Plan Review Details - Permit 03101282
Plan Review Stops For Permit 03101282
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-01-27 Cont ID  
Sent By jwitmer Date 2005-01-27 Time 08:14 Rev Time 0.00
Received By pschmitz Date 2005-08-18 Time 14:58 Sent To B
Notes
2005-08-18 00:00:00REVISION:
 DETAIL OF SAFE WASTE
2005-01-27 00:00:001-27-05 REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-07-23 Cont ID  
Sent By jwitmer Date 2004-07-16 Time 09:02 Rev Time 1.10
Received By jwitmer Date 2004-07-23 Time 11:11 Sent To PC
Notes
2004-07-16 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03101282
 ADD: 1931 N DIXIE HWY
 CONT: MCLAREN CONSTRUCTION
 TEL: (561)686-6500
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) PROVIDE A UNITY OF TITLE FOR LOTS
 11,21&22. PLANS INDICATE WORK TO BE
 SOMPLETED AT 1935, APPLICATION INDICATES
 1931, WORK WILL BE CROSSING PROPERTY
 LINES.
  
 2) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-01-05 Cont ID  
Sent By jwitmer Date 2004-01-05 Time 09:27 Rev Time 2.75
Received By jwitmer Date 2004-01-05 Time 09:27 Sent To  
Notes
2004-01-05 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03101282
 ADD: 1931 N DIXIE
 CONT: MCLAREN CONSTRUCTION
 TEL: (561)686-6500
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 SECOND REVIEW
 ACTION DENIED:
  
 1) PROVIDE A UNITY OF TITLE FOR LOTS
 11,21& 22. PLANS INDICATE WORK BEING
 DONE AT 1935, APPLICATION INDICATES 1931
 CROSING PROPERTY LINES! TABLE 600 ISSUES
  
 2) 1027.1.1(3) STORAGE SINGLE EXIT,
 SINGLE EXIT MAXIMUM TRAVEL DISTANCE TO
 THE EXIT DOES NOT EXCEED 50 FT. FREZZER
 ON THE DIAGONAL 60 FT.
  
 3)1004.1.4 WHERE 2 OR MORE EXITS OR
 EXIT ACCESS DOORS ARE REQUIED, AT LEAST
 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL
 BE PLACED A DISTANCE APART EQUAL TO NOT
 LESS THAN 1/2 OF THE LENGTH OF THE MAX-
 IMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA TO BE SERVED.
 EXCEPTION: SPRINKLERED BUILDINGS; 1/3RD
 THE LENGTH OF THE DIAGONAL OF THE BUILD-
 ING OR AREA TO BE SERVED.
  
 4) 2603.5.1.2 FOAM PLASTIC INSTALLED IN
 A MAXIMUM OF 10" IN COOLER AND FREZZER
 WALLS.
 (4) BE PROTECTED BY AN AUTOMATIC
 SPRINKLER SYSTEM. WHERE THE FREZZER OR
 COOLER IS WITHIN A BUILDING, BOTH THE
 COOLER OR FREEZER AND THE PART OF THE
 BUILDING IN WHICH IT IS LOCATED SHALL BE
 FIRE SPRINKLERED.
  
 THE EXCEPTION TO THIS CODE SECTION IS
 2603.5.1.3 WALK IN COOLERS: IN UNSPRINK-
 LERED BUILDINGS WHERE THE FOAM "DOES NOT
 EXCEED 4" AND THE TOTAL AGGREGATE FLOOR
 AREA OF THE COOLERS OR FREZEERS DOES NOT
 EXCEED 400 SQ. FT.
 THE ADDITIONAL WALK IN COOLERS AND
 FREEZERS ARE WELL OVER 400 SQ. FT.
 REQUIRING THE FIRE SPRINKLER SYSTEM.
 BEAUSE COLD STORAGE CONSTRUCTION FRE-
 QUENTLY USES INSULATION IN GREATER THICK
 NESSES, AN EXCEPTION IS GIVEN TO THE RE-
 QUIREMENT FOR THE TESTING AT THICKNESSES
 OF INTENDED USE. IN SUCH CASE, OTHER
 PROTECTION, SPECIFICICALLY AUTOMATIC
 FIRE SUPPRESSION IS REQUIRED INSTEAD.
  
