Plan Review Details - Permit 03101646
Plan Review Stops For Permit 03101646
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-11-19 Cont ID  
Sent By lmartine Date 2003-11-19 Time 14:12 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-12-02 Cont ID  
Sent By dpalmer Date 2003-12-02 Time 04:24 Rev Time 0.50
Received By dpalmer Date 2003-12-02 Time 04:24 Sent To  
Notes
2003-12-02 00:00:00******** NOTES ********
  
 PLANS REDLINED.
 PLEASE SEE 700.12E FOR CIRCUITING OF
 EM/ EXT LTS.
  
 PLEASE SHOW ALL CONTINUOUS LOADS AT 125%
 PER 215.3,230.42 ETC.
  
 PLEASE SEE THESE NOTES WERE FROM FIRST
 REVIEW. PLEASE SUBMIT PLANS WITH CORRECT
 -IONS BEFORE ROUGH ELECTRICAL INSPECTION
 IS CALLED IN.
 PLEASE SEE NOTES FROM FIRE REVIEW.
  
 PLEASE SEE NOTES ON FIRST REVIEW MENTION
 -S TO REMOVE ALL OLD/VOIDED SHEETS AND
 MAKE TWO COMPLETE STES FOR REVIEW AND
 STAMPING. PLEASE SEE THIS WAS NOT DONE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-28 Cont ID  
Sent By dpalmer Date 2003-10-28 Time 14:25 Rev Time 0.33
Received By dpalmer Date 2003-10-28 Time 14:25 Sent To  
Notes
2003-10-28 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED
 PANEL SCHEDULE.
 BE SURE TO CIRCUIT EM/EXT LTS PER 700.12
 -E
  
 2)NOTE: PLEASE SHOW LOAD CALCULATION
 PER 220.3,220.10,220.11,220.13 ETC AND
 ALL CONTINUOUS LOADS PER 230.42,215.3
 LOAD CALC SHOWN IS FOR RESIDENTIAL.
  
 3)NOTE: PLANS REFERENCE 1999 NEC. WE
 ARE NOW UNDER THE 2002 NEC AS OF 7/1/03
  
 4)NOTE: PLEASE CLARIFY LOADS SHOWN FOR
 A/C AHU'S ??? NOT CLEAR WHICH ONE AND
 NOTE MENTIONS 1@ 10KW???
  
 5)NOTE: PLEASE CLARIFY NEW OR EXISTING
 SIGN CIRCUIT PER 600.5
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 THAT MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-12-12 Cont ID  
Sent By mcarsill Date 2003-12-12 Time 07:43 Rev Time 0.00
Received By mcarsill Date 2003-12-12 Time 07:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-11-13 Cont ID  
Sent By mcarsill Date 2003-11-13 Time 07:15 Rev Time 0.00
Received By mcarsill Date 2003-11-13 Time 07:15 Sent To  
Notes
2003-11-13 00:00:001) IT APPEARS THAT ANOTHER EXIT SIGN
 IS NEEDED NEAR RECEPTION AREA SO AS
 TO DIRECT PERSONS TO EXIT DOOR THAT
 IS NOT VISIBLE FROM HALLWAY.
  
 2) THE LIFE SAFETY SUMMARY ON PAGE
 4.1 INDICATES NO FIRE SPRINKLER SYSTEM
 HOWEVER PAGES 2.1 AND 3.1 DIFFER FROM
 PAGE 4.1.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-11-26 Cont ID  
Sent By csiegber Date 2003-11-26 Time 14:08 Rev Time 0.00
Received By csiegber Date 2003-11-26 Time 14:08 Sent To  
Notes
2003-11-26 00:00:00TO COMM BD#30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-11-19 Cont ID  
Sent By lmartine Date 2003-11-19 Time 17:05 Rev Time 0.00
Received By lmartine Date 2003-10-28 Time 11:09 Sent To  
Notes
2003-10-28 00:00:00TO COMM BD#19