Plan Review Details - Permit 03101412
Plan Review Stops For Permit 03101412
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2003-12-15 Cont ID  
Sent By mamini Date 2003-12-15 Time 08:54 Rev Time 0.00
Received By mamini Date 2003-12-15 Time 08:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2003-11-07 Cont ID  
Sent By dpalmer Date 2003-11-07 Time 11:26 Rev Time 0.25
Received By dpalmer Date 2003-11-07 Time 11:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-11-06 Cont ID  
Sent By dpalmer Date 2003-11-06 Time 06:50 Rev Time 0.33
Received By dpalmer Date 2003-11-06 Time 06:43 Sent To  
Notes
2003-11-06 00:00:00************ UNSAT ****************
  
 1)NOTE: PLEASE SEE THAT NO ELECTRICAL
 PLANS WERE SUBMITTED FOR REVIEW.
 PLEASE SUBMIT.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2005-06-10 Cont ID  
Sent By mamini Date 2005-06-10 Time 16:08 Rev Time 1.00
Received By mamini Date 2005-06-10 Time 16:08 Sent To  
Notes
2005-06-10 00:00:00PASSED:
  
 1. REVIEWED FOR REVISIONS.
  
 1F ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2004-03-17 Cont ID  
Sent By dlauderm Date 2004-03-17 Time 12:53 Rev Time 1.00
Received By dlauderm Date   Time   Sent To  
Notes
2004-03-17 00:00:00PASSED

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2003-12-16 Cont ID  
Sent By csiegber Date 2004-03-05 Time 09:51 Rev Time 1.00
Received By mamini Date 2003-12-16 Time 15:10 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2003-11-18 Cont ID  
Sent By mamini Date 2003-11-18 Time 08:54 Rev Time 1.00
Received By mamini Date 2003-11-18 Time 08:54 Sent To  
Notes
2003-11-18 00:00:00FAILED:
 1. SHEET PD 1 OF 4, PLEASE SHOW ALL THE
 DRAINAGE PIPE, STRUCTURES BEING REMOVED,
 RELOCATED OR TO BE ABANDONED. REFER TO
 POST DEVELOPMENT DRANAGE BASIN EXHIBIT 2
 ( DB 2) IN DRANAGE REPORT.
 2. SHEET PD 4, LAKE 1 CONTROL STRUCTURE
 DETAILS SHOWS WIER INV. ELEVATION AT
 14.35', CALCULATION SHOWS IT AT 10.91'
 PLEASE VERIFY.
 2. PLEASE SHOW DOMESTIC WATER LINE TO
 THE PROPOSED CLUBHOUSE AND POOL, A
 SEPARATE BACKFLOW PREVENTER FOR THE
 POOL IS REQUIRED.
 3. PROPOSED WORK IN CONGRESS AVE. AND
 EXECUTIVE CENTER DR. REQUIRES PERMIT AND
 APPROVAL FROM COUNTY AND CITY
 RESPECTIVELY.
 4. A COPY OF SFWMD PERMIT IS AT THE TIME
 OF ACTUAL PERMITING MUST BE SUBMITTED.
 5. DRIVEWAY APPROACHES MUST BE
 CONSTRUCTED WITH 6" CONCRETE FROM EDGES
 OF PAVEMENT TO PROPERTY LINE.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-12-16 Cont ID  
Sent By nmccray Date 2003-12-16 Time 15:39 Rev Time 0.00
Received By nmccray Date 2003-12-16 Time 15:39 Sent To  
Notes
2003-12-16 00:00:00************PROVISO*********************
 WET FIRE HYDRANTS ARE REQUIRED PRIOR TO,
 DURING AND AFTER CONSTRUCTION.
  
 SUITABLE ROADS ARE TO BE PROVIDED FOR
 FIRE AND PARAMEDICAL ACCESS DURING
 CONSTRUCTION.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-11-06 Cont ID  
Sent By mcarsill Date 2003-11-06 Time 14:29 Rev Time 0.00
Received By mcarsill Date 2003-11-06 Time 14:29 Sent To  
Notes
2003-11-06 00:00:001) WET FIRE HYDRANTS ARE REQUIRED
 PRIOR TO, DURING AND AFTER CONSTRUCTION.
  
 2) SUITABLE ROADS ARE TO BE PROVIDED
 FOR FIRE AND PARAMEDICAL ACCESS
 DURING CONSTRUCTION.
  
