Plan Review Details - Permit 03101544
Plan Review Stops For Permit 03101544
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-11-06 Cont ID  
Sent By csiegber Date 2003-11-06 Time 11:34 Rev Time 0.00
Received By csiegber Date 2003-11-06 Time 11:34 Sent To M
Notes
2003-11-06 00:00:00TO PK BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-10-24 Cont ID  
Sent By csiegber Date 2003-10-24 Time 16:02 Rev Time 0.00
Received By csiegber Date 2003-10-24 Time 16:02 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-11-07 Cont ID  
Sent By pkrauss Date 2003-11-07 Time 07:41 Rev Time 0.25
Received By pkrauss Date 2003-11-07 Time 07:37 Sent To  
Notes
2003-11-07 00:00:00PROVISO:
 AUXILIARY DRAIN PAN REQUIRED PER 2001
 FBC(M) 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-10-29 Cont ID  
Sent By csiegber Date 2003-11-06 Time 11:34 Rev Time 0.25
Received By pkrauss Date 2003-10-29 Time 07:12 Sent To  
Notes
2003-10-29 00:00:00DENIED:
 1.PLAN DOES NOT INDICATE MAIN OR BRANC
 H DUCT SIZES.
  
 2.RETURN AIR REQUIRED FROM BEDROOM
 AREAS.PLEASE SIZE RETURN AS PER
 REVISION TO THE 2001 FBC(M) 601.4,
 EFFECTIVE JUNE 30,2003:
  
 RETURN AIR JUMPER SHALL BE SIZED 1 1/2
 TIMES THE CROSS SECTIONAL AREA OF THE
 SUPPLY DUCT FOR THE ROOM ITS SERVING
 WITH THE DOOR HAVING AN UNRESTRICTED 1"
 UNDERCUT. (ALL SUPPLY AIR TO THE ROOM
 SHALL BE CALCULATED)
  
 AIR TRANSFER GRILLES SHALL BE SIZED 50
 SQ INCHES PER 100 CFM SUPPLY AIR.
  
 3.EMERGENCY DRAIN PAN REQUIRED AS PER
 2001 FBC(M) 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.