| 2003-10-24 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE MAKE THE FOLLOWING CHANGES TO |
| | PLAN FOR CODE COMPLIANCE,AND RESUBMIT |
| | FOR REVIEW. |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2} PLEASE NOTE THAT ALL PLANS |
| | THAT ARE SIGNED AND SEALED BY ARCH/ OR |
| | ENGINEER ARE REQ`D PER 61G15-23.002 FOR |
| | ENGINEER AND 61G1-16.004 FOR ARCH. |
| | SHALL HAVE A TITLE BLOCK.ALSO A WET |
| | SIGNATURE. |
| | |
| | 3} PLEASE NOTE THAT THE DRYER LISTED ON |
| | THE PANEL SCHEDULE IS SHOWN AT 20 AMPS. |
| | SEE 220.18. |
| | |
| | 4} PLEASE DO LOAD CALCULATIONS PER |
| | 220.30,220.31 OR SHOW A GENERAL LOAD |
| | CALC PER ARTICLE 220. |
| | |
| | 5} PLEASE NOTE THE GEC MUST COMPLY WITH |
| | 250.66,INDICATE ON THE RISER DIAGRAM. |
| | |
| | 6} THE PANEL SCHEDULE INDICATES NEW |
| | SMALL APPLIANCE CIRCUITS,BUT NO WORK TO |
| | THE KITCHEN IS INDICATED IN THE SCOPE |
| | OF WORK FOR THIS PERMIT.THE LAST |
| | ELECTRICAL PERMIT ISSUED BESIDES LOW |
| | VOLTAGE WAS IN 1997 AND FOR A PANEL |
| | RELOCATION.IF THE KITCHEN IS TO BE |
| | REWIRED PLEASE INDICATE SAME ON THE |
| | PERMIT APPLICATION AND INCLUDE IN THE |
| | VALUE OF THE JOB. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECRICAL PLAN REVIEW |
| | 561/805-6718 |