 3) SEPARATE PLANS AND PERMITS
 REQUIRED FOR ENTRY GATES. WHAT
 PROVISIONS WILL BE MADE FOR FIRE
 AND PARAMEDICAL ACCESS. WHAT HAPPENS
 WHEN LOSS OF POWER OCCURS. WILL THE
 GATEHOUSE BE STAFFED FULL TIME OR
 PART TIME.
  
 4) TAMPER SWITCHES, CHAINS AND LOCKS
 ARE REQUIRED ON FIRE LINE BACKFLOW
 DEVICE.
  
 5) FIRE HYDRANTS SHALL HAVE A MINIMUM
 CLEARANCE OF 7'-6" TO THE FRONT AND
 SIDES OF THEM. A MINIMUM OF 4'
 CLEARANCE IS REQUIRED TO THE REAR OF
 THEM.
  
 6) IT APPEARS THAT ADDITIONAL FIRE
 HYDRANTS MAY BE NEEDED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By drunnels Date 2005-06-02 Time 09:29 Sent To ENG
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-03-05 Cont ID  
Sent By csiegber Date 2004-03-05 Time 09:51 Rev Time 0.00
Received By csiegber Date 2004-03-05 Time 09:51 Sent To ENG
Notes
2004-03-05 00:00:00TO MA DESK/3RD REQUEST

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-12-12 Cont ID  
Sent By mmclean Date 2003-12-15 Time 09:06 Rev Time 0.00
Received By csiegber Date 2003-12-12 Time 11:38 Sent To  
Notes
2003-12-12 00:00:00TO COMM BD#54

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-12-11 Cont ID  
Sent By csiegber Date 2003-12-11 Time 14:55 Rev Time 0.00
Received By csiegber Date 2003-12-11 Time 14:55 Sent To Z
Notes
2003-12-11 00:00:00TO MM/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-10-22 Cont ID  
Sent By mmclean Date 2003-10-30 Time 16:36 Rev Time 0.00
Received By csiegber Date 2003-10-22 Time 16:19 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-12-15 Cont ID  
Sent By mamini Date 2003-12-15 Time 08:55 Rev Time 0.00
Received By mamini Date 2003-12-15 Time 08:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-12-15 Cont ID  
Sent By mamini Date 2003-12-15 Time 08:55 Rev Time 0.00
Received By mamini Date 2003-12-15 Time 08:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2003-12-15 Cont ID  
Sent By csiegber Date 2003-12-11 Time 14:55 Rev Time 0.00
Received By mmclean Date 2003-12-15 Time 09:06 Sent To I
Notes
2003-12-12 00:00:002ND REQUEST - PER ERIC SCHNEIDER SENIOR
 PLANNER 1. NO LANDSCAPE PLANS WERE
 INCLUDED, NEED TO PROVIDE ON FOR PERMIT
 2. SITE PLAN SHEET 1 OR 5 IS NOT THE ONE
 THE CITY COMMISSION APPROVED.NEED TO
 SUBMIT THE 9/26/03 REVISED ONE ITEMS
 AFFECTED ARE: PARKING DATA IS MISSING.
 3. ENTRY SIGN LOCATION SHOWN ON SHEETS
 1,3 & 5 DO NOT MEET SETBACKS.RESIDENTIAL
 DEVELOPMENT ENTRY SIGNS ARE REQUIRED TO
 HAVE A 20' SETBACK FROM THE ROW.
2003-10-30 00:00:0010/29/03 PER ERIC SCHNEIDER 659-8031
 * NO LANDSCAPE PLANS WERE INCLUDED NEE
 TO PROVIDE ONE FOR PERMIT
 * SITE PLAN SHEET 1 OF 5 IS NOT THE ONE
 THE CITY COMMISSION APPROVED.NEED TO
 SUBMIT THE 9/26/03 REVISED ONE ITEMS
 AFFECTED ARE PARKING DATA IS
 INCORRECT & THE BIKE RACK DETAIL IS
 MISSING
 * ENTRY SIGN LOCATION SHOWN ON SHEETS 1
 3 & 5 OF 5 DO NOT MEET SETBACKS.
 RESIDENTIAL DEVELOPMENT ENTRY SIGNS
 ARE REQUIRED TO HAVE A 20' SETBACK FROM
 THE ROW.