Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-01-26 Cont ID  
Sent By jgomez Date 2004-01-26 Time 18:36 Rev Time 2.50
Received By jgomez Date 2004-01-26 Time 18:36 Sent To PC
Notes
2004-01-26 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-SHEET S-3: A)DIAPHRAGM SCHEDULE AND
 ROOF SHEATHING AND NAILING NOTE DON'T
 MATCH. REVISE/CLARIFY AS REQUIRED.
 B)CONNECTOR TC-5 @ MASONRY APPLICATION:
 SEE USP TECHNICAL BULLETIN AND REVISE
 SIZE OF SCREW TO ACHIEVE REQUIRED MIN.
 EMBEDMENT. ALSO, CLARIFY IF THIS
 CONNECTOR WAS REVISED/UPDATED BY USP
 TO COMPLY WITH SEC. 1609.4.3 FBC 2001
 WHICH DOESN'T ALLOW THE STEEL STRESS
 TO BE INCREASED.
 C)CLARIFY WHY UPLIFT SHOWN ON TRUSS
 ANCHOR SCHEUDLE IS HIGHER THAN THE
 ONE PUBLISHED BY USP. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 3-PROVIDE FLORIDA PRODUCT APPROVAL FOR:
 A)ROOF TILE.
 B)8'X7' GARAGE DOOR THAT MEET THE DESIGN
 PRESSURES CALCULATED BY ARCHITECT.
 C)STRUCTURAL CONNECTORS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-12-24 Cont ID  
Sent By csiegber Date 2004-01-20 Time 16:36 Rev Time 1.50
Received By jgomez Date 2003-12-24 Time 11:40 Sent To PC
Notes
2003-12-24 00:00:00BUILDING REVIEW CHECKLIST:
 1-LOAD SCHEDULE: ADD THE 30PSF/10PSF
 ATTIC LIVE LOAD AS REQUIRED BY TABLE
 1604.1 FBC 2001.
 2-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS INCLUDING FLORIDA PRODUCT
 APPROVAL.
 3-REVISE ROOF SHEATHING AND NAILING NOTE
 AND DIAPHRAGM SCHEDULE ON SHEET S-3.
 SEE TABLE 2306.1 CITY AMENDMENTS TO
 FBC 20001 FOR REQUIRED NAILING SIZE &
 SPACING AT 25' MEAN ROOF HEIGHT.
 4-SHEET A-5: REVISE HANDRAIL HEIGHT TO
 COMPLY WITH SEC. 1007.5.1 FBC 2001.
 5-PROVIDE COMPLETE SOIL TEST REPORT WITH
 SOIL BEARING PREPARATION AND BEARING
 CAPACITY. SECTION 1804.2.2 OF CITY
 AMENDMENTS TO FBC 2001.
 6-PROVIDE FLORIDA PRODUCT APPROVALS OR
 SITE SPECIFIC ENGINEERING FOR ROOF
 TILE, ALL TYPES OF WINDOWS AND DOORS
 (SEE PLANS), WINDOW MULLIONS, TRUSS
 ANCHORS. VISIT WWW.FLORIDABUILDING.ORG
 FOR ALL THE INFORMATION REQUIRED TO BE
 SUBMITTED.
 7-SHEET S-3: REVISE CONNECTOR TC-5. THIS
 IS A WOOD TO WOOD CONNECTOR, WHILE,
 APPLICATION IS WOOD TRUSS TO MASONRY.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 8-ARCHITECT TO PROVIDE ALL INFORMATION
 ON TITLE BLOCK AS REQUIRED BY SECTION
 61G1-16.004 OF THE FLORIDA ADMINISTRA-
 TIVE CODE.
 9-ARCHITECT TO UPDATE SPECIFICATIONS ON
 SHEET C-1. SEE COMMENTS.
 10-SHEET A-1: CLARIFY NOTE #24. WHAT'S
 THE HEIGHT OF THE HANDRAIL?.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-11-19 Cont ID  
Sent By jgomez Date 2003-11-19 Time 13:22 Rev Time 2.00
Received By jgomez Date 2003-11-19 Time 13:22 Sent To M
Notes
2003-11-19 00:00:00BUILDING REVIEW CHECKLIST:
 1-LOAD SCHEDULE: ADD THE ATTIC LIVE LOAD
 AS REQUIRED BY TABLE 1604.1 FBC 2001.
 **NOTE: ADD 30PSF LIVE LOAD FOR ATTIC
 WITH STORAGE AND 10PSF W/O STORAGE.
 2-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS: A)NEED FLORIDA PRODUCT
 APPROVAL FOR LOCAL PRODUCT APPROVAL.
 B)PROVIDE KEY PLAN AND COMPLETE INSTALLA
 TION SCHEDULE.
 C)CLEARLY MARK ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE &
 SPACING.
 3-REVISE ROOF SHEATHING AND NAILING
 NOTE AND DIAPHRAGM SCHEUDLE ON SHEET
 S-3. SEE TABLE 2306.1 CITY AMENDMENTS
 TO FBC 2001 FOR REQUIRED NAILING AT
 MEAN ROOF HEIGHT OF 25' OR MORE.
 4-SHEET A-5: REVISE HANDRAIL HEIGHT TO
 COMPLY WITH SEC. 1007.5.1 FBC 2001.
 5-PROVIDE COMPLETE SOIL TEST REPORT WITH
 SOIL BEARING INFORMATION AND SOIL
 PREPARATION. SECTION 1804.2.2 CITY
 AMENDMENTS TO FBC 2001.
 6-PROVIDE FLORIDA PRODUCT APPROVAL OR
 LOCAL PRODUCT APPROVAL FOR ROOF TILE,
 ALL TYPES OF DOORS AND WINDOWS, WINDOW
 DOOR MULIIONS AS REQUIRED BY
 FBC AS OF OCTOBER 1ST 2003. SEE COPY
 OF FREQUENTLY ASKED QUESTION REGARDING
 THIS NEW PROCESS. ALSO, VISIT WWW.
 FLORIDABUILDING.ORG FOR MORE INFO.
  
 **NOTES:
 * NEED PRODUCT APPROVAL FOR DOUBLE ENTRY
 DOORS AS SHOWN ON PLANS.
 * MAKE SURE ALL PROVIDED INFORMATION IS
 NOT EXPIRED.
 * ONLY SUBMIT INFORMATION FOR ITEMS THAT
 APPLY TO THIS HOUSE TO REDUCE PAPER-
 WORK AND UNNECESSARY REVIEWS. -
  
 7-OWES $21.91 FOR UPDATED VALUATION.
 SEE ATTACHED RECEIPT.
 8-SHEET S-3: ROOF FRAMING PLAN SPECIFIES
 CONNECTOR TC-5 AND TC-6. BUT, THEY ARE
 WOOD TO WOOD CONNECTORS. NEED MASONRY
 CONNECTORS. REVISE AS REQUIRED.
 9-REVISE ENERGY CALCULATIONS: A)THIS IS
 NOT LAKES OF LAGUNA.
 B)THERE IS NOT ADJACENT WOOD WALL. SEE
 PLANS AND REVISE AS REQUIRED.
 C)PROVIDE TWO COPIES WITH ORIGINAL SEAL,
 SIGNATURE AND DATE AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-05-05 Cont ID  
Sent By jleahy Date 2004-05-05 Time 10:39 Rev Time 0.15
Received By jleahy Date 2004-05-05 Time 10:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-12-16 Cont ID  
Sent By csiegber Date 2004-05-03 Time 13:45 Rev Time 0.50
Received By btrobaug Date 2003-12-16 Time 13:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-12-10 Cont ID  
Sent By btrobaug Date 2003-12-10 Time 08:46 Rev Time 0.50
Received By btrobaug Date 2003-12-10 Time 08:31 Sent To M
Notes
2003-12-10 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 NOTE: PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATED AND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025.
