Plan Review Details - Permit 03101510
Plan Review Stops For Permit 03101510
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-09-21 Cont ID  
Sent By lsmith Date 2004-09-21 Time 14:38 Rev Time 1.00
Received By lsmith Date 2004-09-21 Time 14:38 Sent To  
Notes
2004-09-21 00:00:00PROVISO:
 NEW WINDOWS & DOOR MUST HAVE STORM PANEL
 PROTECTION BY SEPARATE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-04-19 Cont ID  
Sent By lsmith Date 2004-04-19 Time 10:28 Rev Time 0.75
Received By lsmith Date 2004-04-19 Time 10:28 Sent To  
Notes
2004-04-19 00:00:001.PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2. THE PLANS SUBMITTED ARE COPIES.
 NEED ORIGINAL PLANS WITH SIGN & SEAL OF
 ENGINEER & DEPT. OF HEALTH STAMP.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-02-24 Cont ID  
Sent By kstevens Date 2004-04-17 Time 12:49 Rev Time 0.50
Received By lsmith Date 2004-02-24 Time 16:04 Sent To  
Notes
2004-02-24 00:00:00SEE NOTES FROM FIRST REVIEW:
  
 PRODUCT APPROVALS FOR WINDOWS & DOORS
 HAVE NOT BEEN SUBMITTED.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-11-12 Cont ID  
Sent By lsmith Date 2003-11-12 Time 14:06 Rev Time 0.75
Received By lsmith Date 2003-11-12 Time 14:06 Sent To  
Notes
2003-11-12 00:00:00******BUIDING FAILED**********
  
 1. SUBMIT PRODUCT APPROVALS FOR 2
 WINDOWS & DOOR.
 2. PROVIDE STORM PANEL DETAILS & PRODUCT
 APPROVALS FOR STORM PANELS REQUIRED PER
 FBC 2001.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2004-09-20 Cont ID  
Sent By dpalmer Date 2004-09-20 Time 10:58 Rev Time 0.25
Received By dpalmer Date 2004-09-20 Time 10:58 Sent To  
Notes
2004-09-20 00:00:00NO ELECTRICAL SUBMITTED, NO ELECTRICAL
 CONT SIGNED ON.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2003-10-28 Cont ID  
Sent By dpalmer Date 2003-10-28 Time 12:58 Rev Time 0.25
Received By dpalmer Date 2003-10-28 Time 12:58 Sent To  
Notes
2003-10-28 00:00:00NO ELECTRICAL PLANS SUBMITTED FOR
 REVIEW.
 SUBMIT DRAWING WITH ELECTRICAL PERMIT
 APPLICATION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-11-13 Cont ID  
Sent By mcarsill Date 2003-11-13 Time 07:08 Rev Time 0.00
Received By mcarsill Date 2003-11-13 Time 07:08 Sent To  
Notes
2003-11-13 00:00:001) ENSURE EXIT SIGNS AND EMERGENCY
 LIGHTS ARE WORKING IN EXISTING
 CLUBHOUSE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-08-25 Cont ID  
Sent By csiegber Date 2004-08-25 Time 16:03 Rev Time 0.00
Received By csiegber Date 2004-08-25 Time 16:03 Sent To  
Notes
2004-08-25 00:00:00TO COMM BD#47

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-06-18 Cont ID  
Sent By csiegber Date 2004-06-18 Time 15:57 Rev Time 0.00
Received By csiegber Date 2004-06-18 Time 15:57 Sent To  
Notes
2004-06-18 00:00:00TO COMM BD#10

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-14 Cont ID  
Sent By csiegber Date 2004-04-14 Time 10:00 Rev Time 0.00
Received By csiegber Date 2004-04-14 Time 10:00 Sent To P
Notes
2004-04-14 00:00:00TO KS BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-04 Cont ID  
Sent By csiegber Date 2004-02-04 Time 10:51 Rev Time 0.00
Received By csiegber Date 2004-02-04 Time 10:51 Sent To P
Notes
2004-02-04 00:00:00TO COMM BD#47

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-11-13 Cont ID  
Sent By rbrown Date 2004-02-05 Time 18:21 Rev Time 0.00
Received By rbrown Date 2003-10-24 Time 12:17 Sent To  
Notes
2003-10-24 00:00:00TO COMM BD#47

Review Stop P PLUMBING
Rev No 5 Status P Date 2004-10-07 Cont ID  
Sent By kstevens Date 2004-10-07 Time 13:48 Rev Time 1.00
Received By kstevens Date 2004-10-07 Time 13:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2004-07-03 Cont ID  
Sent By kstevens Date 2004-07-03 Time 14:40 Rev Time 0.33
Received By kstevens Date 2004-07-03 Time 14:40 Sent To  
Notes
2004-07-03 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1) WHITE OUT CHANGES ARE NOT ACCEPTABLE
 PER SECTION 104.2.1.3. SHEET SHALL BE
 REDRAWN WITH ALL CORRECTIONS. ANY QUEST-
 IONS PLEASE CALL KEN STEVENS (561) 805-
 6721.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-04-17 Cont ID  
Sent By kstevens Date 2004-04-17 Time 12:49 Rev Time 1.00
Received By kstevens Date 2004-04-17 Time 12:49 Sent To B
Notes
2004-04-17 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) PLANS ARE COPIES AND AS SUCH ARE NOT
 SEALED AND ORIGINAL SIGNATURE IS NOT ON
 PLANS. SUBMIT PLANS THAT ARE SIGNED,
 SEALED AND DATED AS REQUIRED IN FAC
 61G15-23.002(1)
 2) SUBMIT ORIGINAL PERMIT APPLICATION
 WITH PLANS WHEN RESUBMITTING FOR REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-02-06 Cont ID  
Sent By csiegber Date 2004-04-14 Time 10:00 Rev Time 0.50
Received By kstevens Date 2004-02-06 Time 07:45 Sent To  
Notes
2004-02-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) BOTH COPIES SHALL BE STAMPED BY THE
 PALM BEACH COUNTY HEALTH UNIT, AND NOTES
 FROM PBC HEALTH UNIT TO BE ON BOTH SETS
 OF PLANS. 101.4.7.
 2) AIR RELIEF VALVES NOT APPROVED FOR
 VENTING. AIR ADMITTENCE VALVES MAY BE
 USED PER SECTION 917.
 3) INDIRECT WASTE REQUIRED FOR 3 COMP.
 SINK FOR WASHING DRINK GLASSES. SECTION
 802.
 4) WATER RISER DIAGRAM NOT ON ONE SET OF
 PLANS. 104.3.1.1
 5) CORRECTIONS OR CHANGES TO PLANS BY
 HAND NOT ACCEPTABLE. NEW SHEETS REQUIRED
 6) SEE ATTACHED SHEET CONCERNING FLORIDA
 STATUTE 533.80(2)(B) AS SOME COMMENTS
 ARE FROM PREVIOUS REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-11-05 Cont ID  
Sent By csiegber Date 2004-02-04 Time 10:51 Rev Time 0.50
Received By kstevens Date 2003-11-05 Time 13:16 Sent To  
Notes
2003-11-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) PLANS SHALL BE ROUTED TO THE PALM
 BEACH COUNTY HEALTH UNIT, DIVISION OF
 ENVIRONMENTAL HEALTH. 901 EVERNIA ST.
 W.P.B. (561) 355-3018 PRIOR TO BEING
 RESUBMITTED FOR PLAN REVIEW. 101.4.7
 2) SANITARY RISER AND FLOOR PLAN DO NOT
 MEET CODE REQUIREMENTS. THE HAND WASH
 SINK AND THE THREE COMPARTMENT SINKS ARE
 NOT VENTED PROPERLY. 1002.3(5)
 3) ANY PORTION OF THE DRAINAGE SYSTEM
 INSTALLED UNDERGROUND SHALL NOT BE LESS
 THAN 2" IN DIAMETER. 710.3. (SEE HAND
 WASH SINK).
 4) INDIRECT WASTE REQUIRED FOR 3 COMP.
 SINK FOR WASHING DRINK GLASSES. SECTION
 802
 5) WATER RISER DIAGRAM REQUIRED. SECTION
 104.3.1.1 PLUMBING (3) & (10)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]