Plan Review Details - Permit 03101646
| Plan Review Stops For Permit 03101646 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2003-11-19 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2003-11-19 |
Time |
14:12 |
Rev Time |
1.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2003-12-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-12-02 |
Time |
04:24 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-12-02 |
Time |
04:24 |
Sent To |
|
|
| Notes |
| 2003-12-02 00:00:00 | ******** NOTES ******** | | | | | | PLANS REDLINED. | | | PLEASE SEE 700.12E FOR CIRCUITING OF | | | EM/ EXT LTS. | | | | | | PLEASE SHOW ALL CONTINUOUS LOADS AT 125% | | | PER 215.3,230.42 ETC. | | | | | | PLEASE SEE THESE NOTES WERE FROM FIRST | | | REVIEW. PLEASE SUBMIT PLANS WITH CORRECT | | | -IONS BEFORE ROUGH ELECTRICAL INSPECTION | | | IS CALLED IN. | | | PLEASE SEE NOTES FROM FIRE REVIEW. | | | | | | PLEASE SEE NOTES ON FIRST REVIEW MENTION | | | -S TO REMOVE ALL OLD/VOIDED SHEETS AND | | | MAKE TWO COMPLETE STES FOR REVIEW AND | | | STAMPING. PLEASE SEE THIS WAS NOT DONE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-10-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-10-28 |
Time |
14:25 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-10-28 |
Time |
14:25 |
Sent To |
|
|
| Notes |
| 2003-10-28 00:00:00 | ************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH SUBMITTED | | | PANEL SCHEDULE. | | | BE SURE TO CIRCUIT EM/EXT LTS PER 700.12 | | | -E | | | | | | 2)NOTE: PLEASE SHOW LOAD CALCULATION | | | PER 220.3,220.10,220.11,220.13 ETC AND | | | ALL CONTINUOUS LOADS PER 230.42,215.3 | | | LOAD CALC SHOWN IS FOR RESIDENTIAL. | | | | | | 3)NOTE: PLANS REFERENCE 1999 NEC. WE | | | ARE NOW UNDER THE 2002 NEC AS OF 7/1/03 | | | | | | 4)NOTE: PLEASE CLARIFY LOADS SHOWN FOR | | | A/C AHU'S ??? NOT CLEAR WHICH ONE AND | | | NOTE MENTIONS 1@ 10KW??? | | | | | | 5)NOTE: PLEASE CLARIFY NEW OR EXISTING | | | SIGN CIRCUIT PER 600.5 | | | | | | PLEASE SEE COMMENTS FROM OTHER REVIEWERS | | | THAT MAY HAVE AN AFFECT ON ELECTRICAL | | | PLANS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | INSERT NEW SHEETS INTO TWO COMPLETE SETS | | | FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2003-12-12 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-12-12 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-12-12 |
Time |
07:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2003-11-13 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-11-13 |
Time |
07:15 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-11-13 |
Time |
07:15 |
Sent To |
|
|
| Notes |
| 2003-11-13 00:00:00 | 1) IT APPEARS THAT ANOTHER EXIT SIGN | | | IS NEEDED NEAR RECEPTION AREA SO AS | | | TO DIRECT PERSONS TO EXIT DOOR THAT | | | IS NOT VISIBLE FROM HALLWAY. | | | | | | 2) THE LIFE SAFETY SUMMARY ON PAGE | | | 4.1 INDICATES NO FIRE SPRINKLER SYSTEM | | | HOWEVER PAGES 2.1 AND 3.1 DIFFER FROM | | | PAGE 4.1. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-11-26 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-11-26 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-11-26 |
Time |
14:08 |
Sent To |
|
|
| Notes |
| 2003-11-26 00:00:00 | TO COMM BD#30 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-11-19 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2003-11-19 |
Time |
17:05 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2003-10-28 |
Time |
11:09 |
Sent To |
|
|
| Notes |
| 2003-10-28 00:00:00 | TO COMM BD#19 |
|
|
|