 5)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-11-19 Cont ID  
Sent By jwitmer Date 2003-11-19 Time 08:57 Rev Time 0.00
Received By jwitmer Date 2003-11-19 Time 10:57 Sent To  
Notes
2003-11-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03101282
 ADD: 1931 N DIXIE
 CONT: MCLAREN CONSTRUCTION
 TEL: (561)686-6500
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) PROVIDE A UNITY OF TITLE FOR LOTS
 11,21 & 22. PLANS INDICATE WORK BEING
 DONE AT 1935, APPLICATION INDICATES 1931
 CROSSING THE PROPERTY LINES!
  
 2) 1027.1.1 STORAGE SINGLE EXIT, (3)
 SINGLE EXIT MAXIMUM TRAVEL DISTANCE TO
 THE EXIT DOES NOT EXCEED 50 FT.
  
 3) SECTION 2/6 MECHANICAL ROOF TOP UNITS
 SEE TABLE 1511.7 THE MINIMUM "CLEAR
 HEIGHT"REQUIRED UNDER A/C UNITS WILL
 VARY ON THE WIDTH OF THE UNIT!
  
 4) 2603.5.1.2 COOLER AND FREEZER WALLS.
 MUST MEET REQUIREMENTS 1-4,
 1) FLAME SPREAD INDEX OF 25 OR LESS
 SMOKE DEVELOPMENT OF NOT MORE THAN
 450, WHERE TESTED IN A MINIMUM 4"
 THICKNESS.
 2) HAVE FLASH AND SELF-IGNITION TEMP-
 ERATURES OF 600 DEGREES AND 800 DE-
 GREES RESPECTIVELY
 3) HAVE A COVERING OF NOT LESS THAN
 0.032 INCH THICK ALUMINIUM OR COR-
 ROSION - RESISTANT STEEL HAVING A
 BASE METAL THICKNESS NOT LESS THAN
 0.016 INCHES
 4) BE PROTECTED BY AN AUTOMATIC SPRINK
 LER SYSTEM. WHERE THE COOLER OR
 FREEZER AND THAT PART OF THE BUILD-
 ING IN WHICH IT IS LOCATED SHALL BE
 SPRINKLERED.
  
 5) IN UNSPRINKLERED BUILDINGS FOAM
 PLASTIC HAVING A THICKNESS THAT DOES NOT
 EXCEED 4 INCHES AND A MINIMUM FLAME
 SPREAD OF 75 IS PERMITTED IN WALK-IN
 COOLERS OR FREEZER UNITS WHERE THE
 AGGREGATE FLOOR AREA DOES NOT EXCEED 400
 SQ FT AND THE FOAM PLASTIC IS COVERED BY
 A METAL FACING NOT LESS THAN 0.032 "
 THICK ALUMINUM OR CORRISION-RESISTANT
 STEEL HAVING A MINIMUM BASE METAL OF
 0.016. ATHICKNESS OF UP TO 10" IS PERMIT
 TED WHERE PROTECTED BY A THERMAL BARRIER
  
 6)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 7)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT.
 MISSING REPORTS:
 A) EXTERIOR DOORS
 B) ROOFING ASSEMBLIES.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVALFORM PER
 RULE 9B-72. SEE ATTACHMENT.
  
 8) 1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 9)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-09-01 Cont ID  
Sent By dpalmer Date 2005-09-01 Time 13:24 Rev Time 0.33
Received By dpalmer Date 2005-09-01 Time 13:24 Sent To  
Notes
2005-09-01 00:00:00**REDLINED EQUIPMENT GROUNDING NOT SHOWN
 TO PANEL "S".
 SIZING PER 250.122
 250.110

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2005-08-09 Cont ID  
Sent By dpalmer Date 2005-08-09 Time 20:08 Rev Time 0.40
Received By dpalmer Date 2005-08-09 Time 20:08 Sent To  
Notes
2005-08-09 00:00:00************* UNSAT *************
  
 1)NOTE: PLEASE SEE EQUIPMENT GROUNDING
 NOT SHOWN FROM MAIN TO GUTTER, SUB
 PANELS. PLEASE SIZE PER 250.122.
 250.110,250.24.250.118, LOCAL
 AMENDMENTS.
 PLEASE SEE PREVIOUS PLANS CALLED FOR
 EQUIPMENT GRNDS, HOWEVER THEY WERE
 REDLINED AS BEING WRONG SIZE.
  
