Plan Review Details - Permit 03101476
Plan Review Stops For Permit 03101476
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-02-27 Cont ID  
Sent By shill Date 2004-02-27 Time 12:34 Rev Time 1.00
Received By shill Date 2004-02-27 Time 12:33 Sent To  
Notes
2004-02-27 00:00:00REVISION FOR FOUNDATION REPLACEMENT,
 HELIX PILES, 2/25/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-02-04 Cont ID  
Sent By csiegber Date 2004-02-09 Time 09:42 Rev Time 1.00
Received By shill Date 2004-02-04 Time 16:22 Sent To  
Notes
2004-02-04 00:00:00****CORRECTIONS****
  
 REVISION FOR FOOTER REPAIR
  
 1.)ALL CHANGES TO THE ORIGINAL PLAN
 SHOULD BE CLEARLY INDICATED WITH
 CLOUDS.A STOOP, FRENCH DOORS, AND
 WINDOWS WERE ADDED.
  
 2.)SUBMIT PRODUCT APPROVALS FOR THE
 FRENCH DOORS, WINDOWS, MULLIONS, IMPACT
 PROTECTION.
  
 3.)THE PLANS ARE TO BE APPROVED BY
 HISTORIC BEFORE RESUBMITTAL.
  
 4.)ZONING APPROVAL REQUIRED FOR THE
 STOOP.PROVIDE A SITE PLAN FOR ZONING
 REVIEW.
  
 5.)THE FIRM LICENSE NUMBER IS TO BE
 ON THE TITLE BLOCK, FAC61G1-16.004.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-12-17 Cont ID  
Sent By csiegber Date 2004-01-28 Time 11:58 Rev Time 0.25
Received By shill Date 2003-12-17 Time 11:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-12-16 Cont ID  
Sent By shill Date 2003-12-16 Time 14:37 Rev Time 1.00
Received By shill Date 2003-12-16 Time 14:37 Sent To  
Notes
2003-12-16 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)HAVE NEW SHEETS STAMPED BY
 HISTORIC PRESERVATION DEPARTMENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-11-13 Cont ID  
Sent By pkrauss Date 2003-11-13 Time 12:45 Rev Time 1.50
Received By sthyng Date 2003-11-13 Time 13:01 Sent To  
Notes
2003-11-13 00:00:00*****CORRECTIONS******
  
 SAMANTHA THYNG (HILL)
 BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)PROVIDE A DETAIL FOR THE NEW
 BARRELL CEILING OVER THE STAIRS.FBC
 1007.7, A MINIMUM OF 6'8" HEADROOM IS
 REQUIRED.
  
 2.)PROVIDE A DETAIL FOR THE NEW
 RAILING TO COMPLY WITH FBC1007.5,1608.2.
  
 3.)PROVIDE A WALL SECTION FOR THE
 EXTERIOR WALL REPAIR, FBC104.3.1.1,
 WALL SECTION FROM FOUNDATION THROUGH
 ROOF (IF APPLICABLE), INCLUDING
 ASSEMBLY AND MATERIALS.
  
 4.)OBTAIN HISTORIC PRESERVATION
 DIVISION APPROVAL BEFORE RESUBMITTAL
 (NEW SHEETS WITH CHANGES).

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-05-25 Cont ID  
Sent By btrobaug Date 2004-05-25 Time 11:25 Rev Time 0.50
Received By btrobaug Date 2004-05-25 Time 11:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-12-05 Cont ID  
Sent By csiegber Date 2004-05-21 Time 11:01 Rev Time 0.50
Received By btrobaug Date 2003-12-05 Time 12:06 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-11-05 Cont ID  
Sent By csiegber Date 2003-12-04 Time 14:18 Rev Time 0.50
Received By btrobaug Date 2003-11-05 Time 06:38 Sent To P
Notes
2003-11-05 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} THE #4 GROUNDING ELECTRODE CONDUCTOR
 ON THE RISER IS INCORRECT FOR THE
 SERVICE. SEE 250.66(#2).
  
 3} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 4} PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECT--ED PER 210.8.A.6.
  
 5} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 6} PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210.52.SEE
 REVIEWED SET.
  
 7} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210.52E
  
 8} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210.52C 1,2,3,4,AND 5.
  
 9} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STAIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-05-21 Cont ID  
Sent By csiegber Date 2004-05-21 Time 11:01 Rev Time 0.00
Received By csiegber Date 2004-05-21 Time 11:01 Sent To E
Notes
2004-05-21 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-09 Cont ID  
Sent By csiegber Date 2004-02-09 Time 09:42 Rev Time 0.00
Received By csiegber Date 2004-02-09 Time 09:42 Sent To B
Notes
2004-02-09 00:00:00TO SH DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-01-28 Cont ID  
Sent By csiegber Date 2004-01-28 Time 11:58 Rev Time 0.00
Received By csiegber Date 2004-01-28 Time 11:58 Sent To B
Notes
2004-01-28 00:00:00TO SH DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-12-04 Cont ID  
Sent By csiegber Date 2003-12-04 Time 14:18 Rev Time 0.00
Received By csiegber Date 2003-12-04 Time 14:18 Sent To E
Notes
2003-12-04 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-10-24 Cont ID  
Sent By csiegber Date 2003-10-24 Time 10:16 Rev Time 0.00
Received By csiegber Date 2003-10-24 Time 10:16 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2003-12-16 Cont ID  
Sent By shill Date 2003-12-16 Time 14:36 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
2003-12-16 00:00:00NO MECH PER PK (SEE RESUB SHEET)

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-11-13 Cont ID  
Sent By btrobaug Date 2003-12-05 Time 15:08 Rev Time 0.10
Received By pkrauss Date 2003-11-07 Time 06:32 Sent To B
Notes
2003-11-07 00:00:00DENIED:
 INSUFFICIENT INFORMATION SUBMITTED FOR
 REVIEW.
  
 PLEASE PROVIDE MECHANICAL INFORMATION,
 ENERGY CALCULATIONS, OR FORM 600C WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-11-05 Cont ID  
Sent By btrobaug Date 2003-11-05 Time 12:23 Rev Time 0.25
Received By kstevens Date 2003-11-05 Time 17:02 Sent To M
Notes
2003-11-05 00:00:00NO PLUMBING PLANS SUBMITTED OR NEEDED.
 FIXTURE REPLACEMENT ONLY SHOWN.