Plan Review Details - Permit 03110094
Plan Review Stops For Permit 03110094
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-04-23 Cont ID  
Sent By csiegber Date 2004-05-21 Time 13:20 Rev Time 1.00
Received By shill Date 2004-04-23 Time 15:12 Sent To  
Notes
2004-04-23 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SUBMIT ONLY SHEETS WHICH HAVE
 CHANGED AS A REVISION, AND PAY A
 REVISION FEE.THE ENTIRE PLAN INCLUDING
 APPROVED PLUMBING, ELECTRIC AND
 BUILDING SHEETS WERE SUBMITTED.
  
 2.)SEPARATE PERMIT FOR SHUTTERS.
  
 3.)THE PRODUCT APPROVALS FOR THE
 CONNECTORS ARE DIFFICULT TO REVIEW.
 PROVIDE A LIST OF THE CONNECTORS YOU
 ARE USING AND PROVIDE STATEWIDE PRODUCT
 APPROVAL FOR THOSE CONNECTORS.
  
 4.)SUBMIT THE CALCS IN COMPLIANCE
 WITH FAC61G15-23.002.
  
 5.)SITE SPECIFIC PRODUCT APPROVALS
 WERE SUBMITTED FOR THE ROYALL WALL
 PRODUCT.THE PAPERWORK WAS NOT IN
 COMPLIANCE WITH FAC9B-72.ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-12-08 Cont ID  
Sent By csiegber Date 2004-04-14 Time 09:27 Rev Time 3.00
Received By shill Date 2003-12-03 Time 10:20 Sent To  
Notes
2003-12-08 00:00:00******PROVISO*******
  
 ADDRESS FOLLOWING CORRECTIONS BEFORE
 FRAMING INSPECTION.
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
2003-12-03 00:00:00*****CORRECTIONS*******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)THE ENGINEER'S NAME AND LICENSE
 NUMBER IS TO BE PRINTED ON THE PLAN,
 FAC61G15-23.002.
  
 2.)THE GIRDER/WALL CONNECTION (SHEET
 3) SPECIFIES HUGHES CONNECTORS; HUGHES
 IS NO LONGER IN BUSINESS.
  
 3.)THE WOOD CONSTRUCTION NOTES, ITEM
 #4, REFERS TO FBC3218.17.NOT IN THE
 FBC CODE BOOK.
  
 4.)HHGT1 AND HHGT2, CONNECTOR KST260
 SHEET RF1, NAILING CONFLICTS WITH
 CATALOG AND DESIGN UPLIFT ON THE PLAN
 EXCEEDS MAX ALLOWED BY THE CATALOG
 (USE THE GREY BAR WITHOUT STRESS
 INCREASE FOR STEEL, USP 2003 CATALOG).
  
 5.)WOOD-TO-WOOD CONNECTORS ARE
 SPECIFIED IN WOOD-TO-MASONRY
 APPLICATIONS; FOR EXAMPLE, USP HTW.
 ADDRESS.(SHEET RF1).
  
 6.)PROVIDE A FIREBLOCK DETAIL FOR
 THE DROPPED CEILINGS/SOFFITS, FBC
 705.3, 2305.1.4.
  
 7.)STATEWIDE, LOCAL OR SITE SPECIFIC
 PRODUCT APPROVALS REQUIRED FOR THE
 FOLLOWING:
 GARAGE DOOR
 GLASS BLOCK
 SHUTTERS
 TRUSS CONNECTORS
 FIXED GLASS WINDOW
  
 PROVIDE A TRUSS CONNECTOR LIST WITH
 ALL APPROVAL NUMBERS.
  
 FOR MORE INFORMATION,
 WWW.FLORIDABUILDING.ORG
  
 8.)ADDITIONAL FEES DUE (RADON),
 SEE ATTACHED BZ233271.
  
 9.)REMOVE THE TITLE BLOCK FOR
 AFFINITI FROM THE PLAN AS THEY ARE
 NOT THE DESIGNER OF RECORD.
  
 10.) SAFEGUARD (STORM SHUTTER SBCCI
 REPORT) IS NO LONGER IN BUSINESS. SUBMIT
 VALID PRODUCT APPROVALS FOR STORM
 SHUTTERS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-11-18 Cont ID  
Sent By btrobaug Date 2003-11-18 Time 07:48 Rev Time 0.50
Received By btrobaug Date 2003-11-18 Time 07:32 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-05-21 Cont ID  
Sent By csiegber Date 2004-05-21 Time 13:20 Rev Time 0.00
Received By csiegber Date 2004-05-21 Time 13:20 Sent To B
Notes
2004-05-21 00:00:00TO SH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-14 Cont ID  
Sent By csiegber Date 2004-04-14 Time 09:27 Rev Time 0.00
Received By csiegber Date 2004-04-14 Time 09:27 Sent To B
Notes
2004-04-14 00:00:00TO SH DESK/SUBMITTAL OF PROVISO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-04 Cont ID  
Sent By mmclean Date 2003-11-05 Time 15:55 Rev Time 0.00
Received By sthyng Date 2003-11-04 Time 13:51 Sent To  
Notes
2003-11-05 00:00:00TO SFD RACK/E
2003-11-04 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-12-01 Cont ID  
Sent By kstevens Date 2003-12-01 Time 09:49 Rev Time 0.50
Received By hmoser Date 2003-12-01 Time 15:16 Sent To B
Notes
2003-12-01 00:00:00PASS PROVISO
 RETURN AIR REQUIREMENTS TO COMPLY
 WITH THE FLORIDA BUILDING CODE(M) 2003
 CHANGES.CHANGES WENT INTOEFFECT JULY
 2003.
 REFER TO SECTION 307.2.3 AUXILIARY DRAIN
 PANS
 PLAN REVIEW BY HAROLD MOSER

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-12-01 Cont ID  
Sent By kstevens Date 2003-12-01 Time 09:49 Rev Time 0.50
Received By kstevens Date 2003-12-01 Time 09:49 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-11-05 Cont ID  
Sent By mmclean Date 2003-11-05 Time 15:55 Rev Time 0.00
Received By mmclean Date 2003-11-05 Time 15:55 Sent To I
Notes
***NONE***