 2)NOTE: PLEASE SEE PLANS INDICATE "TWO"
 -SECTIONS FOR PANEL "T", PANEL SCHEDULE
 FOR PANEL "T" ALSO IS SHOWN AS 84
 CIRCUITS, HOWEVER WHAT APPEARS TO BE
 ONLY ONE PANEL SCHEDULE, WITH 42
 CIRCUITS WAS SUBMITTED?
 PLEASE CORRELATE. IF SECTION TWO TO
 PANEL "T" DOES NOT CONTAIN ANY OCP
 DEVICES OR CIRCUIT, PLEASE SHOW SEC TWO
 BLANK. IF INDEED THERE ARE CIRCUITS IN
 THIS PANEL, PLEASE SHOW.
 PLEASE ALSO SEE RISER SHOWS ONLY ONE
 PANEL SECTION FOR "T".
 215.5
  
 3)NOTE: PLEASE INDICATE ALL CIRCUITING
 ON PLANS AND CORRELATE WITH THE
 SUBMITTED PANEL SCHEDULE.
 PLEASE SEE EM/EXT LTS, 700.12E,THE
 BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 PLEASE SEE OTHER POSSIBLE LTS SHOWN ON
 PLANS WHICH DO NOT APPEAR TO SHOW ANY
 MEANS OF CONTROL OR CIRCUITS?
 THESE HAVE BEEN REDLINED ON ONE SET OF
 PLANS.
  
 PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL THIS
 OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-01-24 Cont ID  
Sent By dpalmer Date 2005-01-24 Time 17:45 Rev Time 0.33
Received By dpalmer Date 2005-01-24 Time 17:45 Sent To  
Notes
2005-01-24 00:00:00********** NOTES REDLINED **********
  
 PLEASE SEE EQUIPMENT GROUNDING CONDUCTOR
 REDLINED ON ORIG PLANS ARE STILL SHOWN
 WRONG SIZE. PLEASE SEE 250.122 FOR MIN
 SIZE FOR 600A'S.
  
 PLEASE ALSO SEE RISER SHOWS AN EQUIPMENT
 GROUNDING CONDUCTOR FROM METER TO MAIN
 DISC. PLEASE SEE THIS IS NOT PERMITTED
 UNDER 250.6,250.24. AN EQP GRND IS ONLY
 INSTALLED "AFTER" THE FIRST MEANS OF
 DISCONNECT.
  
  
 **PLEASE SEE THESE ITEMS HAVE BEEN
 REDLINED ON PLANS AND NEED TO BE
 CORRECTED IF PLANS COME BACK IN FOR
 REVISIONS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-07-06 Cont ID  
Sent By dpalmer Date 2004-07-06 Time 09:00 Rev Time 0.30
Received By dpalmer Date 2004-07-06 Time 08:56 Sent To  
Notes
2004-07-06 00:00:00REDLINED EQUIPMENT GRND TO BE SIZED PER
 250.122.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-12-30 Cont ID  
Sent By dpalmer Date 2003-12-30 Time 07:21 Rev Time 0.33
Received By dpalmer Date 2003-12-30 Time 07:21 Sent To  
Notes
2003-12-30 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLANS HAD ORIGINALLY PASSED WITH
 REDLINED PLANS FOR MISSING ALL EQUIPMENT
 GROUNDING CONDUCTORS. TWO NEW SEPARATE
 SHEETS WERE TURNED IN, NOT IN SETS AND
 ONLY ONE EQUIPMENT GROUNDING CONDUCTOR
 WAS ADDED FROM GUTTER TO SUB-PANEL "S".
  
 PLEASE SEE THAT ALL OLD/VOIDED/REPLACED
 SHEETS MUST BE REMOVED FROM OLD SETS AND
 INSERT ANY AND ALL NEW SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 THESE NEW SHEETSHAVE NOT BEEN CORRECT-
 -ED TO ORIG NOTE. 250.110, 250.122, 250.
 24 ETC.
  
