PROVIDE ALL LICENSE #'S
 AND REQ'D TITLE BLOCK INFORMATION ON
 ALL SHEETS AND PLANS. PER FS 471/481
 FAC 61G15-23.002/ 61G1-16.004
 THIS IS REQ'D FOR ALL TRADES WEATHER
 OR NOT COMMENT IS MADE.
 FS 471.023, FS 481.219
  
 3)NOTE: PLEASE PROVIDE ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULE
 (S) TO BE SUBMITTED.
  
 4)NOTE: PLEASE SEE 700.12E FOR EM/ EXT
 LTS.
  
 5)NOTE: PLEASE SEE ELECTRICAL RM, SHOWN
 WITH NO REQ'D LIGHTING. 700.16, LS 101
 5-8.
  
 6)NOTE: PLEASE SEE 220.12A FOR MIN
 OF SHOW WINDOW LOADS.
 SEE 600.5 FOR DEDICATED SIGN CIRCUIT.
 ETC.
  
 7)NOTE: PLEASE VERIFY SIZE OF METER CAN
 FOR 450A SERVICE SHOWN. SERVICE IS
 SHOWN EXSITING?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2004-01-29 Cont ID  
Sent By btrobaug Date 2004-02-27 Time 08:39 Rev Time 0.00
Received By mcarsill Date 2004-01-29 Time 08:01 Sent To  
Notes
2004-01-29 00:00:001) EXIT SIGN DIRECTING PERSONS INTO
 SHED IS TO BE REMOVED. PEOPLE ARE
 NOT TO EXIT INTO AND OUT OF A SHED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2004-01-16 Cont ID  
Sent By mcarsill Date 2004-01-16 Time 15:33 Rev Time 0.00
Received By mcarsill Date 2004-01-16 Time 15:33 Sent To  
Notes
2004-01-16 00:00:001) FAILED TO LABEL PLANS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-01-02 Cont ID  
Sent By mcarsill Date 2004-01-02 Time 15:21 Rev Time 0.00
Received By mcarsill Date 2004-01-02 Time 15:21 Sent To  
Notes
2004-01-02 00:00:001) AREAS NEED TO BE LABELED AS TO WHAT
 THEY ARE.
  
 2) PLANS DO NOT INDICATE ANY EXISTING
 OR NEW EXIT SIGNS OR EMERGENCY LIGHTS.
  
 3) PLANS DO NOT INDICATE OCCUPANCY
 TYPE OR OCCUPANT LOADS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-01-02 Cont ID  
Sent By mcarsill Date 2004-01-02 Time 15:12 Rev Time 0.00
Received By mcarsill Date 2004-01-02 Time 15:12 Sent To  
Notes
2004-01-02 00:00:001) AREAS NEED TO BE LABELED AS TO WHAT
 THEY ARE.
  
 2) PLANS DO NOT INDICATE ANY EXISTING
 EXIT SIGNS OR EMERGENCY LIGHTS.
  
 3) PLANS DO NOT INDICATE OCCUPANCY
 TYPE OR OCCUPANT LOADS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-03-04 Cont ID  
Sent By csiegber Date 2004-03-04 Time 13:29 Rev Time 0.00
Received By csiegber Date 2004-03-04 Time 13:28 Sent To B
Notes
2004-03-04 00:00:00TO AL DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-02-19 Cont ID  
Sent By csiegber Date 2004-02-19 Time 14:00 Rev Time 0.00
Received By csiegber Date 2004-02-19 Time 14:00 Sent To B
Notes
2004-02-19 00:00:00TO AL DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-01-27 Cont ID  
Sent By csiegber Date 2004-01-27 Time 09:59 Rev Time 0.00
Received By csiegber Date 2004-01-27 Time 09:59 Sent To  
Notes
2004-01-27 00:00:00TO COMM BD#25
 `

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-01-14 Cont ID  
Sent By csiegber Date 2004-01-14 Time 16:22 Rev Time 0.00
Received By csiegber Date 2004-01-14 Time 16:22 Sent To  
Notes
2004-01-14 00:00:00TO COMM BD#5

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-12-30 Cont ID  
Sent By csiegber Date 2003-12-30 Time 10:42 Rev Time 0.00
Received By csiegber Date 2003-12-30 Time 10:42 Sent To  
Notes
2003-12-30 00:00:00TO COMM BD#50

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-12-30 Cont ID  
Sent By alange Date 2003-12-30 Time 10:36 Rev Time 0.00
Received By alange Date 2003-12-30 Time 10:36 Sent To  
Notes
2003-12-30 00:00:00NOT RES. NEEDS TO GO ON THE COMMERCIAL
 BOARD ALANGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-19 Cont ID  
Sent By csiegber Date 2003-12-19 Time 16:28 Rev Time 0.00
Received By csiegber Date 2003-12-19 Time 16:28 Sent To  
Notes
2003-12-19 00:00:00TO RES BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved