Plan Review Details - Permit 03110456
Plan Review Stops For Permit 03110456
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-06-25 Cont ID  
Sent By jgomez Date 2004-06-25 Time 15:06 Rev Time 0.33
Received By jgomez Date 2004-06-25 Time 15:06 Sent To PC
Notes
2004-06-25 00:00:00THRESHOLD INSPECTOR CERTIFICATION LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-05-12 Cont ID  
Sent By csiegber Date 2004-06-23 Time 10:41 Rev Time 0.33
Received By jgomez Date 2004-05-12 Time 16:59 Sent To PC
Notes
2004-05-12 00:00:00REMAINDER:
 PLEASE SUBMIT CERTIFICATE OF COMPLIANCE
 AFFIDAVIT FROM THE THRESHOLD INSPECTOR
 FOR OFF-SITE CONSTRUCTED COMPONENTS
 (ROYAL WALL PRODUCTS).

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-04-22 Cont ID  
Sent By jgomez Date 2004-04-22 Time 12:24 Rev Time 0.33
Received By jgomez Date 2004-04-22 Time 12:24 Sent To PC
Notes
2004-04-22 00:00:00BUILDING REVIEW CHECKLIST:
 1-PERMIT ENGINEERING SERVICES CERT. #
 IS NOT CORRECT. IT DOESN'T MATCH THE
 NUMBER REGISTERED WITH THE FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS.
  
 2-PROVIDE ALL THE INFORMATION AS REQ'D
 BY CHAPTER 471 FLORIDA STATUTES. SEE
 ATTACHED COPY OF CHAPTER 61G15-23 FOR
 INFORMATION REQUIRED TO BE PROVIDED BY
 ENGINEER WHEN SUBMITTING INFORMATION
 FOR PUBLIC RECORDS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-03-31 Cont ID  
Sent By csiegber Date 2004-04-12 Time 11:38 Rev Time 2.50
Received By jgomez Date 2004-03-31 Time 15:59 Sent To PC
Notes
2004-03-31 00:00:00BUILDING REVIEW PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-ENGINEER TO UPDATE ROYAL WALL PANELS
 DESIGN CRITERIA. NEED TO USE ACI 318
 2002 EDITION NOT 1995.(CALLED ALBERT
 KWAN ON 3-31-04 AND HE AGREED TO
 UPDATE INFORMATION).

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-03-08 Cont ID  
Sent By csiegber Date 2004-03-17 Time 11:39 Rev Time 3.50
Received By jgomez Date 2004-03-05 Time 17:41 Sent To PC
Notes
2004-03-05 00:00:00BUILDING REVIEW CHECKLIST:
 1-SITE SPECIFIC PRODUCT APPROVAL FOR
 ROYAL WALL SYSTEM DOESN'T MEET THE
 REQUIREMENTS STIPULATED ON THE FORM:
 A)NEED APPROVED THIRD PARTY QUALITY
 ASSURANCE ENTITY.
 B)EVALUATION REPORT DOCUMENTATION WITH
 INFORMATION REQUIRED BY 9B-72.040(5)
 WAS NOT SUBMITTED.
 C)NEED COMPLETE ENGINEERED WALL PANELS
 PACKAGE FOR THIS SITE SPECIFIC INSTA-
 LLATION.
 D)PROVIDE COMPLETE DETAILS AND SPECS FOR
 WOOD LEDGERS AT SECOND FLOOR. ARCHITEC
 TURAL PLANS SAY TO SEE STRUCTURAL DWGS
 AND STRUCTURAL DWGS SAY CONNECTION BY
 OTHERS. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
 2-PERMIT ENGINEERING SERVICES COMPANY
 REGISTERED NUMBER SHOWN ON PLANS DOES
 NOT MATCH FLORIDA REGISTERED NUMBER.
 CLARIFY/REVISE AS REQUIRED.
 3-PRODUCT APPROVALS NEED THE FOLLOWING:
 A)ENTRY DOORS: NEED FLORIDA REPORT AND
 DRAWINGS TO MATCH. THERMA-TRU DOORS &
 BENCHMARK DOORS ARE 2 DIFFERENT DOORS.
 PROVIDE DWGS OF DOORS TO BE INSTALLED
 AND MATCHING PRODUCT APPROVAL PACKAGE.
 B)TRUSS CONNECTORS:PROVIDE FLORIDA OR
 LOCAL PRODUCT APPROVAL INFORMATION
 ALONG WITH DADE COUNTY DRAWINGS.
  
