Plan Review Details - Permit 03101545
Plan Review Stops For Permit 03101545
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-11-06 Cont ID  
Sent By csiegber Date 2003-11-06 Time 11:34 Rev Time 0.00
Received By csiegber Date 2003-11-06 Time 11:34 Sent To M
Notes
2003-11-06 00:00:00TO PK BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-10-24 Cont ID  
Sent By csiegber Date 2003-10-24 Time 16:01 Rev Time 0.00
Received By csiegber Date 2003-10-24 Time 16:01 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-11-07 Cont ID  
Sent By pkrauss Date 2003-11-07 Time 07:02 Rev Time 0.25
Received By pkrauss Date 2003-11-07 Time 06:58 Sent To  
Notes
2003-11-07 00:00:00PROVISO:
 AUXILIARY DRAIN PAN REQUIRED AS PER
 2001 FBC(M) 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-10-29 Cont ID  
Sent By csiegber Date 2003-11-06 Time 11:34 Rev Time 0.33
Received By pkrauss Date 2003-10-29 Time 07:22 Sent To  
Notes
2003-10-29 00:00:00DENIED:
 PLEASE CLARIFY THE FOLLOWING INFORMATION
  
 1.LOCATION OF THE AHU OR UNITS.
  
 2.RETURN AIR REQUIRED FROM ROOMS THAT
 CAN BE SEPARATED BY DOORS.SEE ATTACHED
 FOR THE SIZING OF RETURN AIR AS PER
 REVISION TO THE 2001 FBC(M) 601.4
 EFFECTIVE JUNE 30, 2003.
  
 3.AUXILIARY DRAIN PAN REQUIRED AS PER
 2001 FBC(M) 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.