| 2003-11-21 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-LOAD SCHEDULE: ADD THE ATTIC LIVE LOAD |
| | AS REQUIRED BY TABLE 1604.1 FBC 2001. |
| | **NOTE: ADD 30PSF LIVE LOAD FOR ATTIC |
| | WITH STORAGE AND 10PSF W/O STORAGE. |
| | 2-PROVIDE COMPLETE INFORMATION FOR STORM |
| | SHUTTERS: A)NEED FLORIDA PRODUCT |
| | APPROVAL OR SITE SPECIFIC ENGINEERING. |
| | B)PROVIDE KEY PLAN AND COMPLETE INSTA- |
| | LLATION SCHEDULE. |
| | C)CLEARLY MARK ON DRAWINGS SPECIFIC |
| | MOUNTING CONDITIONS & ANCHOR TYPE AND |
| | SPACING TO BE USED. |
| | |
| | 3-PROVIDE COMPLETE SOIL TEST REPORT WITH |
| | SOIL BEARING INFORMATION AND SOIL PRE- |
| | PARATION RECOMMENDATIONS. SECTION |
| | 1804.2.2 CITY AMENDMENTS TO FBC 2001. |
| | 4-PROVIDE FLORIDA PRODUCT APPROVAL OR |
| | SITE SPECIFIC ENGINEERING FOR ROOF |
| | TILE, ALL TYPES OF DOORS AND WINDOWS, |
| | WINDOW MULLIONS AS SHOWN ON PLANS AS |
| | REQ'D BY FBC AS OF OCTOBER 1ST 2003. |
| | **SEE WWW FLORIDABUILDING.ORG. |
| | |
| | **NOTES: |
| | * NEED ENTRY DOOR W/SIDELITE AS SHOWN ON |
| | PLANS. |
| | * MAKE SURE INFORMATION PROVIDED IS NOT |
| | EXPIRED. |
| | * ONLY SUBMIT INFORMATION FOR ITEMS THAT |
| | APPLY TO THIS HOUSE TO REDUCE PAPER |
| | WORK AND UNNECESSARY REVIEWS. |
| | |
| | 5-SPECIFY FASTENING REQUIREMENTS FOR |
| | ROOF TILE. SEE SECTION 104.2.1.1 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 6-OWES $22.08 FOR UPDATED VALUATION. SEE |
| | ATTACHED RECEIPT. |
| | 7-SHEET A-2: RAKE BEAM DETAIL 3/A2 DOES |
| | NOT MATCH SPECIFICATIONS SHOWN ON |
| | TIE-BEAM SCHEDULE. REVISE/CLARIFY AS |
| | REQ'D. SEC. 104.2.1.2 CITY AMENDMENTS. |
| | 8-SPECIFY SAFETY GLASS WHERE REQUIRED. |
| | SEE PLANS FOR COMMENTS AND SECTION |
| | 2405.2 FBC 2001. |
| | 9-PROVIDE SPECIFICATIONS FOR ANCHORING |
| | GABLE END TRUSS. DETAIL 7/A6 SEND YOU |
| | TO THE CONNECTOR SCHEDULE, BUT THERE |
| | ARE NOT SPECS ON THE SCHEDULE FOR |
| | GABLE END TRUSSES. NEITHER ON THE ROOF |
| | FRAMING PLAN. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |