Plan Review Details - Permit 03110095
Plan Review Stops For Permit 03110095
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-05-24 Cont ID  
Sent By alange Date 2004-05-24 Time 09:37 Rev Time 0.50
Received By alange Date 2004-05-24 Time 09:37 Sent To  
Notes
2004-05-24 00:00:00ROYAL WALL INFO SUBMITTED OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-04-23 Cont ID  
Sent By csiegber Date 2004-05-21 Time 13:21 Rev Time 2.00
Received By shill Date 2004-04-23 Time 14:00 Sent To  
Notes
2004-04-23 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)RF1 AND THE MECHANICAL PAGE HAVE
 BEEN REVIEWED FOR CODE COMPLIANCE AND
 STAMPED.
  
 2.)IT IS UNCLEAR WHAT THE CHANGES
 ARE ON THE OTHER SHEETS SUBMITTED.ALL
 CHANGES ARE TO BE CLEARLY INDICATED
 WITH CLOUDS OR TRIANGLES.A NEW
 REVISION DATE IS GIVEN BUT I CAN'T
 LOCATE THE CHANGES.
  
 3.)SEPARATE PERMIT FOR SHUTTERS.
  
 4.)THE PRODUCT APPROVALS FOR THE
 CONNECTORS ARE DIFFICULT TO REVIEW.
 PLEASE PROVIDE A LIST OF THE CONNECTORS
 USED AND PROVIDE STATEWIDE PRODUCT
 APPROVAL FOR THOSE CONNECTORS.
  
 5.)THE CALCS SUBMITTED ARE LACKING
 THE INFORMATION REQUIRED BY FAC61G15-
 23.002.
  
 6.)SITE SPECIFIC PRODUCT APPROVAL
 APPLICATION WAS SUBMITTED FOR THE ROYALL
 WALL PRODUCT.THE PAPERWORK WAS NOT IN
 COMPLIANCE FAC9B-72.HOWEVER, MY
 UNDERSTANDING IS THAT THIS PRODUCT CAN
 BE APPROVED UNDER FBC103.7.ADDRESS.
  
 7.)ADDITIONAL FEES DUE.IF THE
 OTHER REVISED SHEETS ARE RESUBMITTED,
 THIS IS A REVISION, NOT A SUBMITTAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-12-30 Cont ID  
Sent By pkrauss Date 2004-04-19 Time 14:08 Rev Time 1.00
Received By shill Date 2003-12-30 Time 13:30 Sent To  
Notes
2003-12-30 00:00:00****PROVISO*****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)HHGT1 AND HHGT2, CONNECTOR KST260,
 NAILING CONFLICTS WITH CATALOG AND
 DESIGN UPLIFT ON PLAN EXCEEDS MAX
 ALLOWED BY THE CATALOG.REVISE RF1.
  
 2.)WOOD TO WOOD CONNECTORS ARE
 USED IN WOOD TO MASONRY APPLICATION;
 ADDRESS.REVISE RF1 OR SUBMIT
 CALCULATIONS.
  
 4.)SUBMIT SITE SPECIFIC OR STATEWIDE
 PRODUCT APPROVAL FOR THE FOLLOWING:
 GARAGE DOOR
 GLASS BLOCK
 SHUTTERS
 FIXED GLASS
  
 *****SUBMIT REVISIONS BEFORE FRAMING
 INSPECTION********

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-12-05 Cont ID  
Sent By csiegber Date 2003-12-29 Time 09:24 Rev Time 2.00
Received By sthyng Date 2003-12-04 Time 13:12 Sent To  
Notes
2003-12-04 00:00:00*****CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)THE ENGINEER'S NAME AND LICENSE
 NUMBER IS TO BE PRINTED ON THE PLAN,
 FAC61G15-23.002.
  
 2.)THE GIRDER/WALL CONNECTION (SHEET
 3) SPECIFIES HUGHES CONNECTORS; HUGHES
 IS NO LONGER IN BUSINESS.
  
 3.)THE WOOD CONSTRUCTION NOTES, ITEM
 #4, REFERS TO FBC3218.17.NOT IN FBC
 CODE BOOK.
  
 4.)HHGT1 AND HHGT2, CONNECTOR KST260
 SHEET RF1, NAILING CONFLICTS WITH
 CATALOG AND DESIGN UPLIFT ON THE PLAN
 EXCEEDS MAX ALLOWED BY THE CATALOG
 (USE THE GREY BAR WITHOUT STRESS
 INCREASE FOR STEEL, USP 2003 CATALOG).
  
 5.)WOOD-TO-WOOD CONNECTORS ARE
 SPECIFIED IN WOOD-TO-MASONRY
 APPLICATIONS; FOR EXAMPLE, USP HTW.
 ADDRESS.(SHEET RF1).
  
