2003-11-21 00:00:00******CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)IMPACT PROTECTION REQUIRED FOR
 GLAZING FBC1606.1.4.PER EXCEPTION
 FBC3401.7.2.4, THE TWO REPACEMENT
 WINDOWS SHOWN ON THE PLAN WILL NOT
 REQUIRE OPENING PROTECTION IF THE
 AGGREGATE AREA OF THE GLAZING IN THE
 REPLACED COMPONENTS DOES NOT EXCEED THE
 AGGREGATE AREA OF THE GLAZED OPENINGS
 IN THE DWELLING.IF YOU WOULD LIKE TO
 BE EXEMPTED FROM IMPACT PROTECTION
 REQUIREMENTS, SUBMIT CALCULATIONS
 (EXISTING GLAZED OPENINGS, GLAZING IN
 THE REPLACED COMPONENTS).
  
 2.)STATEWIDE PRODUCT APPROVALS
 REQUIRED, 9B-72, FOR WINDOWS, IMPACT
 PROTECTION (IF APPLICABLE), SIDING (SEE
 ATTACHED), DOOR.SUBMIT THE STATEWIDE
 PRODUCT APPROVAL NUMBER OR COVER SHEET
 WITH THE TEST REPORT (SUCH AS SBCCI OR
 DADE COUNTY NOA).FOR MORE INFORMATION,
 WWW.FLORIDABUILDING.ORG.
  
 3.)WHAT TYPE OF ROOM IS LOCATED WHERE
 THE WINDOWS ARE TO BE REPLACED? BEDROOMS
 ARE TO COMPLY WITH FBC1005.4, EMERGENCY
 EGRESS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-11-14 Cont ID  
Sent By csiegber Date 2003-11-10 Time 15:06 Rev Time 0.33
Received By btrobaug Date 2003-11-14 Time 14:28 Sent To P
Notes
2003-11-14 00:00:00DENIED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE A LOAD CALCULATION
 SHOWING EXISTING LOADS AND ALL NEW
 LOADS.SEE ARTICLE 220 NEC.THE
 CALCULATION GIVEN IS NOT IN THE CORRECT
 FORMAT.
 ALSO THE NOTE INDICATING A/C WILL NOT
 BE USED WHEN HEATER IS IN USE IS NOT
 ACCEPTABLE,THERE IS NO LANGUAGE IN THE
 NEC THAT CONSIDERS THESE NON-CONCURRENT
 LOADS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-11-10 Cont ID  
Sent By csiegber Date 2003-11-10 Time 11:20 Rev Time 0.00
Received By csiegber Date 2003-11-10 Time 11:20 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-11-20 Cont ID  
Sent By btrobaug Date 2003-11-14 Time 14:43 Rev Time 0.33
Received By kstevens Date 2003-11-20 Time 14:27 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved