Plan Review Details - Permit 03110011
Plan Review Stops For Permit 03110011
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-11-19 Cont ID  
Sent By jwitmer Date 2003-11-19 Time 14:36 Rev Time 2.00
Received By jwitmer Date 2003-11-19 Time 14:33 Sent To PC
Notes
2003-11-19 00:00:00 
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 03110011
 ADDRESS: 2951 ELECTRONIC WAY
 CONT: ANDERSON-MOORE
 TELL # (561) 753-7400
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.104.2.1.2 ADMINISTRATIVE CODE.
  
 104.4.5. SPECIAL FOUNDATION PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECT
 OR ENLARGE A BUILDING HAS BEEN FILED, &
 PENDING ISSURANCE OF SUCH PERMIT, THE
 BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR
 THE FOUNDATION ONLY, UPON WRITTEN RE-
 QUEST OF THE OWNER AND CONTRACTOR. THE
 HOLDER OF SUCH A SPECIAL PERMIT IS PRO-
 CEEDING AT HIS OR HER OWN RISK AND WITH-
 OUT ASSURANCE THAT A PERMIT FOR THE
 REMAINDER OF THE WORK WILL BE GRANTED
 AND THAT CORRECTIONS WILL NOT BE RE-
 QUIRED IN ORDER TO MEET THE PROVISIONS
 OF THE TECHNICAL CODE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-11-18 Cont ID  
Sent By csiegber Date 2003-11-19 Time 11:43 Rev Time 1.22
Received By jwitmer Date 2003-11-18 Time 09:25 Sent To  
Notes
2003-11-18 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03110011
 ADD: 2951 ELECTRONIC WAY
 CONT: ANDERSON-MORE
 TEL: (561)753-7400
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2)FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 3) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 SHEETS :
 A-1 NOT SEALED
 SURVEY S-1 MISSING SIGNATURE/ DATE
 SURVEY S-2 MISSING SEAL/SIGN& DATE
  
 4) 104.4.5. SPECIAL FOUNDATION PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECT
 OR ENLARGE A BUILDING HAS BEEN FILED, &
 PENDING ISSURANCE OF SUCH PERMIT, THE
 BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR
 THE FOUNDATION ONLY, UPON WRITTEN RE-
 QUEST OF THE OWNER AND CONTRACTOR. THE
 HOLDER OF SUCH A SPECIAL PERMIT IS PRO-
 CEEDING AT HIS OR HER OWN RISK AND WITH-
 OUT ASSURANCE THAT A PERMIT FOR THE
 REMAINDER OF THE WORK WILL BE GRANTED
 AND THAT CORRECTIONS WILL NOT BE RE-
 QUIRED IN ORDER TO MEET THE PROVISIONS
 OF THE TECHNICAL CODE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-11-13 Cont ID  
Sent By csiegber Date 2003-11-17 Time 14:35 Rev Time 2.00
Received By jwitmer Date 2003-11-13 Time 14:28 Sent To  
Notes
2003-11-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03110011
 ADD: 2951 ELECTRONIC WAY
 CONT: ANDERSON-MOORE
 TEL: (561)753-7400
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 FOUNDATION PERMIT
 ACTION: DENIED
  
 1) PROVIDE 2 CURRENT COPIES OF SIGNED &
 SEALED SURVEYS WITH PROPOSED IMPROVEMENT
 TO BE COMPLETED. PROVIDE SITE DRAWING
 INDICATING THE POSITION OF THE BUILDING.
  
 2) WEST PALM BEACH ADMINISTRATIVE CODE
 105.3(4) A SPECIAL ONSITE INSPECTOR
 SHALL BE ONSITE AT ALL TIMES THAT WORK
 IS IN PROGRESS FOR STRUCTURAL COMPONENTS
 FOR BUILDINGS WITH AREA GREATER THAN
 20,000 SQ FT. THEY NEED TO REGISTER WITH
 DON NEELY OR HAROLD PISKURA, AT 805-6665
 THE OUTSIDE COORDINATOR.
  
 3)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 A) THE STRUCURAL PLANS SUBMITTED, S-1
 & S-3 DO NOT HAVE A FOOTER & FOUNDATION
 SCHEDULE.
 B) THE STRUCTURAL PLANS DO NOT INDI-
 CATE THE DEPTH THE FOOTER IS BELOW FIN-
 ISHED GRADE. ARDAMANS GEOTECHNICAL RE-
 PORT REQUIRES A MINIMUM OF 18" BELOW
 FINAL GRADE.
 C) PLANS INDICATE TOP OF FOUNDATION:
 SEE PLAN??????????NOT SHOWN ON S-1/S-3.
  
