Plan Review Details - Permit 03101552
Plan Review Stops For Permit 03101552
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-04-01 Cont ID  
Sent By rbrown Date 2004-03-30 Time 15:19 Rev Time 0.00
Received By rbrown Date 2004-04-01 Time 11:46 Sent To  
Notes
2004-03-30 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 --PROVISO--
 SHEET 3, TRUSS ANCHORAGE SCHEDULE.
 IN ACCORDANCE WITH THE 2004 SIMPSON
 CATALOGUE, THE FASTENERS USED WITH THE
 SPECIFIED SIMPSON ANCHORS SHALL BE:
 META12 - (7)10DX1-1/2 NAILS OR BETTER
 HHETA20 - (11)10DX1-1/2 NAILS OR BETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-01-14 Cont ID  
Sent By csiegber Date 2004-03-26 Time 11:08 Rev Time 0.00
Received By rbrown Date 2004-01-14 Time 14:10 Sent To  
Notes
2004-01-14 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 12/3/03:
  
 6) SHEET 3, TRUSS ANCHORAGE SCHEDULE.
 TRUSS ANCHORAGE NOTE #3 STATES THAT
 TRUSS ANCHORAGE SPECIFICATION WILL BE
 PROVIDED WITH THE TRUSS SHOP DRAWINGS.
 THAT PROPOSAL IS NOTED, BUT A PERMIT
 CANNOT BE ISSUED UNTIL THE PLANS SPECIFY
 VALID ANCHORS (MANUFACTURER AND REF.)
 AND SHOW THOSE ANCHORS TO HAVE UPLIFT
 CAPACITY IN EXCESS OF THE CALCULATED
 UPLIFT.
  
 7) FL. ADMIN CODE RULE 9B-72.
 A SEARCH AT THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
 SHOWS NO MATCHING STATEWIDE PRODUCT
 APPROVAL FOR EITHER OF THE TWO PROPOSED
 OUTSWING COMMERCIAL STEEL DOORS (IMPACT)
 BY FIREDOOR CORPORATION OF FLORIDA.
 - FOR EXAMPLE, REFER TO THE STATEWIDE
 PRODUCT APPROVAL LISTING PRINTED AND
 ADDED TO THE ASPHALT SHINGLE SUBMITTAL -
 SPECIFY ALTERNATIVE DOORS THAT HAVE
 STATEWIDE OR LOCAL PRODUCT APPROVAL.
 ALSO, NOTE THAT DRAWING SHEETS 1 THRO' 5
 OF 5 ARE MISSING FROM BOTH OF THE
 SUBMITTED MIAMI-DADE NOA'S.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-12-03 Cont ID  
Sent By rbrown Date 2003-12-03 Time 16:55 Rev Time 0.00
Received By rbrown Date 2003-12-03 Time 16:55 Sent To  
Notes
2003-12-03 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 3) 61G15-23.002(2)FL. ADMIN. CODE.
 THE PLANS ARE MISSING EITHER THE ADDRESS
 OF THE ENGINEER OR, IF APPLICABLE, THE
 THE DETAILS OF THE ENGINEERING BUSINESS.
 PLANS SIGNED & SEALED BY A PROFESSIONAL
 ENGINEER SHALL INCLUDE EITHER THE NAME,
 ADDRESS AND LICENSE NUMBER OF THE
 ENGINEER OR, THE NAME AND LICENSE NUMBER
 OF THE ENGINEER AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH
 WHICH THE ENGINEER IS PRACTICING.
  
 4) FBC 1606.1.7WIND LOAD.THE PLANS
 SHALL STATE THE BASIC WIND SPEED, WIND
 IMPORTANCE FACTOR, WIND EXPOSURE
 CATEGORY, INTERNAL PRESSURE COEFFICIENT,
 AND EXTERIOR COMPONENT AND CLADDING
 DESIGN WIND PRESSURES.
  
 5) FBC 1606.1DESIGN AS PARTIALLY
 ENCLOSED.THE PROVISION OF HURRICANE
 SHUTTERS IS NOTED (SHEET 3, ELEVATIONS).
 WHAT IS THE 'FREE AREA' OF THE LOUVERS
 L1 AND L2?IT APPEARS THAT THE PRESENCE
 OF THE LOUVERS, WHEN SHUTTERS ARE NOT
 REQUIRED TO BE IN PLACE, CAUSES THE
 BUILDING TO FALL WITHIN THE DEFINITION
 OF A 'PARTIALLY ENCLOSED BUILDING' (SEE
 FBC 1606.1.5, DEFINITIONS).ANNOTATE
 THE PLANS TO CONFIRM THAT THE BUILDING
 IS DESIGNED AS PARTIALLY ENCLOSED.
  
 6) SHEET 3, TRUSS ANCHORAGE SCHEDULE
 GIVES HUGHES ANCHOR REFERENCES.THAT
 COMPANY NO LONGER SUPPLIES ANCHORS.
 AMEND THE PLANS TO SPECIFY VALID ANCHOR
 REFERENCES FROM A CURRENT SUPPLIER.
  
