Plan Review Details - Permit 03110072
Plan Review Stops For Permit 03110072
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-12-11 Cont ID  
Sent By lsmith Date 2003-12-11 Time 07:57 Rev Time 1.50
Received By lsmith Date 2003-12-11 Time 07:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-12-02 Cont ID  
Sent By csiegber Date 2003-12-10 Time 11:46 Rev Time 2.50
Received By lsmith Date 2003-12-02 Time 08:14 Sent To  
Notes
2003-12-01 00:00:00*******BUILDING PLAN REVIEW FAILED*****
  
 1.PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT.
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-11-07 Cont ID  
Sent By dpalmer Date 2003-11-07 Time 07:19 Rev Time 0.33
Received By dpalmer Date 2003-11-07 Time 07:19 Sent To M
Notes
2003-11-07 00:00:00REDLINED RECEPTS PER 210.52 UPSTAIRS
 AND DOWN.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-12-10 Cont ID  
Sent By csiegber Date 2003-12-10 Time 11:45 Rev Time 0.00
Received By csiegber Date 2003-12-10 Time 11:46 Sent To B
Notes
2003-12-10 00:00:00TO LS DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-02 Cont ID  
Sent By mmclean Date 2003-11-04 Time 17:41 Rev Time 0.00
Received By csiegber Date 2003-11-04 Time 09:13 Sent To  
Notes
2003-11-05 00:00:00TO SFD RACK/E
2003-11-04 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-11-22 Cont ID  
Sent By dpalmer Date 2003-11-07 Time 07:20 Rev Time 0.50
Received By hmoser Date 2003-11-22 Time 13:35 Sent To P
Notes
2003-11-22 00:00:00PASS PRIVISO
 1) RETURN AIR IN MASTER BED ROOM WRONG
 SIZE
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-11-24 Cont ID  
Sent By hmoser Date 2003-11-22 Time 13:36 Rev Time 0.33
Received By jleech Date 2003-11-24 Time 19:25 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-11-04 Cont ID  
Sent By mmclean Date 2003-11-04 Time 17:41 Rev Time 0.00
Received By mmclean Date 2003-11-04 Time 17:41 Sent To I
Notes
***NONE***