 PLEASE SUBMIT ANY REVISED SHEETS INTO
 SETS. REVISED SHEETS ALSO CONATIN PLUMB-
 ING DETAILS.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-10-28 Cont ID  
Sent By dpalmer Date 2003-10-28 Time 06:28 Rev Time 0.50
Received By dpalmer Date 2003-10-28 Time 06:17 Sent To  
Notes
2003-10-28 00:00:00****** REDLINED *******
  
 1)NOTE: EQUIPMENT GROUNDING FROM MAIN TO
 GUTTER AND FROM GUTTER TO SUB-PANELS.
 250.110/ 250.122
  
 2)NOTE: 700.12E
  
 PASSED PENDING ANY COMMENTS FROM OTHER
 REVIEWERS THAT MAY HAVE AN AFFECT ON
 ELECTRICAL PLAN.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2003-11-26 Cont ID  
Sent By csiegber Date 2003-11-26 Time 14:42 Rev Time 0.00
Received By csiegber Date 2003-11-26 Time 14:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-08-15 Cont ID  
Sent By mwennerg Date 2005-08-15 Time 13:50 Rev Time 0.00
Received By mwennerg Date 2005-08-15 Time 13:50 Sent To  
Notes
2005-08-15 00:00:00REVISION DATED 7/25/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-02-23 Cont ID  
Sent By nmccray Date 2005-02-23 Time 10:13 Rev Time 0.00
Received By nmccray Date 2005-02-23 Time 10:08 Sent To  
Notes
2005-02-23 00:00:00REVISION 1-20-05

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-12-24 Cont ID  
Sent By mcarsill Date 2003-12-24 Time 15:52 Rev Time 0.00
Received By mcarsill Date 2003-12-24 Time 15:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-11-13 Cont ID  
Sent By mcarsill Date 2003-11-13 Time 07:09 Rev Time 0.00
Received By mcarsill Date 2003-11-13 Time 07:09 Sent To  
Notes
2003-11-13 00:00:001) PLEASE EXPLAIN RATIONALE FOR THE
 DOOR SIZES BEING USED FOR EXITING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-08-30 Cont ID  
Sent By adarroug Date 2005-08-30 Time 14:56 Rev Time 0.00
Received By adarroug Date 2005-08-30 Time 14:56 Sent To E
Notes
2005-08-30 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-07-28 Cont ID  
Sent By adarroug Date 2005-07-28 Time 13:43 Rev Time 0.00
Received By adarroug Date 2005-07-28 Time 13:43 Sent To  
Notes
2005-08-01 00:00:00TO "COMM" BD#33
2005-07-28 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-01-20 Cont ID  
Sent By mjacobs Date 2005-01-20 Time 13:03 Rev Time 0.00
Received By mjacobs Date 2005-01-20 Time 13:03 Sent To  
Notes
2005-01-20 00:00:00TO "COMM BD#64/REV.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-08-11 Cont ID  
Sent By csiegber Date 2004-08-11 Time 15:31 Rev Time 0.00
Received By csiegber Date 2004-08-11 Time 15:31 Sent To P
Notes
2004-08-11 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-30 Cont ID  
Sent By csiegber Date 2004-06-30 Time 13:46 Rev Time 0.00
Received By csiegber Date 2004-06-30 Time 13:46 Sent To  
Notes
2004-06-30 00:00:00TO COMM BD#42

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-12-16 Cont ID  
Sent By csiegber Date 2003-12-16 Time 12:37 Rev Time 0.00
Received By csiegber Date 2003-12-16 Time 12:37 Sent To  
Notes
2003-12-16 00:00:00TO COMM BD#24

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-10-21 Cont ID  
Sent By mmclean Date 2003-11-24 Time 11:15 Rev Time 0.00
Received By csiegber Date 2003-10-21 Time 16:52 Sent To  
Notes
2003-10-21 00:00:00TO COMM BD#26

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2005-02-15 Cont ID  
Sent By pkrauss Date 2005-02-15 Time 15:08 Rev Time 0.35
Received By pkrauss Date 2005-02-15 Time 15:04 Sent To  
Notes
2005-02-15 00:00:00HANGING DETAIL REVISED

