Plan Review Details - Permit 03101790
Plan Review Stops For Permit 03101790
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-02-27 Cont ID  
Sent By jwitmer Date 2004-02-27 Time 09:13 Rev Time 1.20
Received By jwitmer Date 2004-02-27 Time 09:13 Sent To  
Notes
2004-02-27 00:00:00BUILDING PROVISO:
 ARCHITECT WILL PROVIDE METHOD OF ATTACH-
 MENT TO THEEXISTING CEILING AND SPACING
 FOR THE NEW SOFFIT BEFORE FRAMING
 INSPECTION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-11-26 Cont ID  
Sent By jwitmer Date 2003-11-26 Time 16:55 Rev Time 0.55
Received By jwitmer Date 2003-11-26 Time 16:49 Sent To  
Notes
2003-11-26 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 03101790
 ADD: 319 CLEMATIS STREET
 CONT: CABOT
 TEL: (561)601-8848
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A102 DETAIL# 3 INDICATES THE USE
 OF SOFFITS, THE ATTACHMENT TO THE STRUC-
 TURE ABOVE NOT GIVEN NOR THE CENTER/
 CENTER FOR STEEL STUDS.
  
 3) NOTE : TYPE II BUILDING ALL BACKING
 TO BE FIRE RETARDENT TREATED,609.2.1
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-03-05 Cont ID  
Sent By dpalmer Date 2004-03-05 Time 12:11 Rev Time 0.50
Received By dpalmer Date 2004-03-05 Time 12:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-02-06 Cont ID  
Sent By dpalmer Date 2004-02-06 Time 13:42 Rev Time 0.50
Received By dpalmer Date 2004-02-06 Time 13:42 Sent To  
Notes
2004-02-06 00:00:00UNSAT *****************************
  
 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 AS THEY WILL HAVE A DIRECT AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2003-11-06 Cont ID  
Sent By dpalmer Date 2003-11-06 Time 14:34 Rev Time 0.25
Received By dpalmer Date 2003-11-06 Time 14:34 Sent To  
Notes
2003-11-06 00:00:00NO NEW ELECTRICAL WORK SHOWN.
 PLANS SHOW LAYOUT OF EXSITNG ONLY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-03-05 Cont ID  
Sent By dpalmer Date 2004-03-05 Time 12:10 Rev Time 0.50
Received By dpalmer Date 2004-03-05 Time 12:09 Sent To  
Notes
2004-03-05 00:00:00OK PER MIKE CARSILLO

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-01-29 Cont ID  
Sent By mcarsill Date 2004-01-29 Time 15:06 Rev Time 0.00
Received By mcarsill Date 2004-01-29 Time 15:06 Sent To  
Notes
2004-01-29 00:00:001) COULD NOT LOCATE ANY FIRE ALARM
 EQUIPMENT ON PAGE EO1. NOTE # 12
 DEALS WITH EMERGENCY LIGHTING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-11-13 Cont ID  
Sent By mcarsill Date 2003-11-13 Time 07:10 Rev Time 0.00
Received By mcarsill Date 2003-11-13 Time 07:10 Sent To  
Notes
2003-11-13 00:00:001) REFLECTED CEILING PLAN ON PAGE
 A1-02 DISPLAYS AN EXIT SIGN NEAR DOOR
 IN WORK AREA 403. THE FLOOR PLAN
 ON A1-01 DOES NOT DISPLAY THE SAME
 INFORMATION.
  
 2) PLANS DO NOT INDICATE ANY EXISTING
 OR NEW FIRE ALARM STROBES.
  
 3) NEW SOFFIT SHALL NOT INTERFERE WITH
 THE OPERATION OF ANY FIRE
 SPRINKLER HEADS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-29 Cont ID  
Sent By csiegber Date 2004-01-29 Time 11:06 Rev Time 0.00
Received By csiegber Date 2004-01-29 Time 11:06 Sent To  
Notes
2004-01-29 00:00:00TO COMM BD#9

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-10-29 Cont ID  
Sent By csiegber Date 2003-10-29 Time 16:44 Rev Time 0.00
Received By csiegber Date 2003-10-29 Time 16:44 Sent To  
Notes
2003-10-29 00:00:00TO COMM BD#16

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-02-19 Cont ID  
Sent By pkrauss Date 2004-02-19 Time 06:37 Rev Time 0.40
Received By pkrauss Date 2004-02-19 Time 06:37 Sent To  
Notes
2004-02-19 00:00:00PROVISO:
 1.PROVIDE MANUFACTURER INSTALLATION
 INSTRUCTIONS FOR THE FIRE DAMPER ON THE
 JOBSITE AT THE TIME OF INSPECTION.
  
 2.NO COMBUSTIBLES ALLOWED ABOVE THE
 CEILING IN THE RETURN AIR PLENUM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-11-24 Cont ID  
Sent By pkrauss Date 2003-11-24 Time 16:16 Rev Time 0.40
Received By pkrauss Date 2003-11-24 Time 16:16 Sent To  
Notes
2003-11-24 00:00:00DENIED:
 1.PLANS VAGUE AS TO THE SCOPE OF HVAC
 WORK.
  
 2.PLEASE PROVIDE REVISED OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) 403.3.
  
 3.PLEASE INDICATE EXISTING SYSTEM.
 RTU, AHU, VAV'S?
  
 4.INDICATE IF RETURN IS A DUCTED OR
 PLENUM.NO COMBUSTIBLES ABOVE THE
 CEILING IN THE RETURN AIR PLENUM PER
 2001 FBC(M) 602.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-11-26 Cont ID  
Sent By jwitmer Date 2003-11-26 Time 16:49 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***