Plan Review Details - Permit 03101990
Plan Review Stops For Permit 03101990
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-01-05 Cont ID  
Sent By jwitmer Date 2004-01-05 Time 13:29 Rev Time 0.75
Received By jwitmer Date 2004-01-05 Time 13:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-12-01 Cont ID  
Sent By jwitmer Date 2003-12-01 Time 08:57 Rev Time 1.25
Received By jwitmer Date 2003-12-01 Time 08:57 Sent To  
Notes
2003-12-01 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03101990
 ADD: 1801 PALM BCH LAKES# 850
 CONT: EUGENE V. GIARRATANA
 TEL: (954-781-7080
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 2)705.7.1 JOINTS INSTALLED IN OR BE-
 TWEEN FIRE RESISTANT WALLS, FIRE RESIS-
 TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES
 AND FIRE RESISTANT ROOFS OR ROOF/ CEIL-
 ING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE RE-
 QUIRED FIRE RESISTANCE RATING OF THE
 WALL, FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
  
 IS THE PLUMBING VENTS TO BE INSIDE
 THE RATED PARTITIONS BETWEEN TENANT
 SPACES? IF SO IS THE WASTE PIPE TO BE
 PVC? THEN PROVIDE PRODUCT TESTING ASSEM-
 BLY FOR THE PIPE.
  
 3) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY.
  
 4)11-5.2 COUNTERS AND BARS
 WHERE FOOD OR DRINK IS SERVED @ COUNTERS
 EXCEEDING 34" IN HEIGHT FOR CONSUMPTION
 BY CUSTOMERS SEATED ON STOOLS OR STAND-
 ING AT THE COUNTER, A PORTION OF THE
 MAIN COUNTER WHICH IS 60" IN LENGTH MIN-
 IMUM SHALL BE PROVIDED IN COMPLIANCE
 WITH 11-4.32 OR SERVICE SHALL BE AVAIL-
 ABLE AT ACCESSIBLE TABLES WITHIN THE
 SAME AREA.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-01-05 Cont ID  
Sent By dpalmer Date 2004-01-05 Time 06:11 Rev Time 0.25
Received By dpalmer Date 2004-01-05 Time 06:11 Sent To  
Notes
2004-01-05 00:00:00NOTED ON PLANS 700.12E.
 NO CHANGE REQ'D.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-11-04 Cont ID  
Sent By dpalmer Date 2003-11-04 Time 07:50 Rev Time 0.50
Received By dpalmer Date 2003-11-04 Time 07:50 Sent To  
Notes
2003-11-04 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR ALL
 NEW SERVICE EQUIPMENT BEING INSTALLED.
 MAIN DISC/ PANEL AND BRKRS ARE ALL TO
 BE RATED FOR THE AVAILABLE FAULT CURRENT
 PER 110.9 NEC.
  
 2)NOTE: PLEASE SHOW LOADING FOR TRACK
 PER 220.12B
  
 3)NOTE: PLEASE SEE THAT VOLTAGE SHOW ON
 PANEL AND RISER IS SHOWN AT 120/208V
 AND ELECTRICAL SPECS SHOW VOLTAGE AT
 120/220? PLEASE CORRELATE.
  
 4)NOTE: PLEASE VERFIY CIRCUITING FOR
 EM/EXT LTS PER 700.12E.
 SHOW ALL CIRCUITING.
  
 5)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215.3/230.42 ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-01-02 Cont ID  
Sent By mcarsill Date 2004-01-02 Time 07:27 Rev Time 0.00
Received By mcarsill Date 2004-01-02 Time 07:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-11-13 Cont ID  
Sent By mcarsill Date 2003-11-13 Time 07:13 Rev Time 0.00
Received By mcarsill Date 2003-11-13 Time 07:13 Sent To  
Notes
2003-11-13 00:00:001) NEW COOLER AND FREEZER ARE TO BE
 FIRE SPRINKLER PROTECTED. THE
 MECHANICAL PLAN SEEMS TO SUGGEST FIRE
 SPRINKLER HEADS IN COOLER BUT NOT
 THE FREEZER.
  
 2) PLEASE PROVIDE PRODUCT APPROVALS
 FOR BREAD OVEN.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-05-24 Cont ID  
Sent By alange Date 2004-05-24 Time 14:42 Rev Time 0.00
Received By alange Date 2004-05-24 Time 14:42 Sent To M
Notes
2004-05-24 00:00:00TO HM DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-12-30 Cont ID  
Sent By csiegber Date 2003-12-30 Time 08:34 Rev Time 0.00
Received By csiegber Date 2003-12-30 Time 08:34 Sent To  
Notes
2003-12-30 00:00:00TO COMM BD#49

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-05 Cont ID  
Sent By kstevens Date 2003-12-05 Time 18:42 Rev Time 0.00
Received By kstevens Date 2003-11-03 Time 10:15 Sent To  
Notes
2003-11-03 00:00:00TO COMM BD#3

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-08-11 Cont ID  
Sent By pkrauss Date 2004-08-11 Time 14:46 Rev Time 0.30
Received By pkrauss Date 2004-08-11 Time 14:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-11-22 Cont ID  
Sent By alange Date 2004-05-24 Time 14:42 Rev Time 1.00
Received By hmoser Date 2003-11-22 Time 08:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-01-14 Cont ID  
Sent By kstevens Date 2004-01-14 Time 17:52 Rev Time 0.75
Received By kstevens Date 2004-01-14 Time 17:52 Sent To  
Notes
2004-01-14 00:00:00PASSED/PROVISO - MANUF. SHEETS REQUIRED
 AT PLUMBING FINAL FOR FILTER. SHALL BE
 "NSF" APPROVED. - VALVE REQUIRED AT W/H
 FOR THERMAL EXPANSION CONTROL

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-12-05 Cont ID  
Sent By kstevens Date 2003-12-05 Time 18:30 Rev Time 0.75
Received By kstevens Date 2003-12-05 Time 18:16 Sent To  
Notes
2003-12-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) ROUTE PLANS TO DEPT. OF BUSINESS
 REGULATION HOTEL AND RESTAURANT DIVISION
 (954) 958-5520 FOR REVIEW PRIOR TO RE-
 SUBMITTING TO CITY WPB. WORK SHEET SHALL
 BE ATTACHED TO PLANS. SECTION 1011.4.7
 2) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE, FOR SIZING OF GREASE INTER-
 CEPTOR. (561) 837-4074 WASTE ORD #2938-
 96
 3) SHT A-3 OF 4 WATER FILTER TO SODA
 SHALL BE "NSF" APPROVED. SUBMIT MANUF.
 SPECIFICATION SHEETS. SECTION 303.4
 4) SHT A-3 OF 4 RPZ BACKFLOW REQUIRED ON
 WATER SERVICE TO SPACE. MAXIMUM 4' ABOVE
 THE FLOOR FOR CERTIFICATION AND SERVIC-
 ING. SECTION 608.13.2
 5) THERMAL EXPANSION CONTROL REQUIRED
 FOR WATER HEATER. SECTION 607.3.2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]