 4) 104.4.5. SPECIAL FOUNDATION PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECT
 OR ENLARGE A BUILDING HAS BEEN FILED, &
 PENDING ISSURANCE OF SUCH PERMIT, THE
 BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR
 THE FOUNDATION ONLY, UPON WRITTEN RE-
 QUEST OF THE OWNER AND CONTRACTOR. THE
 HOLDER OF SUCH A SPECIAL PERMIT IS PRO-
 CEEDING AT HIS OR HER OWN RISK AND WITH-
 OUT ASSURANCE THAT A PERMIT FOR THE
 REMAINDER OF THE WORK WILL BE GRANTED
 AND THAT CORRECTIONS WILL NOT BE RE-
 QUIRED IN ORDER TO MEET THE PROVISIONS
 OF THE TECHNICAL CODE.
 A) THE CODE ARTICLES IN REGARDS TO THE
 HANDICAPPED RAMP, IT CAN NOT BE DETERMIN
 ED THAT THE FOUNDATION PERMIT HAS COR-
 RECTED THESE ITEMS.
  
 5)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6) BEFORE A PERMIT CAN BE ISSUED, STATE
 RADON TO BE PAID AT .01 PER SQ. FT.=
 $278.38.
  
 7) SPECIAL INSPECTOR SUBMIT (3) OF ALL
 PLANS, REPORTS, SUBMITTALS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2003-12-17 Cont ID  
Sent By dpalmer Date 2003-12-17 Time 13:31 Rev Time 0.25
Received By dpalmer Date 2003-12-17 Time 13:31 Sent To  
Notes
2003-12-17 00:00:00SEPARATE PERMIT WAS PULLED FOR SLAB
 WORK.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-09 Cont ID  
Sent By dpalmer Date 2003-12-09 Time 16:12 Rev Time 0.50
Received By dpalmer Date 2003-12-09 Time 16:12 Sent To  
Notes
2003-12-09 00:00:00***********UNSAT **************
  
 1)NOTE: PLEASE SEE THAT THIS PERMIT #
 FOR FOUNDATION ONLY CONTAINED NO
 ELECTRICAL REVIEW ON ORIG SUBMITTAL.
 PLEASE SUBMIT ANY REVISED PLANS UNDER
 THE PERMIT THE ELECTRICAL REVIEW WAS
 DONE.
 PLEASE SEE THAT A COMPLETELY NEW SET OF
 PLANS WERE SUBMITTED AS A REVISION AND
 NO REVISIONS WERE INDICATED. THIS WILL
 BE REQ'D WHEN PLANS ARE SUBMITTED AS A
 REVISION UNDER MAIN PERMIT #.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2003-11-05 Cont ID  
Sent By mamini Date 2003-11-05 Time 14:34 Rev Time 0.50
Received By mamini Date 2003-11-05 Time 14:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-12-17 Cont ID  
Sent By shernand Date 2003-12-17 Time 13:05 Rev Time 0.00
Received By shernand Date 2003-12-17 Time 13:05 Sent To  
Notes
2003-12-17 00:00:00TO KEN STEVENS.SH

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-12-05 Cont ID  
Sent By csiegber Date 2003-12-05 Time 08:44 Rev Time 0.00
Received By csiegber Date 2003-12-05 Time 08:44 Sent To  
Notes
2003-12-05 00:00:00TO COMM BD#44/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-11-19 Cont ID  
Sent By csiegber Date 2003-11-19 Time 11:43 Rev Time 0.00
Received By csiegber Date 2003-11-19 Time 11:43 Sent To B
Notes
2003-11-19 00:00:00TO JW DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-11-17 Cont ID  
Sent By csiegber Date 2003-11-17 Time 14:35 Rev Time 0.00
Received By csiegber Date 2003-11-17 Time 14:35 Sent To B
Notes
2003-11-17 00:00:00TO JW DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-11-19 Cont ID  
Sent By csiegber Date 2003-11-03 Time 16:02 Rev Time 0.00
Received By jwitmer Date 2003-11-03 Time 16:03 Sent To  
Notes
2003-11-03 00:00:00TO COMM BD#60
 `

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-12-17 Cont ID  
Sent By kstevens Date 2003-12-17 Time 13:44 Rev Time 1.00
Received By kstevens Date 2003-12-17 Time 13:44 Sent To  
Notes
2003-12-17 00:00:00PLUMBING APPROVED FOR FOUNDATION ONLY
 PLUMBING PERMIT REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-12-16 Cont ID  
Sent By kstevens Date 2003-12-16 Time 18:09 Rev Time 0.50
Received By kstevens Date 2003-12-16 Time 18:09 Sent To  
Notes
2003-12-16 00:00:00DENIED
  
 FOUNDATION PLANS SHOW NO PLUMBING PLANS.
 SUBMIT PLUMBING PLANS FOR REVIEW UNDER
 THE ORIGINAL BLDG COM PERMIT APPLICATION
 NUMBER. THE PLANS SUBMITTED FOR REVISION
 HAVE NO REVISION INDICATION SHOWN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]