 6.)PROVIDE A FIREBLOCK DETAIL FOR
 THE DROPPED CEILINGS/SOFFITS, FBC
 705.3, 2305.1.4.
  
 7.)STATEWIDE, LOCAL OR SITE SPECIFIC
 PRODUCT APPROVALS REQUIRED FOR THE
 FOLLOWING:
 GARAGE DOOR
 GLASS BLOCK
 SHUTTERS
 TRUSS CONNECTORS
 FIXED WINDOW, NON IMPACT
 FIXED WINDOW, IMPACT
 PRINT THE COVER SHEET AND ATTACH TO
 THE NOA OR SBCCI REPORT.
  
 FOR CONNECTORS, PROVIDE A SCHEDULE
 WITH STATEWIDE PRODUCT APPROVAL
 NUMBERS.
  
 FOR MORE INFORMATION,
 WWW.FLORIDABUILDING.ORG
  
 8.)ARCHITECTURALS ARE FOR GARAGE L,
 STRUCTURALS AND SITE PLAN ARE FOR GARAGE
 RIGHT.
  
 9.)FEES DUE, $38.56 RADON, SEE
 ATTACHED BZ231387.
  
 10.) IF AFFINITI IS NOT THE DESIGNER
 OF RECORD AND ANOTHER ARCHITECT HAS
 SEALED THE PLAN, REMOVE AFFINITI'S TITLE
 BLOCK FROM THE PLAN.
  
 11.) SAFEGUARD (STORM SHUTTER SBCCI
 REPORT) IS NO LONGER IN BUSINESS. SUBMIT
 VALID PRODUCT APPROVALS FOR STORM
 SHUTTERS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-11-13 Cont ID  
Sent By btrobaug Date 2003-11-13 Time 16:58 Rev Time 0.50
Received By btrobaug Date 2003-11-13 Time 16:26 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-05-21 Cont ID  
Sent By csiegber Date 2004-05-21 Time 13:21 Rev Time 0.00
Received By csiegber Date 2004-05-21 Time 13:21 Sent To B
Notes
2004-05-21 00:00:00TO SH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-04-14 Cont ID  
Sent By csiegber Date 2004-04-14 Time 10:09 Rev Time 0.00
Received By csiegber Date 2004-04-14 Time 10:09 Sent To M
Notes
2004-04-14 00:00:00TO PK BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-12-29 Cont ID  
Sent By csiegber Date 2003-12-29 Time 09:23 Rev Time 0.00
Received By csiegber Date 2003-12-29 Time 09:23 Sent To B
Notes
2003-12-29 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-12-24 Cont ID  
Sent By mmclean Date 2003-12-24 Time 15:29 Rev Time 0.00
Received By csiegber Date 2003-12-24 Time 09:44 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-04 Cont ID  
Sent By sthyng Date 2003-12-04 Time 13:19 Rev Time 0.00
Received By sthyng Date 2003-11-04 Time 12:39 Sent To  
Notes
2003-11-05 00:00:00TO SFD RACK/E
2003-11-04 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-04-19 Cont ID  
Sent By pkrauss Date 2004-04-19 Time 14:08 Rev Time 0.30
Received By pkrauss Date 2004-04-19 Time 14:08 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-12-03 Cont ID  
Sent By csiegber Date 2004-04-14 Time 10:09 Rev Time 0.50
Received By hmoser Date 2003-12-03 Time 15:30 Sent To P
Notes
2003-12-03 00:00:001) REFER TO SECTION 307.2.3 AUXILIARY
 DRAIN PAN.AUXILIARY DRAIN PANS SHALL BE
 INSTALLED UNDER ALL COILS ON WITCH
 CONDENSATION WILL OCCUR.
 2) RETURN AIR REQUIREMENTS TO COMPLY
 WITH THE FLORIDA BUILDING CODE (M) 2003
 CHANGES.CHANGES WENT INTO EFFECT JULY 1
 2003

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-12-03 Cont ID  
Sent By hmoser Date 2003-12-03 Time 15:31 Rev Time 0.33
Received By jleech Date 2003-12-03 Time 17:00 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2003-12-24 Cont ID  
Sent By mmclean Date 2003-12-24 Time 15:29 Rev Time 0.00
Received By mmclean Date 2003-12-24 Time 15:29 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-11-05 Cont ID  
Sent By csiegber Date 2003-12-24 Time 09:44 Rev Time 0.00
Received By mmclean Date 2003-11-05 Time 16:11 Sent To  
Notes
2003-11-05 00:00:0011/5/03 DENIED, NEED TO HAVE SURVEY/
 FLOOR/MECH PLANS MATCHING CALLED VINCE
 LEFT MSG ON VOICE MAIL MM