| Plan Review Stops For Permit 03110095 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2004-05-24 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2004-05-24 |
Time |
09:37 |
Rev Time |
0.50 |
| Received By |
alange |
Date |
2004-05-24 |
Time |
09:37 |
Sent To |
|
|
| Notes |
| 2004-05-24 00:00:00 | ROYAL WALL INFO SUBMITTED OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2004-04-23 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-05-21 |
Time |
13:21 |
Rev Time |
2.00 |
| Received By |
shill |
Date |
2004-04-23 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2004-04-23 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)RF1 AND THE MECHANICAL PAGE HAVE | | | BEEN REVIEWED FOR CODE COMPLIANCE AND | | | STAMPED. | | | | | | 2.)IT IS UNCLEAR WHAT THE CHANGES | | | ARE ON THE OTHER SHEETS SUBMITTED.ALL | | | CHANGES ARE TO BE CLEARLY INDICATED | | | WITH CLOUDS OR TRIANGLES.A NEW | | | REVISION DATE IS GIVEN BUT I CAN'T | | | LOCATE THE CHANGES. | | | | | | 3.)SEPARATE PERMIT FOR SHUTTERS. | | | | | | 4.)THE PRODUCT APPROVALS FOR THE | | | CONNECTORS ARE DIFFICULT TO REVIEW. | | | PLEASE PROVIDE A LIST OF THE CONNECTORS | | | USED AND PROVIDE STATEWIDE PRODUCT | | | APPROVAL FOR THOSE CONNECTORS. | | | | | | 5.)THE CALCS SUBMITTED ARE LACKING | | | THE INFORMATION REQUIRED BY FAC61G15- | | | 23.002. | | | | | | 6.)SITE SPECIFIC PRODUCT APPROVAL | | | APPLICATION WAS SUBMITTED FOR THE ROYALL | | | WALL PRODUCT.THE PAPERWORK WAS NOT IN | | | COMPLIANCE FAC9B-72.HOWEVER, MY | | | UNDERSTANDING IS THAT THIS PRODUCT CAN | | | BE APPROVED UNDER FBC103.7.ADDRESS. | | | | | | 7.)ADDITIONAL FEES DUE.IF THE | | | OTHER REVISED SHEETS ARE RESUBMITTED, | | | THIS IS A REVISION, NOT A SUBMITTAL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2003-12-30 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-04-19 |
Time |
14:08 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2003-12-30 |
Time |
13:30 |
Sent To |
|
|
| Notes |
| 2003-12-30 00:00:00 | ****PROVISO***** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)HHGT1 AND HHGT2, CONNECTOR KST260, | | | NAILING CONFLICTS WITH CATALOG AND | | | DESIGN UPLIFT ON PLAN EXCEEDS MAX | | | ALLOWED BY THE CATALOG.REVISE RF1. | | | | | | 2.)WOOD TO WOOD CONNECTORS ARE | | | USED IN WOOD TO MASONRY APPLICATION; | | | ADDRESS.REVISE RF1 OR SUBMIT | | | CALCULATIONS. | | | | | | 4.)SUBMIT SITE SPECIFIC OR STATEWIDE | | | PRODUCT APPROVAL FOR THE FOLLOWING: | | | GARAGE DOOR | | | GLASS BLOCK | | | SHUTTERS | | | FIXED GLASS | | | | | | *****SUBMIT REVISIONS BEFORE FRAMING | | | INSPECTION******** |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-12-05 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-29 |
Time |
09:24 |
Rev Time |
2.00 |
| Received By |
sthyng |
Date |
2003-12-04 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2003-12-04 00:00:00 | *****CORRECTIONS****** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | | | | 1.)THE ENGINEER'S NAME AND LICENSE | | | NUMBER IS TO BE PRINTED ON THE PLAN, | | | FAC61G15-23.002. | | | | | | 2.)THE GIRDER/WALL CONNECTION (SHEET | | | 3) SPECIFIES HUGHES CONNECTORS; HUGHES | | | IS NO LONGER IN BUSINESS. | | | | | | 3.)THE WOOD CONSTRUCTION NOTES, ITEM | | | #4, REFERS TO FBC3218.17.NOT IN FBC | | | CODE BOOK. | | | | | | 4.)HHGT1 AND HHGT2, CONNECTOR KST260 | | | SHEET RF1, NAILING CONFLICTS WITH | | | CATALOG AND DESIGN UPLIFT ON THE PLAN | | | EXCEEDS MAX ALLOWED BY THE CATALOG | | | (USE THE GREY BAR WITHOUT STRESS | | | INCREASE FOR STEEL, USP 2003 CATALOG). | | | | | | 5.)WOOD-TO-WOOD CONNECTORS ARE | | | SPECIFIED IN WOOD-TO-MASONRY | | | APPLICATIONS; FOR EXAMPLE, USP HTW. | | | ADDRESS.