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-07-06 Cont ID  
Sent By pkrauss Date 2004-07-06 Time 13:02 Rev Time 0.20
Received By pkrauss Date 2004-07-06 Time 13:02 Sent To  
Notes
2004-07-06 00:00:00HVAC NOT REQUIRED UNDER THIS PERMIT.
 PLEASE PROVIDE MANUFACTURER CUT SHEETS
 FOR COOLER/FREEZER ON THE JOBSITE AT THE
 TIME OF INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2003-12-30 Cont ID  
Sent By pkrauss Date 2003-12-30 Time 13:38 Rev Time 0.45
Received By pkrauss Date 2003-12-30 Time 12:39 Sent To  
Notes
2003-12-30 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW COOLER/FREEZER CUT SHEETS TO BE
 SUBMITTED BY THE REFRIGERATION
 CONTRACTOR.ALL OTHER COMMENTS
 ADDRESSED BY LETTER FROM THE ARCHITECT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2003-12-03 Cont ID  
Sent By pkrauss Date 2003-12-03 Time 10:01 Rev Time 0.15
Received By pkrauss Date 2003-12-03 Time 10:01 Sent To  
Notes
2003-12-03 00:00:00THIS NOTE WAS PER PHONE CONVERSATION
 NOT A RE-SUB OR REVISION:
 COVERSATION W/RAY SEAY CONDENSATE
 TERMINATION IS INDICATED ON PLAN SHEET
 2-B.SAFE-WASTE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-11-24 Cont ID  
Sent By pkrauss Date 2003-11-24 Time 06:37 Rev Time 0.45
Received By pkrauss Date 2003-11-24 Time 06:31 Sent To Z
Notes
2003-11-24 00:00:00DENIED:
 1.PLEASE PROVIDE ENERGY CALCULATIONS
 PER 2001 FBC CHAPTER 13 SUB-CHAPTER 400.
  
 2.PLEASE NOTE PLAN SHEET 6 INDICATES
 HEIGHT OF STANDS FOR CONDENSING UNITS.
 HEIGHT REQUIREMENTS SHALL COMPLY WITH
 2001 FBC 1511.7 (SEE ATTACHED).
  
 3.PLEASE NOTE SHOULD ROOF WHERE THE
 CONDENSERS ARE LOCATED BE GREATER THAN
 16 FT AN APPROVED PERMANENT MEANS OF
 ACCESS WILL BE REQUIRED.
  
 4.COMPLY WITH 2001 FBC 2603.5.1.2 FOR
 CONSTRUCTION OF FREEZER/COOLERS SHOULD
 A PREMANUFACTURED COOLER/FREEZER NOT
 BE USED.PROVIDE MANUFACTURER SUBMITTAL
 DATA FOR COOLER/FREEZER SHOULD A PRE-
 MANFACTUERED UNIT NOT BE USED.
  
 5.PROVIDE INFORMATION ON REFRIGERANT
 AND LINE SETS.INDICATE MATERIAL OF
 REFRIGERANT PIPING.
  
 6.ALL REFRIGERANT PIPING INSTALLED ON
 SITE SHALL BE TESTED IN ACCORDANCE WITH
 2001 FBC(M) 1108.2 AT ONE AND HALF TIMES
 THE DESIGN PRESSURE FOR A MINIMUM OF 4
 HOURS.
  
 7.INDICATE CONDENSATE PIPING AND
 TERMINATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 6 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2005-02-15 Cont ID  
Sent By kstevens Date 2005-02-15 Time 17:06 Rev Time 0.75
Received By kstevens Date 2005-02-15 Time 17:06 Sent To  
Notes
2005-02-15 00:00:00DENIED
 REFERENCE; FBC-2001 CHAPTER 11
  
 1) NEW TOILET LAYOUT, SHOW 5 FOOT
 TURNING AREA REQUIRED BY SECTION
 11-4.22.3.
  
 2) PLUMBING OK - RESUBMIT SHT 2
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-08-23 Cont ID  
Sent By kstevens Date 2004-08-23 Time 11:59 Rev Time 0.25
Received By kstevens Date 2004-08-21 Time 11:19 Sent To  
Notes
2004-08-23 00:00:00REVISION REQUIRED FOR RED LINE CORRECT-
 IONS

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-07-17 Cont ID  
Sent By csiegber Date 2004-08-11 Time 15:31 Rev Time 1.00
Received By kstevens Date 2004-07-17 Time 11:55 Sent To  
Notes
2004-07-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
  
  
  
