Plan Review Details - Permit 03110081
Plan Review Stops For Permit 03110081
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-02-06 Cont ID  
Sent By rbrown Date 2004-02-06 Time 16:17 Rev Time 0.00
Received By rbrown Date 2004-02-06 Time 16:17 Sent To  
Notes
2004-02-06 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 12/9/03:
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 3) FL. ADMIN CODE RULE 9B-72.
 A SEARCH AT THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
 SHOWS NO MATCHING STATEWIDE PRODUCT
 APPROVAL FOR THE SUBMITTED YKK AP INC.
 STOREFRONT AND OUTSWING DOOR PRODUCT
 APPROVAL NOA#'S 02-0215.17 & 02-0221.07
 SPECIFY AN ALTERNATIVE THAT HAS
 STATEWIDE PRODUCT APPROVAL (OR APPLY FOR
 SITE SPECIFIC APPROVAL USING THE FORM
 AVAILABLE FROM THIS OFFICE).
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
 THE PRODUCT APPROVAL SHEETS SHALL BE
 MARKED, AS APPROPRIATE, TO IDENTIFY
 WHICH PRODUCT OPTIONS/MATERIALS/SIZES
 ARE TO BE USED.
  
 4) FBC 1606.1.7WIND LOAD.THE PLANS
 SHALL STATE THE BASIC WIND SPEED 140MPH,
 WIND IMPORTANCE FACTOR (1.0), EXPOSURE
 CATEGORY (B), INTERNAL PRESSURE COEFF.
 (0.18), AND EXTERIOR COMPONENT AND
 CLADDING DESIGN WIND PRESSURES
 APPLICABLE TO THE INSTALLATION OF DOOR
 #20 AND REPLACEMENT OF THE STOREFRONT
 WINDOW.IT IS NOTED THAT THE PLAN
 REFERS TO FBC 1606.1.7 BUT MERE CITING
 OF THE CODE IS NOT ADEQUATE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-12-09 Cont ID  
Sent By rbrown Date 2003-12-09 Time 15:09 Rev Time 0.00
Received By rbrown Date 2003-12-09 Time 15:09 Sent To  
Notes
2003-12-09 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) FBC 11-4.13.6SHEET 4, DOORS 10, 11
 AND 21.AMEND THE PLANS TO PROVIDE/
 CONFIRM A MINIMUM 18" CLEARANCE BETWEEN
 THE STRIKE EDGE OF THE DOOR AND THE
 ADJACENT 45-DEGREE WALL ON THE PULL-SIDE
 OF THE DOOR.
  
 3) SUBMIT PRODUCT APPROVALS FOR THE NEW
 EXTERIOR DOOR #20
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
  
 4) INSTALLATION OF THE NEW EXTERIOR DOOR
 #20 WILL REQUIRE ALTERATION/REPLACEMENT
 OF THE EXISTING WINDOW IN THAT LOCATION.
 AMEND THE PLANS TO STATE THE WIND DESIGN
 INFORMATION AS REQUIRED BY FBC 1606.1.7,
 INCLUDING THE POSITIVE AND NEGATIVE WIND
 DESIGN PRESSURES FOR THE NEW DOOR AND
 REPLACEMENT WINDOW. ALSO, SUBMIT DETAILS
 AND A PRODUCT APPROVAL (SEE NOTE ABOVE
 ABOUT STATEWIDE APPROVAL) FOR A MULLION
 TO WHICH THE DOOR FRAME WILL BE ATTACHED
  
 5) FBC 2405.2THE PARALEGAL OFFICE
 GLAZING IS IN A 'HAZARDOUS LOCATION' AND
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-01-15 Cont ID  
Sent By dpalmer Date 2004-01-15 Time 07:31 Rev Time 0.50
Received By dpalmer Date 2004-01-15 Time 07:24 Sent To  
Notes
2004-01-15 00:00:00**** NOTE REDLINED ***
  
 1)NOTE: PLANS STILL DO NOT INDICATE
 NEW OR EXISTING REQ'D SIGN CIRCUIT?
 600.5

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-11-04 Cont ID  
Sent By dpalmer Date 2003-11-04 Time 14:05 Rev Time 0.50
Received By dpalmer Date 2003-11-04 Time 14:05 Sent To  
Notes
2003-11-04 00:00:00*************** UNSAT *************
  
 1)NOTE: PLEASE SEE THAT PLANS ARE REQ'D
 TO BE SIGNED, DATED AND SEALED BY THE
 ENGINEER OF RECORD. PER FAC 61G15-23.002
 AND FS 471
 PLEASE SEE THAT THIS IS REQ'D FOR ALL
 TRADES WEATHER OR NOT COMMENT IS MADE.
  
 2)NOTE: PLEASE SEE THAT PANEL SCHEDULES
 ARE VERY FAINT AND NOT CLEAR. PLEASE
 DARKEN IN ORDER TO READ.
  
 3)NOTE: PLEASE SHOW ALL CONTINOUS LOADS
 AT 125% 215.3/ 230.42 ETC.
  
