Plan Review Details - Permit 03110330
Plan Review Stops For Permit 03110330
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-01-13 Cont ID  
Sent By mjacobs Date 2005-01-13 Time 13:58 Rev Time 0.00
Received By prafter Date 2005-01-26 Time 11:02 Sent To M
Notes
2005-01-27 00:00:00PROVISO:PROVIDE R/A OUT OFFICE .
 OCCUPATIONAL LICEND REQUIRED
 IF CONDUCTING A BUSNESS FROM THE HOME.
 PAT RAFTER 561/805/6725 OR 805/6719.
2005-01-13 00:00:00TO "M/AC" BOX./REV.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-01-28 Cont ID  
Sent By csiegber Date 2004-01-28 Time 14:29 Rev Time 0.00
Received By csiegber Date 2004-01-28 Time 14:29 Sent To M
Notes
2004-01-28 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-12-22 Cont ID  
Sent By csiegber Date 2003-12-22 Time 12:57 Rev Time 0.00
Received By csiegber Date 2003-12-22 Time 12:57 Sent To M
Notes
2003-12-22 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-11-06 Cont ID  
Sent By csiegber Date 2003-11-06 Time 16:04 Rev Time 0.00
Received By csiegber Date 2003-11-06 Time 16:04 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-01-27 Cont ID  
Sent By prafter Date 2005-01-27 Time P Rev Time 1.00
Received By prafter Date 2005-01-27 Time 14:29 Sent To  
Notes
2005-01-27 00:00:00PROVISO:OFFICE REQUIRES RETURN AIR
 OUT OF ROOM.
 PCCUPATIONAL LICENSE REQUID IF
 CONDUCTING A BUSINESS FROM THE HOME.
 PAT RAFTER 561/805/6725 OR 805/6719

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2004-02-11 Cont ID  
Sent By pkrauss Date 2004-02-11 Time 07:03 Rev Time 0.33
Received By pkrauss Date 2004-02-11 Time 07:02 Sent To  
Notes
2004-02-11 00:00:00DENIED:
 PLEASE INDICATE MASTER BEDROOM ON PLAN.
 MASTER BEDROOM RETURN AIR SHALL BE SIZED
 ACCORDING TO THE TOTAL OF SUPPLY AIR TO
 THE MASTER SUITE. (6" SUPPLY TO BEDROOM
 WITH 4" SUPPLY TO BATHROOM FOR A TOTAL
 OF 10".RETURN SHALL BE A MINIMUM OF
 13").PLANS INDICATE TWO ADDITIONAL
 ROOMS WITH SUPPLY AIR WITH NO RETURNS
 INDICATED.PLEASE REVISE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-12-30 Cont ID  
Sent By csiegber Date 2004-01-28 Time 14:29 Rev Time 0.33
Received By pkrauss Date 2003-12-30 Time 07:34 Sent To  
Notes
2003-12-30 00:00:00DENIED:
 PROVISO FROM PREVIOUS REVIEW BY HAROLD
 MOSER WAS NOT ADDRESSED.
 RETURN AIR REQUIRED FROM BEDROOM AREAS
 PER REVISION TO THE 2001 FBC(M) 601.4.
 PLEASE PROVIDE PLANS INDICATING RETURN
 OR TRANSFER AIR DUCT/GRILLES.INDICATE
 DUCT/GRILLE SIZES SHOWING COMPLIANCE
 WITH THE AFOREMENTIONED CODE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-11-17 Cont ID  
Sent By csiegber Date 2003-12-22 Time 12:57 Rev Time 0.50
Received By hmoser Date 2003-11-17 Time 17:22 Sent To  
Notes
2003-11-17 00:00:00PASS PRIVISO
 1) REFER TO SECTION 604.1 BALANCED
 RETURN AIR REQUIREMENTS.CHANGES WENT
 INTO EFFECT JULY 1 2003.
 2) REFER TO SECTION 307.2.3 AUXILLIARY
 DRAIN PANS.AUXILLIARY DRAIN PANS SHALL
 BE INSTALLED UNDER ALL COILS WHICH
 CONDENSATION WILL OCCUR.
 3) NEED HEATER SIZE ON PLAN
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732