 1) FROM PREVIOUS REVIEWS: THE FLOOR
 DRAINS IN THE COOLERS ARE NOT INDIRECTLY
 CONNECTED AS REQUIRED IN SECTION 802.1.2

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-01-08 Cont ID  
Sent By kstevens Date 2004-01-08 Time 13:54 Rev Time 2.00
Received By kstevens Date 2004-01-08 Time 13:54 Sent To  
Notes
2004-01-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 BUILDING
  
 1) FROM PREVIOUS REVIEW: SHT 5 FROOR
 DRAINS/SINKS LOCATED WITHIN WALK-IN
 REFRIGERATORS OR FREEZERS IN FOOD SERV-
 ICE AND FOOD ESTABLISHMENTS SHALL BE IN-
 DIRECTLY CONNECTED TO THE SANITARY
 DRAINAGE SYSTEM BY MEANS OF AN AIR GAP.
 SECTION 802.1.2
 2) RESPONSE FROM PREVIOUS REVIEW NOTED:
 FOLLOWING INFORMATION REQUIRED.
 A) GUTTERS AND DOWNSPOUTS NOT SHOWN FOR
 EAST SIDE OF BUILDING.
 B) COMMENT RESPONSE STATES THAT IS
 ASSUMED THAT 1/2 AREA OF ROOF DRAINS TO
 THE EAST, AND 1/2 AREA OF ROOF DRAINS TO
 THE WEST. SINCE SIZING OF GUTTERS AND
 DOWNSPOUTS REQUIRE SQUARE FOOTAGE TO BE
 CALCULATED FOR EACH DOWNSPOUT, SHOW
 EXACTLY WHERE THE ROOF PITCHES FROM AND
 IN WHAT DIRECTION.
 C) SHOW HIGH AND LOW POINTS OF THE GUTT-
 ERS AND INDICATE THE SQUARE FOOTAGE BE-
 ING DRAINED BY EACH DOWNSPOUT.
 D) CLAIRFY OPTIONAL GUTTER. GUTTERS ARE
 REQUIRED.
 E) ONE PORTION OF RESPONSE INDICATES A
 3" RWL, AND ANOTHER PORTION OF RESPONSE
 INDICATES 4" RWL. PLEASE CLAIRFY.
 F) INDICATE THE HEIGHT AND WIDTH OF ALL
 GUTTERS.
 3) SEE ATTACHED SHEET CONCERNING DESIGN
 PROFESSIONALS AND FS553.80(2)(B).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-11-04 Cont ID  
Sent By kstevens Date 2003-11-04 Time 14:49 Rev Time 1.00
Received By kstevens Date 2003-11-04 Time 14:49 Sent To  
Notes
2003-11-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT 5 FLOOR DRAINS LOCATED WITHIN
 WALK-IN REFRIGERATORS OR FREEZERS IN
 FOOD SERVICE AND FOOD ESTABLISHMENTS
 SHALL BE INDIRECTLY CONNECTED TO THE
 SANITARY DRAINAGE SYSTEM BY MEANS OF AN
 AIR GAP. SECTION 802.1.2
 2) SHT 5, EVERY DRY VENT CONNECTING TO A
 HORIZONTAL DRAIN SHALL CONNECT ABOVE THE
 CENTERLINE OF THE HORIZONTAL DRAIN PIPE.
 SECTION 905.3. (NO HORIZONTAL DRY VENTS)
 3) SHT 5, FLOOR DRAINS ARE NOT APPROVED
 FOR USE AS AN INDIRECT WASTE. SECTION
 802.3
 4) SHT 6, SUBMIT CALCULATIONS FOR ROOF
 DRAINS, GUTTERS AND DOWNSPOUTS PER TABLE
 1106.6. SHOW TOTAL SQUARE FOOTAGE OF
 ROOF, AND SHOW 1/2 AREA OF ALL VERTICAL
 WALLS INCLUDING PARAPETS IN CALCULATIONS
 SHOW SIZE OF GUTTERS AND DOWNSPOUTS.
 SHOW LOCATIONS OF GUTTERS AND DOWNSPOUTS
 SHOW SLOPE OF ROOF AND SLOPE OF GUTTERS.
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2003-11-24 Cont ID  
Sent By pkrauss Date 2003-11-24 Time 07:57 Rev Time 0.00
Received By mmclean Date 2003-11-24 Time 11:15 Sent To I
Notes
***NONE***