 4-PROVIDE INFO. FOR STORM SHUTTERS. NEED
 FLORIDA OR LOCAL PRODUCT APPROVAL AND
 COMPLETE INSTALLATION SCHEDULE, KEY
 PLAN, ETC.
 5-ENGINEERING CALCULATIONS FOR TRUSS
 ANCHORS FASTENER TYPE/NUMBER DIFFERENT
 THAN THOSE PUBLISHED BY MANUFACTURER
 TO HAVE ORIGINAL SEAL, SIGNATURE AND
 DATE AND TO HAVE ALL ENGINEER'S INFO.
 AS REQUIRED BY CHAPTER 471 FL. STATUTE
 WHEN SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS.
 6-NOTICE OF COMMENCEMENT IS VOID BECAUSE
 CONSTRUCTION DIDN'T STARTED WITHIN 90
 DAYS AFTER RECORDATION.
 7-OWES $18.20 FOR UPDATED VALUATION AND
 RADON FEES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-01-07 Cont ID  
Sent By pkrauss Date 2004-03-01 Time 15:37 Rev Time 4.00
Received By jgomez Date 2004-01-06 Time 16:39 Sent To PC
Notes
2004-01-06 00:00:00BUILDING REVIEW CHECKLIST:
 1-SURVEY FOOTPRINT DOESN'T MATCH PLANS.
 2-AFFINITI ARCHITECT TO SIGN, SEAL,DATE
 ALL PLANS AS REQUIRED BY CHAPTER 481
 FLORIDA STATUTES WHEN SUBMITTING PLANS
 FOR PUBLIC RECORDS. ALSO, SEE REQ'D
 INFORMATION TO BE ON TITLE BLOCK.
 3-PERMIT ENGINEERING SERVICES COMPANY
 REGISTERED NUMBER DOESN'T MATCH NUMBER
 ON FBPE. CLARIFY/REVISE AS REQ'D.
 4-DESIGN CRITERIA: NEED TO ADD 30PSF OR
 10PSF ATTIC LIVE LOAD AS REQUIRED BY
 TABLE 1604.1 FBC 2001.
 5-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENING AS REQUIRED BY SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
 6-CLARIFY IF FIXED WINDOWS AT DINING,
 LIVING ROOM AND ALL TRANSOM WINDOWS
 ARE BUTT GLAZING, STRUCTURAL MULLIONS
 OR FIXED MUNTINGS. REVISE DWGS TO
 SHOW CORRECT INSTALLATION. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-IMPACT GLAZING AT DEN WINDOW WILL NOT
 COMPLY WITH SECTION 1005.4.5. NEED TO
 PROVIDE EMERGENCY EGRESS FROM AN AREA
 THAT CANN'T BE LOCKED. REVISE STORM
 SHUTTERS INSTALLATION SCHEDULE AS WELL
 8-PROVIDE FLORIDA PRODUCT APPROVAL OR
 COMPLETE SITE SPECIFIC ENGINEERING W/
 ALL DOCUMENTATION REQUIRED BY THE
 STATE (SEE WWW.FLORIDABUILDING.ORG)
 FOR ROYAL WALL SYSTEM, SLIDING GLASS
 DOORS, SINGLE HUNG WINDOWS,ENTRY DOOR,
 GARAGE DOORS, TRUSS ANCHORS,ROOF TILE,
 FIXED WINDOWS, WINDOW MULLIONS, GLASS
 BLOCK.
 9-PROVIDE FLORIDA PRODUCT APPROVAL OR
 SITE SPECIFIC COMPLETE INFORMATION FOR
 STORM SHUTTERS. KEY PLAN TO MATCH
 PLANS, INSTALLATION SCHEDULE TO MATCH
 INFORMATION ON ENGINEERED DWGS. THIS
 MODEL HAS WOOD APPLICATIONS ALSO.
 10-PROVIDE COMPLETE GABLE END DETAIL
 SHOWING COMPLIANCE WITH SEC. 2117 FBC
 WHICH REQUIRES STRUCTURAL CONTINUITY.
 11-CLARIFY WHY ARE THERE TWO DIFFERENT
 TRUSS ANCHOR SCHEDULES. SEE SHEET RF-1
 AND SD-2. ALSO, UPDATE TRUSS ANCHOR
 SCHEDULE AND ALL DETAILS THAT ARE
 AFFECTED BY SEC. 1609.4.3 FBC 2001
 WHICH DOESN'T ALLOW THE STEEL STRESS
 TO BE INCREASED.
 **NOTE: ONLY USP 2003 AND SIMPSON HIGH
 WIND RESISTANT CONSTRUCTION CATALOGUES
 WERE REVISED TO SATISFY THIS SECTION.
 USE IETHER WHEN SELECTING CONNECTORS.
 PROVIDE COMPLETE ENGINEERING ANALYSIS
 FOR DIFFERENT VALUES AND FASTENINGS
 OTHER THAN THOSE PUBLISHED.
 12-NEED RECORDED NOTICE OF COMMENCEMENT.
 13-OWES $18.20 FOR UPDATED VALUATION.
 14-SHEET #3: A)UPDATE CONNECTORS. HUGHES
 IS OUT OF BUSINESS. SEE COMMENTS.
 B)REVISE HANDRAIL HEIGHT SHOWN ON BLDG
 SECTION 1/3. SEE SEC. 1007.5.1 FBC/01.
 C)STUCCO TO BE 7/8" MIN. SEE ASTM C-926.
 D)PROVIDE GIRDER/WALL CONNECTION DETAIL
 THAT REFLECTS ACTUAL CONDITIONS SHOWN
 ON PLANS. SAME APPLIES TO 2 STORY
 BEARING WALL. DON'T USE GENERIC DETAIL
 15-SHEET #7: A) CLARIFY/UPDATE INFO.
 SEE COMMENTS.
 16-SHEET #1 OF STRUCTURAL DRAWINGS:
 A)PROVIDE DETAIL/SPECS FOR CONNECTION
 OF ROYAL WALL SYSTEM TO WOOD FRAMING.
 IT SAYS CONNECTION BY BUILDER, BUT,
 THERE ARE NOT SPECS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 B)PROVIDE COMPLETE DETAILS/SPECS FOR
 FRAMED WALL BY OTHERS. NEED COMPLETE
 DETAILS/SPECS, CONNECTIONS, FRAMING
 FOR OPENINGS TO RECEIVE STORM SHUTTERS
 & SHOW HOW SHEARWALL ARE TRANSFERRED.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-12-04 Cont ID  
Sent By btrobaug Date 2003-12-04 Time 13:28 Rev Time 0.50
Received By btrobaug Date 2003-12-04 Time 13:10 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-06-23 Cont ID  
Sent By csiegber Date 2004-06-23 Time 10:41 Rev Time 0.00
Received By csiegber Date 2004-06-23 Time 10:41 Sent To B
Notes
2004-06-23 00:00:00TO JG DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-04-14 Cont ID  
Sent By csiegber Date 2004-04-14 Time 09:57 Rev Time 0.00
Received By csiegber Date 2004-04-14 Time 09:57 Sent To M
Notes
2004-04-14 00:00:00TO PK BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-04-12 Cont ID  
Sent By csiegber Date 2004-04-12 Time 11:37 Rev Time 0.00
Received By csiegber Date 2004-04-12 Time 11:37 Sent To B
Notes
2004-04-12 00:00:00TO JG DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-03-17 Cont ID  
Sent By csiegber Date 2004-03-17 Time 11:39 Rev Time 0.00
Received By csiegber Date 2004-03-17 Time 11:39 Sent To B
Notes
2004-03-17 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-02-25 Time 14:55 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 14:55 Sent To M
Notes
2004-02-25 00:00:00TO PK BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-07 Cont ID  
Sent By mmclean Date 2003-11-17 Time 14:02 Rev Time 0.00
Received By csiegber Date 2003-11-10 Time 10:23 Sent To  
Notes
2003-11-26 00:00:0011/26/03 TO SFD RACK/E
2003-11-10 00:00:0011/10/03 TO Z
 11/21/03 TO Z RESUB

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-03-01 Cont ID  
Sent By csiegber Date 2004-04-14 Time 09:57 Rev Time 0.35
Received By pkrauss Date 2004-03-01 Time 15:32 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-12-10 Cont ID  
Sent By csiegber Date 2004-02-25 Time 14:55 Rev Time 0.50
Received By hmoser Date 2003-12-10 Time 15:38 Sent To B
Notes
2003-12-10 00:00:00PASS PRIVISO
 1) REFER TO SECTION 307.2.3 AUXILIARY
 DRAIN PAN.AUXILIARY DRAIN PANS SHALL BE
 INSTALLED UNDER ALL COILS ON WITCH
 CONDENSATION WILL OCCUR.
 2) RETURN AIR REQUIREMENTS TO COMPLY
 WITH THE FLORIDA BUILDING CODE (M) 2003
 CHANGES.CHANGES WENT INTO EFFECT JULY 1
 2003

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-12-06 Cont ID  
Sent By jleech Date 2003-12-06 Time 09:55 Rev Time 0.50
Received By jleech Date 2003-12-06 Time 09:55 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2003-11-25 Cont ID  
Sent By mmclean Date 2003-11-25 Time 14:55 Rev Time 0.00
Received By mmclean Date 2003-11-25 Time 14:55 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-11-17 Cont ID  
Sent By csiegber Date 2003-11-21 Time 16:11 Rev Time 0.00
Received By mmclean Date 2003-11-17 Time 14:02 Sent To I
Notes
2003-11-17 00:00:0011/17/03 SURVEY/FLOOR/FOUNDATION/ELEC
 PLANS DOES NOT MATCH NEED TO FLIP CALLED
 CONTR MM