 7) SUBMIT PRODUCT APPROVALS FOR THE
 EXTERIOR DOORS AND THE ROOF COVERING.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
  
 8) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-01-02 Cont ID  
Sent By dpalmer Date 2004-01-02 Time 08:11 Rev Time 0.33
Received By dpalmer Date 2004-01-02 Time 08:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-31 Cont ID  
Sent By dpalmer Date 2003-10-31 Time 16:31 Rev Time 0.50
Received By dpalmer Date 2003-10-31 Time 16:31 Sent To  
Notes
2003-10-31 00:00:00********** UNSAT ****************
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002,
 PLEASE ALL INFORMATION ON TITLE BLOCK
 AS SET FORTH IN FAC.
  
 PLANS ARE ONLY IN FOR PLAN REVIEW.
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 THAT MAY OR MAY NOT HAVE AN AFFECT ON
 ELECTRICAL PLAN.
 TITLE BLOCK INFORMATION REQ'D FOR ALL
 SHEETS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2003-12-23 Cont ID  
Sent By mamini Date 2003-12-23 Time 16:04 Rev Time 1.00
Received By mamini Date 2003-12-23 Time 16:04 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2003-10-31 Cont ID  
Sent By mamini Date 2003-10-31 Time 15:47 Rev Time 1.00
Received By mamini Date 2003-10-31 Time 15:47 Sent To  
Notes
2003-10-31 00:00:00FAILED :
 1. PLEASE NOTE THAT A SEPARATE PERMIT
 APPLICATION AND FEES FOR "UNDERGROUND
 UTILITIES AND SITE WORK" PERMIT IS
 REQUIRED.PLEASE SUBMIT TWO SETS OF
 CIVIL PLANS ONLY, SIGNED AND SEALED.
 2. CONNECTION TO CITY WATER AND SEWER IN
 COUNTY R.O.W REQUIRE A SEPARATE PERMIT
 FROM THE COUNTY.
 3. CONNECTION TO COUNTY'S 30" R.C.P
 FOR STORM WATER DISCHARGE ALSO REQUIRES
 PERMIT AND APPROVAL FROM THE COUNTY.
 4. PLEASE PROVIDE STORM WATER
 CALCULATION FOR OUR REVIEW AND APPROVAL.
 5. CONNECTIONS TO THE CITY SERVICES AND
 LOCATIONS FOR METER AND BACKFLOW
 PREVENTERS MUST BE APPROVED BY THE
 PUBLIC UTILITIES AND ENGINEERING,PLEASE
 SUBMIT TWO SETS OF CIVIL PLANS ONLY,ATT:
 MANNY GONZALEZ, 659-8040.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-11-13 Cont ID  
Sent By mcarsill Date 2003-11-13 Time 07:05 Rev Time 0.00
Received By mcarsill Date 2003-11-13 Time 07:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-03-26 Cont ID  
Sent By csiegber Date 2004-03-26 Time 11:08 Rev Time 0.00
Received By csiegber Date 2004-03-26 Time 11:08 Sent To B
Notes
2004-03-26 00:00:00TO RB DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-12-19 Cont ID  
Sent By csiegber Date 2003-12-19 Time 16:41 Rev Time 0.00
Received By csiegber Date 2003-12-19 Time 16:41 Sent To  
Notes
2003-12-19 00:00:00TO COMM BD#11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-04 Cont ID  
Sent By mmclean Date 2003-12-04 Time 14:55 Rev Time 0.00
Received By rbrown Date 2003-10-24 Time 16:18 Sent To  
Notes
2003-10-29 00:00:0010/24/03TO Z
 10/29/03TO COMM BD#50

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-11-24 Cont ID  
Sent By pkrauss Date 2003-11-24 Time 16:39 Rev Time 0.38
Received By pkrauss Date 2003-11-24 Time 16:34 Sent To  
Notes
2003-11-24 00:00:00NO MECHANICAL VENTILATION - UNMANNED
 RELAY VAULT.LOUVERS INDICATED FOR
 NATURAL VENTILATION.EXHAUST FAN
 PROVIDED FOR THE RESTROOM.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-01-12 Cont ID  
Sent By kstevens Date 2004-01-12 Time 12:59 Rev Time 0.75
Received By kstevens Date 2004-01-12 Time 12:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-11-05 Cont ID  
Sent By kstevens Date 2003-11-05 Time 17:56 Rev Time 1.00
Received By kstevens Date 2003-11-05 Time 17:56 Sent To  
Notes
2003-11-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
  
 1) SHT 1 OF 3 REST ROOM ELEVATION VIEW
 "A". A WATER CLOSET SHALL NOT BE SET
 CLOSER THAN 30" CENTER TO CENTER BETWEEN
 TOILETS OR ADJACENT FIXTURES. 405.3.1
 2) SHT 1 OF 3 HOSE BIBB DETAIL. AIR
 CHAMBERS NOT APPROVED. DELETE FROM
 DETAIL. 604.9
 3) SHT 2 OF 3 WATER ISOMETRIC. AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 ISOMETRIC. 604.9
 4) SHT 1 OF 1 IRRIGATION PLAN. A TITLE
 BLOCK MUST APPEAR ON ALL ARCHITECTURAL
 DRAWINGS. 61G1-16.004. (SEE ATTACHED
 SHEET FOR REFERENCE).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2003-10-29 Cont ID  
Sent By csiegber Date 2003-10-24 Time 16:18 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
2003-10-29 00:00:0010/29/03 OK PER ANGELLA VANN MM