 PLEASE SEE COMMENTS FROM ALL OTHER
 REVIEWERS AS THEY MAY HAVE AN AFFECT
 ON ELECTRICAL PLANS.
  
 4)NOTE: PLEASE CLARIFY REQ'D SIGN
 CIRCUIT PER 600-5. UNABLE TO READ ON
 PANEL SCHEDUL.
  
 PLEASE REMOVE ALL OLD VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING.
 ONE OLD SET MAY BE SUBMITTED FOR REF
 ONLY AND MAY BE REQ'D BY OTHER REVIEWERS
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-01-15 Cont ID  
Sent By mcarsill Date 2004-01-15 Time 16:25 Rev Time 0.00
Received By mcarsill Date 2004-01-15 Time 16:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-12-08 Cont ID  
Sent By mcarsill Date 2003-12-08 Time 12:14 Rev Time 0.00
Received By mcarsill Date 2003-12-08 Time 12:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-13 Cont ID  
Sent By csiegber Date 2004-01-13 Time 14:06 Rev Time 0.00
Received By csiegber Date 2004-01-13 Time 14:06 Sent To  
Notes
2004-01-13 00:00:00TO COMM BD#8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-10 Cont ID  
Sent By pkrauss Date 2003-12-10 Time 07:11 Rev Time 0.00
Received By pkrauss Date 2003-11-04 Time 09:23 Sent To  
Notes
2003-11-04 00:00:00TO COMM BD#42

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-26 Cont ID  
Sent By pkrauss Date 2004-01-26 Time 08:04 Rev Time 0.33
Received By pkrauss Date 2004-01-26 Time 07:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-12-10 Cont ID  
Sent By pkrauss Date 2003-12-10 Time 06:50 Rev Time 0.55
Received By pkrauss Date 2003-12-09 Time 16:30 Sent To  
Notes
2003-12-10 00:00:00DENIED:
 1)
 PLEASE NOTE PER FS 471.025 & FAC 61G15-
 23.002, PLANS SHALL BE SIGNED, SEALED
 AND DATED BY THE ENGINEER.PER THE
 BOARD OF PROFFESIONAL ENGINEERS, PLANS
 ARE TO BE SIGNED AND NOT INITIALED.
 PLEASE CORRECT.
  
 2)
 PLEASE INDICATE ANY EXISTING DUCT SMOKE
 DETECTORS.SYSTEMS WITH THE DESIGN
 CAPACITY GREATER THAN 2,000 OR COMBINED
 DESIGN CAPACITY SHALL HAVE DUCT SMOKE
 DETECTORS WITH NOTIFICATION TO ALARM/
 STROBE.
  
 3)
 NOTE 6 IS NOT LISTED IN THE SPECIFIC
 NOTES, SHOULD THIS READ NOTE 5?
  
 4)
 PLEASE CLARIFY OUTSIDE AIR REQUIREMENTS
 FOR THE CONFERENCE ROOMS. PER 2001
 FBC(M) TABLE 403.3 & ASHRAE 62-89 THE
 REQUIRED CFM PER PERSON SHOULD BE A
 MINIMUM OF 20 CFM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-01-24 Cont ID  
Sent By kstevens Date 2004-01-24 Time 05:45 Rev Time 0.50
Received By kstevens Date 2004-01-24 Time 05:45 Sent To  
Notes
2004-01-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT 4 SHOWS RELOCATED DRINKING
 FOUNTAINS. A SANITARY RISER DIAGRAM AND
 A WATER RISER DIAGRAM ARE REQUIRED PER
 SECTION 104.3.1.1
 2) SUBMIT A DETAIL FOR DRINKING FOUNTAIN
 SHOWING COMPLIANCE WITH 11-4.15 AND ALL
 SUBSECTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-12-06 Cont ID  
Sent By kstevens Date 2003-12-06 Time 06:30 Rev Time 0.50
Received By kstevens Date 2003-12-06 Time 06:29 Sent To  
Notes
2003-12-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT M1 INDICATES THAT A NEW TOILET
 ROOM WILL BE ADDED, BUT THE FLOOR PLAN
 DOES NOT INDICATE THIS. PLEASE CLAIRFY.
 2) DRINKING FOUNTAIN IS NOT SHOWN ON THE
 NEW FLOOR PLAN. DRINKING FOUNTAIN IS RE-
 QUIRED PER TABLE 403.1. (ALSO SEE 410.1)
 IT SEEMS THAT THE D/F WAS REMOVED WHEN
 FLOOR PLAN WAS DEMOED. PLEASE CLAIRFY.
 IF NEW D/F SUBMIT DETIAL SHOWING COMPLI-
 ANCE WITH 11-4.15 AND ALL SUBSECTIONS &
 SECTION 11-4/1/3(10)(A) FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING.
 3) ALL CAPPED PLUMBING LINES SHALL BE
 INSPECTED PRIOR TO COVERING.
 4) SIGNATURE REQUIRED ON SEAL OF ENGIN-
 EER PER FAC 61G15-23.001(1) & FS471.025
 ALSO ENGINEERS NAME AND LICENSE NUMBER
 IS REQUIRED ON TITLE BLOCK PER FAC
 61G15-23.002(2) & FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]