  
 NOTE THAT ONE
 SET OF PLANS HAS NO SIGNATURE OR
 DATE.PLEASE RESUBMIT FOR REVIEW UPON
 COMPLIANCE WITH THIS STATUTE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-11-05 Cont ID  
Sent By csiegber Date 2003-12-09 Time 10:13 Rev Time 0.50
Received By btrobaug Date 2003-11-05 Time 13:37 Sent To M
Notes
2003-11-05 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 TOTHE PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATED AND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025.
 SEE SHEET E-2.
  
 2} PLEASE SEE NOTES ON PLANS REGARDING
 HOW THE SMOKE DETECTORS ARE FED.SHEET
 E-1 SHOWS THEM BEING FED FROM A KITCHEN
 OR BATHROOM LIGHT CIRCUIT.NOTE #14 ON
 E-2 SAYS THE SAME THING.PLEASE NOTE
 THAT NFPA-70 (NEC) 2002 EDITION
 REQUIRES THESE AND ALL "OUTLETS" (SEE
 DEFINITION IN NEC),BE PROTECTED BY ARC
 FAULT CIRCUIT INTERUPTERS. SEE210.12(B).
 PLEASE CHANGE THIS WORDING ON ALL
 FUTURE PLANS,ALL MODELS.THANKS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-05-03 Cont ID  
Sent By csiegber Date 2004-05-03 Time 13:49 Rev Time 0.00
Received By csiegber Date 2004-05-03 Time 13:49 Sent To M
Notes
2004-05-03 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-05-03 Cont ID  
Sent By csiegber Date 2004-05-03 Time 13:45 Rev Time 0.00
Received By csiegber Date 2004-05-03 Time 13:45 Sent To E
Notes
2004-05-03 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-04-13 Cont ID  
Sent By csiegber Date 2004-04-13 Time 11:34 Rev Time 0.00
Received By csiegber Date 2004-04-13 Time 11:34 Sent To M
Notes
2004-04-13 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-01-20 Cont ID  
Sent By csiegber Date 2004-01-20 Time 16:36 Rev Time 0.00
Received By csiegber Date 2004-01-20 Time 16:36 Sent To B
Notes
2004-01-20 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-12-09 Cont ID  
Sent By csiegber Date 2003-12-09 Time 10:13 Rev Time 0.00
Received By csiegber Date 2003-12-09 Time 10:13 Sent To E
Notes
2003-12-09 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-11-22 Cont ID  
Sent By mmclean Date 2003-10-29 Time 12:46 Rev Time 0.00
Received By csiegber Date 2003-10-28 Time 09:31 Sent To  
Notes
2003-10-29 00:00:00TO Z
 10/29/03TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-05-07 Cont ID  
Sent By pkrauss Date 2004-05-07 Time 15:32 Rev Time 0.30
Received By pkrauss Date 2004-05-07 Time 15:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-04-26 Cont ID  
Sent By csiegber Date 2004-05-03 Time 13:49 Rev Time 0.35
Received By pkrauss Date 2004-04-26 Time 07:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-12-16 Cont ID  
Sent By csiegber Date 2004-04-13 Time 11:34 Rev Time 0.33
Received By pkrauss Date 2003-12-16 Time 16:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-11-22 Cont ID  
Sent By btrobaug Date 2003-12-10 Time 09:47 Rev Time 0.50
Received By hmoser Date 2003-11-22 Time 12:14 Sent To  
Notes
2003-11-22 00:00:00PLAN DENIED
 1) ENERGY CALCULATIONS DO NOT MATCH PLAN
 2) REFER 2003 CODE CHANGES ON BALANCED
 RETURN AIR.WENT INTO EFFECT JULY 1 2003
 3) REFER TO SECTION 307.2.3 AUXILIARY
 DRAIN PAN.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-11-08 Cont ID  
Sent By jleech Date 2003-11-08 Time 09:23 Rev Time 0.25
Received By jleech Date 2003-11-08 Time 09:23 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-10-29 Cont ID  
Sent By mmclean Date 2003-10-29 Time 12:46 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved