Plan Review Details - Permit 03101273
Plan Review Stops For Permit 03101273
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-12-17 Cont ID  
Sent By shill Date 2003-12-17 Time 18:15 Rev Time 1.00
Received By shill Date 2003-12-17 Time 18:15 Sent To  
Notes
2004-01-29 00:00:00**OK TO REPLACE EX. BEDROOM WINDOWS
 WITH SAME SIZE/TYPE PER NMK, SEE LETTER
 IN FILE

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-11-29 Cont ID  
Sent By btrobaug Date 2003-12-17 Time 14:15 Rev Time 1.50
Received By sthyng Date 2003-11-29 Time 13:50 Sent To M
Notes
2003-11-29 00:00:00*****CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)PROVIDE THE RECEIPT FOR IMPACT
 FEES.
  
 2.)SEE PREVIOUS LIST, ITEM #6, ATTIC
 ACCESS REQUIRED.SHEET A2.0 SHOWS AN
 EXISTING ATTIC ACCESS SERVING THE
 EXISTING HOUSE.IF THE TRUSSES ARE TO
 REMAIN, ACCESS TO THE NEW ATTIC AREA
 (ADDITION) WILL NOT BE POSSIBLE.PLEASE
 CALL ME TO CLARIFY IF NECESSARY.
  
 3.)THE PRODUCT APPROVALS SUBMITTED,
 KINCO SINGLE HUNG IMPACT WINDOW, ARE
 ACCEPTABLE FOR SOME WINDOWS ON THE PLAN
 BUT NOT FOR THE LARGER WINDOWS.THE
 DESIGN PRESSURE FOR THE WINDOWS EXCEED
 THE MAXIMUM DESIGN LOAD CAPACITY (SEE
 THE PRODUCT APPROVAL, HIGHLIGHTED).
  
 4.)THE THERMA-TRU DOOR HAS A STATUS
 OF "PENDING" ON THE DCA WEBSITE.PER
 THE FLORIDA BUILDING COMMISSION, WE
 CANNOT ACCEPT PRODUCTS ON THE PENDING
 LIST.THIS PERMIT CAN BE ISSUED WITH A
 PROVISO THAT A SEPARATE PERMIT BE
 OBTAINED FOR THE DOOR.THERE AREN'T ANY
 EXTERIOR DOORS ON THE PLAN; IF YOU ARE
 REPLACING AN EXISTING DOOR AND WISH FOR
 IT TO BE COVERED UNDER THIS PERMIT,
 REVISE YOUR PERMIT APPLICATION,
 INDICATING WHICH DOOR IS BEING REPLACED.
  
 5.)THE PLANS SHOW WINDOWS WHICH ARE
 "EXISTING", BUT YOUR PERMIT APPLICATION
 INDICATES "WINDOW REPLACEMENT".ARE
 YOUR REPLACING ALL OF THE WINDOWS IN
 THE HOUSE?IF YOU ARE, EXISTING
 BEDROOMS WITH WINDOW BEING REPLACED
 MUST COMPLY WITH FBC1005.4, EMERGENCY
 EGRESS.THE SIZES SHOWN DO NOT COMPLY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-11-13 Cont ID  
Sent By sthyng Date 2003-11-24 Time 13:46 Rev Time 2.00
Received By sthyng Date 2003-11-13 Time 11:28 Sent To  
Notes
2003-11-13 00:00:00*****CORRECTIONS*****
  
 SAMANTHA THYNG (HILL), BUILDING PLANS
 EXMINER561-805-6724
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 3.)PROVIDE A COPY OF THE SURVEY FOR
 THIS PROPERTY.
  
 4.)ADDITIONAL FEES DUE, $3.38.SEE
 ATTACHED BZ233268.(RADON FEES)
  
 5.)PROVIDE ATTIC VENTILATION TO
 COMPLY WITH FBC2309.7.
  
 6.)ATTIC ACCESS REQUIRED, FBC2309.
  
 7.)THE WINDOW SCHEDULE, A2.0, REFERS
 TO THE STRUCTURAL DRAWINGS FOR DESIGN
 PRESSURES.THEY ARE NOT ON THE
 STRUCTURAL DRAWINGS; PROVIDE.
  
 8.)EFFECTIVE OCTOBER 1, STATEWIDE
 PRODUCT APPROVALS ARE REQUIRED.THE
 LIST IS AVAILABLE ONLINE, PLEASE PROVIDE
 THE STATEWIDE PRODUCT APPROVAL AS A
 COVER SHEET TO THE PRODUCT APPROVALS
 ALREADY REVIEWED BY HISTORIC
 PRESERVATION DEPARTMENT.
 WWW.FLORIDABUILDING.ORG (PRODUCT
 APPROVAL, PRODUCT SEARCH).
  
 FOR MORE INFORMATION IN REGARDS TO THE
 PROGRAM, SEE THE DCA WEBSITE AT:
 WWW.DCA.STATE.FL.US/FHCD/FBC/COMMITTEES/
 PRODUCT_APPROVAL/1_PRODUCT_APPROVAL.HTM
  
 IN ADDITION TO THE STATEWIDE PRODUCT
 APPROVAL REQUIRED FOR THE WINDOW, ALSO
 SUBMIT PRODUCT APPROVALS FOR THE ROOF,
 WINDOW MULLION, AND STRUCTURAL
 COMPONENTS (WOOD CONNECTORS).
  
 ANY PRODUCT APPROVALS NOT SUBMITTED
 BEFORE THE PERMIT IS ISSUED WILL
 REQUIRE THAT A SEPARATE PERMIT BE
 OBTAINED FOR THAT ITEM WITH ADDITIONAL
 FEES.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-04-23 Cont ID  
Sent By dpalmer Date 2004-04-23 Time 11:22 Rev Time 0.50
Received By dpalmer Date 2004-04-23 Time 11:22 Sent To  
Notes
2004-04-23 00:00:00** REDLINED **
  
 COLD WATER PIPE
 SUBMIT AIC RATING.110.9

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-12-17 Cont ID  
Sent By alange Date 2004-04-22 Time 11:04 Rev Time 0.50
Received By btrobaug Date 2003-12-17 Time 13:39 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-11-21 Cont ID  
Sent By csiegber Date 2003-12-12 Time 13:41 Rev Time 0.50
Received By btrobaug Date 2003-11-21 Time 15:29 Sent To P
Notes
2003-11-21 00:00:00 
 DENIED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 NOTE: PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED, DATED
 AND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
 ONLY ONE SET SIGNED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-27 Cont ID  
Sent By csiegber Date 2003-11-21 Time 11:39 Rev Time 0.50
Received By btrobaug Date 2003-10-27 Time 12:19 Sent To P
Notes
2003-10-27 00:00:00UNSAT
 ~~~~~
 PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED, DATED
 AND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-04-22 Cont ID  
Sent By alange Date 2004-04-22 Time 11:04 Rev Time 0.00
Received By alange Date 2004-04-22 Time 11:04 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-12-12 Cont ID  
Sent By csiegber Date 2003-12-12 Time 13:40 Rev Time 0.00
Received By csiegber Date 2003-12-12 Time 13:40 Sent To E
Notes
2003-12-12 00:00:00TO BT DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-11-21 Cont ID  
Sent By csiegber Date 2003-11-21 Time 11:39 Rev Time 0.00
Received By csiegber Date 2003-11-21 Time 11:39 Sent To E
Notes
2003-11-21 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-10-24 Cont ID  
Sent By csiegber Date 2003-10-24 Time 14:53 Rev Time 0.00
Received By csiegber Date 2003-10-24 Time 14:53 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-10-21 Cont ID  
Sent By mmclean Date 2003-10-24 Time 10:26 Rev Time 0.00
Received By csiegber Date 2003-10-21 Time 16:30 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-12-02 Cont ID  
Sent By pkrauss Date 2003-12-02 Time 13:32 Rev Time 0.33
Received By pkrauss Date 2003-12-02 Time 12:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2003-11-14 Cont ID  
Sent By sthyng Date 2003-11-29 Time 15:46 Rev Time 0.25
Received By pkrauss Date 2003-11-14 Time 08:20 Sent To  
Notes
2003-11-14 00:00:00SPOKE WITH OWNER BUILDER
 #1 A/C PLAN ON THE ME SHEET.
 #2 ENERGY CALCS ARE FOR THE SECOND FLOOR
 #3 OKAY
 #4 LOCATION OF THE AHU IS ON THE SECOND
 FLOOR IN A CLOSET.
 OWNER BUILDER WILL MAKE CORRECTIONS &
 RESUBMIT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-11-05 Cont ID  
Sent By jleech Date 2003-10-28 Time 17:27 Rev Time 0.33
Received By pkrauss Date 2003-11-05 Time 07:10 Sent To B
Notes
2003-11-05 00:00:00DENIED:
 1.NO MECHANICAL PLANS SUBMITTED.
  
 2.ENERGY CALCULATIONS INDICATE AN
 ADDITION BUT WITH 1038 SQ FT OF
 CONDITION SPACE. WILL THE A/C SYSTEM BE
 INSTALLED FOR THE ENTIRE HOUSE OR JUST
 THE ADDITION?MANUAL J CALCULATIONS ARE
 FOR THE SECOND FLOOR ONLY.
  
 3.PLEASE PROVIDE EQUIPMENT INFORMATION
 (MAKE, MODEL, BTU'S AND SEER OF THE
 CONDENSER).
  
 4.INDICATE LOCATION OF EQUIPMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-11-24 Cont ID  
Sent By pschmitz Date 2003-11-24 Time 13:37 Rev Time 2.00
Received By sthyng Date   Time   Sent To B
Notes
2003-11-24 00:00:00PROVISO:
 SEE SHT PE1.0, SEC 909 WET VENTING.
 PASSED PER PSCHMITZ

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-10-28 Cont ID  
Sent By btrobaug Date 2003-11-21 Time 15:54 Rev Time 0.33
Received By jleech Date 2003-10-28 Time 17:26 Sent To M
Notes
2003-10-28 00:00:00DENIED;
 SANITARY RISER DIAGRAM IS NOT THE SAME
 AS FLOOR PLAN. SHOW HOW 2ND BATHROOM AND
 WASHING MACHINE ARE TO BE PIPED AND SIZE
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2003-10-24 Cont ID  
Sent By csiegber Date 2003-10-21 Time 16:30 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***