(SHEET RF1). | | | | | | 6.)PROVIDE A FIREBLOCK DETAIL FOR | | | THE DROPPED CEILINGS/SOFFITS, FBC | | | 705.3, 2305.1.4. | | | | | | 7.)STATEWIDE, LOCAL OR SITE SPECIFIC | | | PRODUCT APPROVALS REQUIRED FOR THE | | | FOLLOWING: | | | GARAGE DOOR | | | GLASS BLOCK | | | SHUTTERS | | | TRUSS CONNECTORS | | | FIXED WINDOW, NON IMPACT | | | FIXED WINDOW, IMPACT | | | PRINT THE COVER SHEET AND ATTACH TO | | | THE NOA OR SBCCI REPORT. | | | | | | FOR CONNECTORS, PROVIDE A SCHEDULE | | | WITH STATEWIDE PRODUCT APPROVAL | | | NUMBERS. | | | | | | FOR MORE INFORMATION, | | | WWW.FLORIDABUILDING.ORG | | | | | | 8.)ARCHITECTURALS ARE FOR GARAGE L, | | | STRUCTURALS AND SITE PLAN ARE FOR GARAGE | | | RIGHT. | | | | | | 9.)FEES DUE, $38.56 RADON, SEE | | | ATTACHED BZ231387. | | | | | | 10.) IF AFFINITI IS NOT THE DESIGNER | | | OF RECORD AND ANOTHER ARCHITECT HAS | | | SEALED THE PLAN, REMOVE AFFINITI'S TITLE | | | BLOCK FROM THE PLAN. | | | | | | 11.) SAFEGUARD (STORM SHUTTER SBCCI | | | REPORT) IS NO LONGER IN BUSINESS. SUBMIT | | | VALID PRODUCT APPROVALS FOR STORM | | | SHUTTERS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2003-11-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-11-13 |
Time |
16:58 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2003-11-13 |
Time |
16:26 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2004-05-21 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-05-21 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-05-21 |
Time |
13:21 |
Sent To |
B |
|
| Notes |
| 2004-05-21 00:00:00 | TO SH DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2004-04-14 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-14 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-04-14 |
Time |
10:09 |
Sent To |
M |
|
| Notes |
| 2004-04-14 00:00:00 | TO PK BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-12-29 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-29 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-12-29 |
Time |
09:23 |
Sent To |
B |
|
| Notes |
| 2003-12-29 00:00:00 | TO SH DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-12-24 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2003-12-24 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-12-24 |
Time |
09:44 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-12-04 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-12-04 |
Time |
13:19 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-11-04 |
Time |
12:39 |
Sent To |
|
|
| Notes |
| 2003-11-05 00:00:00 | TO SFD RACK/E | | 2003-11-04 00:00:00 | TO Z |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2004-04-19 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-04-19 |
Time |
14:08 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2004-04-19 |
Time |
14:08 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2003-12-03 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-14 |
Time |
10:09 |
Rev Time |
0.50 |
| Received By |
hmoser |
Date |
2003-12-03 |
Time |
15:30 |
Sent To |
P |
|
| Notes |
| 2003-12-03 00:00:00 | 1) REFER TO SECTION 307.2.3 AUXILIARY | | | DRAIN PAN.AUXILIARY DRAIN PANS SHALL BE | | | INSTALLED UNDER ALL COILS ON WITCH | | | CONDENSATION WILL OCCUR. | | | 2) RETURN AIR REQUIREMENTS TO COMPLY | | | WITH THE FLORIDA BUILDING CODE (M) 2003 | | | CHANGES.CHANGES WENT INTO EFFECT JULY 1 | | | 2003 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2003-12-03 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2003-12-03 |
Time |
15:31 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2003-12-03 |
Time |
17:00 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2003-12-24 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2003-12-24 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2003-12-24 |
Time |
15:29 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2003-11-05 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-24 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2003-11-05 |
Time |
16:11 |
Sent To |
|
|
| Notes |
| 2003-11-05 00:00:00 | 11/5/03 DENIED, NEED TO HAVE SURVEY/ | | | FLOOR/MECH PLANS MATCHING CALLED VINCE | | | LEFT MSG ON VOICE MAIL MM |
|
|