|
 |
 |
 |
 |
 |
Plan Review Details - Permit 03101353
| Plan Review Stops For Permit 03101353 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2003-12-05 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2003-12-05 |
Time |
08:06 |
Rev Time |
1.00 |
| Received By |
lsmith |
Date |
2003-12-05 |
Time |
08:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-10-29 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-12-04 |
Time |
15:24 |
Rev Time |
1.50 |
| Received By |
lsmith |
Date |
2003-10-29 |
Time |
14:46 |
Sent To |
|
|
| Notes |
| 2003-10-29 00:00:00 | *****BUILDING REVIEW FAILED********* | | | | | | 1. ACCORDING TO SS61GL 16.004 ALL SIGNED | | | & SEALED PLANS MUST HAVE A RAISED SEAL | | | CLEARLY ON ORIGINAL PLANS WITH ORIGINAL | | | SIGNATURES.SEVERAL OF THE SHEETS WITH | | | THIS PERMIT ARE PHOTOCOPIES FROM ANOTHER | | | HOUSE.REPLACE SHEETS THAT ARE COPIES | | | WITH NEW ORIGINALS & HAVE ARCHITECT TO | | | USE A SEAL THAT IS CLEARLY VISABLE WHEN | | | SQUEEZED. | | | 2. PLANS MUST BE TAKEN TO PALM BEACH | | | COUNTY AND IMPACT FEES PAID.A COPY OF | | | THE RECEIPT MUST BE SUBMITTED WITH THE | | | STAMPED PLANSBEFORE A PERMIT CAN BE | | | ISSUED. | | | 3. SUBMIT AN EXTRA OCPY OF THE 1ST PAGE | | | OF THE FLORIDA ENERGY EFFECIENCY CODE | | | WITH PERMIT PACKAGE.IT IS SENT TO THE | | | STATE OF FLORIDA. | | | 4. BUILDING VALUATION IS BASED ON SQUARE | | | FOOTAGE AS FOLLOWS: | | | U/A @ 74.88 OTHER @ 41.60. | | | TOTAL VALUATION OF THIS HOUSE IS 161141. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2003-10-27 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-10-27 |
Time |
06:58 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-10-27 |
Time |
07:41 |
Sent To |
M |
|
| Notes |
| 2003-10-28 00:00:00 | REDLINED REQUIREMENTS FOR 2002 NEC | | | ALSO REDLINED ADDRESS ON E-SHEETS ONLY. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-12-01 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-01 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-12-01 |
Time |
16:13 |
Sent To |
M |
|
| Notes |
| 2003-12-01 00:00:00 | TO PK BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-10-29 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2003-10-22 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-10-21 |
Time |
15:32 |
Sent To |
|
|
| Notes |
| 2003-10-22 00:00:00 | TO Z | | | TO SFD RACK/E |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2003-12-04 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-12-04 |
Time |
15:24 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2003-12-04 |
Time |
15:24 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2003-10-28 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-01 |
Time |
16:13 |
Rev Time |
0.33 |
| Received By |
pkrauss |
Date |
2003-10-28 |
Time |
06:58 |
Sent To |
E |
|
| Notes |
| 2003-10-28 00:00:00 | DENIED: | | | RETURN AIR NOT SIZED CORRECTLY, SEE | | | ATTACHED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2003-10-28 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2003-10-28 |
Time |
19:49 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2003-10-28 |
Time |
19:48 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2003-10-22 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2003-10-22 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
|
Time |
|
Sent To |
I |
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |