Plan Review Details - Permit 03101246
Plan Review Stops For Permit 03101246
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-01-21 Cont ID  
Sent By jwitmer Date 2004-01-21 Time 13:07 Rev Time 0.75
Received By jwitmer Date 2004-01-21 Time 13:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-01-15 Cont ID  
Sent By csiegber Date 2004-01-21 Time 12:34 Rev Time 0.55
Received By jwitmer Date 2004-01-15 Time 11:44 Sent To  
Notes
2004-01-15 00:00:001 SET OF NEW PLANS REVISIONS ON A2,A4
 1 SET OF OLD DRAWINGSJ WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-12-11 Cont ID  
Sent By jwitmer Date 2003-12-11 Time 12:27 Rev Time 0.75
Received By jwitmer Date 2003-12-11 Time 12:27 Sent To  
Notes
2003-12-11 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03101246
 ADD: 777 S FLAGLER DR/ SUITE # 218
 CONT: DEWHURST ASSOC
 TEL: (561)241-1540
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 BUILDING PROVISO:
 OFFICE # 13 ENTRY: TO COMPLY WITH FL BLD
 CODE 11-4.13.6 MANEUVERING CLEARENCE AT
 DOORS, PULL SIDE 18" FOR DOORS THAT ARE
 NOT AUTOMATIC OR POWER-ASSISTED.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-11-14 Cont ID  
Sent By jwitmer Date 2003-11-14 Time 14:03 Rev Time 1.50
Received By jwitmer Date 2003-11-14 Time 14:03 Sent To  
Notes
2003-11-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03101246
 ADD: 777 S FLAGLER SUITE# 128
 PHILLIPS POINT WEST TOWER
 CONT: DEWHURST ASSOC
 TEL: (561)241-1540
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) FBC 1004.1.2 EVERY ROOM OR TENANT
 SPACE SHALL BE PROVIDED WITH A MINIMUM
 OF ONE MEANS OF EGRESS. EVERY ROOM OR
 TENANT SPACE WHICH HAS AN OCCUPANT LOAD
 OF 50 OR PERSONS OR IN WHICH THE TRAVEL
 DISTANCE FROM THE MOST REMOTE POINT TO
 THE EXIT ACCESS FROM THE ROOM OR TENANT
 SPACE EXCEEDS 75 FT SHALL HAVE NOT LESS
 THAN TWO EGRESS DOORS.
  
 2) THE COMMON PATH OF TRAVEL SHALL NOT
 EXCEED 75 FT. EXCEPTION: AS MODIFIED BY
 SECTION 1018. 1020.1(4) MAXIMUM TRAVEL
 DISTANCE SINGLE EXIT 75 FT.
  
 3)1004.1.4 WHERE 2 OR MORE EXITS OR
 EXIT ACCESS DOORS ARE REQUIED, AT LEAST
 2 OF THE EXIT OR EXIT ACCESS DOORS SHALL
 BE PLACED A DISTANCE APART EQUAL TO NOT
 LESS THAN 1/2 OF THE LENGTH OF THE MAX-
 IMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA TO BE SERVED.
 EXCEPTION (2) 1/3RD DISTANCE FOR FULLY
 SPRINKLERED BUILDINGS.
  
 4) OFFICE# 13 ENTRY DOOR MUST MEET:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 5)1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 6) 609.2.1 TYPE I & II CONSTRUCTION:
 WOOD BACKING TO BE FIRE RESISTANT TREAT-
 ED WOOD.
  
 7)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2004-03-03 Cont ID  
Sent By dpalmer Date 2004-03-03 Time 08:04 Rev Time 0.33
Received By dpalmer Date 2004-03-03 Time 08:04 Sent To  
Notes
2004-03-03 00:00:00*** UNSAT ****
  
 1)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%.
 215.3,230.42 ETC.
  
 PLEASE SEE PLUMB REVIEW COMMENTS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-01-09 Cont ID  
Sent By dpalmer Date 2004-01-09 Time 15:42 Rev Time 0.50
Received By dpalmer Date 2004-01-09 Time 15:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-01-07 Cont ID  
Sent By dpalmer Date 2004-01-07 Time 06:08 Rev Time 0.33
Received By dpalmer Date 2004-01-07 Time 06:08 Sent To  
Notes
2004-01-07 00:00:00*********** UNSAT ******************
  
 1)NOTE: PLEASE SEE THAT OLD/VOIDED SHEET
 -S WERE RESIGNED BY ENGINEER. THESE
 SHEETS HAVE BEEN MARKED OUT AND VOIDED,
 PLEASE BRING IN NEW SHEETS AND INSERT
 INTO SETS FOR STAMPING. THERE WAS NOT
 TWO COMPLETE SETS SUBMITTED FOR STAMPING
 FOR BLDG.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
 '
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-12-12 Cont ID  
Sent By dpalmer Date 2003-12-12 Time 15:23 Rev Time 0.33
Received By dpalmer Date 2003-12-12 Time 15:23 Sent To  
Notes
2003-12-12 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SEE COMMENT FROM PREVIOUS
 REVIEW. MUST CONTAIN A COMPLETE
 SIGNATURE CONTAINING A MIN OF FIRST AND
 LAST NAME AS DIRECTED BY THE FBPE'S.
 FS 471.025 AND FAC 61G15-23.002
 PLEASE SEE THAT ONE SET OF PLANS ARE
 BEING KEPT TO BE PLACED IN FILE.
 IF COMMENTS CONTINUE THEN WE WILL HAVE
 NO CHOICE BUT TO TURN FILE OVER TO THE
 FBPE'S.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANYQUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-11-05 Cont ID  
Sent By dpalmer Date 2003-10-28 Time 10:04 Rev Time 1.00
Received By dpalmer Date 2003-10-28 Time 10:04 Sent To  
Notes
2003-11-05 00:00:00*********** UNSAT *****************
  
 PLEASE NOTE; ELECTRICAL PLANS HAVE BEEN
 VOIDED AND CROSSED OUT.
  
 1)NOTE: PLANS MUST BE SIGNED BY THE
 ENGINEER OF RECORD. PER FS 471.025 AND
 FAC 61G15-23.002. INITIALED PLANS ARE
 NO LONGER ACCEPTABLE. PLANS/COMMENTS
 MAY BE TURNED IN TO THE FBPE'S FOR
 REVIEW IF REQUESTED. PLEASE SEE THAT
 WILL BE NOW KEEPING A RECORD/COPY OF
 ONE SHEET OR SET FOR TRACKING OF
 SIGNATURE AND OR INTERPERTAION/ REVIEW
 BY FBPE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2003-10-28 00:00:00PASSED, PENDING ANY COMMENTS FROM OTHER
 REVIEWS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2004-03-04 Cont ID  
Sent By nmccray Date 2004-03-04 Time 09:55 Rev Time 0.00
Received By nmccray Date 2004-03-04 Time 09:55 Sent To  
Notes
2004-03-04 00:00:00DENIED**********************************
 PLEASE SEE COMMENTS AND NOTES BY
 PLUMBING PLAN REVIEW.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-12-12 Cont ID  
Sent By mcarsill Date 2003-12-12 Time 14:34 Rev Time 0.00
Received By mcarsill Date 2003-12-12 Time 14:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-11-05 Cont ID  
Sent By nmccray Date 2003-11-05 Time 14:51 Rev Time 0.00
Received By nmccray Date 2003-11-05 Time 14:51 Sent To  
Notes
2003-11-05 00:00:00************DENIED**********************
  
 1) PLEASE SHOW EXISTING OR NEW EMERGENCY
 LIGHTS.
  
 2) ON SHEET FA0.1 NOTE #16 FIRE ALARM
 CIRCUITS AND DEVICES SHALL BE CLASS "A"
 STYLE "C". SHOULD AND SHALL BE FIRE
 ALARM CIRCUITS AND DEVICES SHALL BE
 CLASS "A" STYLE "D".
  
 3) ALSO PLEASE SEE COMMENTS FROM OTHER
 PLAN REVIEW PROFESSIONALS.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-02-25 Time 09:56 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 09:56 Sent To  
Notes
2004-02-25 00:00:00TO COMM BD#6

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-01-21 Cont ID  
Sent By csiegber Date 2004-01-21 Time 12:34 Rev Time 0.00
Received By csiegber Date 2004-01-21 Time 12:34 Sent To B
Notes
2004-01-21 00:00:00TO JW DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-12-30 Cont ID  
Sent By csiegber Date 2003-12-30 Time 13:36 Rev Time 0.00
Received By csiegber Date 2003-12-30 Time 13:36 Sent To  
Notes
2003-12-30 00:00:00TO COMM BD#51

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-12-03 Cont ID  
Sent By csiegber Date 2003-12-02 Time 16:36 Rev Time 0.00
Received By csiegber Date 2003-12-02 Time 16:36 Sent To  
Notes
2003-12-02 00:00:00TO COMM BD#11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-11-18 Cont ID  
Sent By pkrauss Date 2003-11-18 Time 07:01 Rev Time 0.00
Received By pkrauss Date 2003-10-21 Time 14:56 Sent To  
Notes
2003-10-21 00:00:00TO COMM BD#12

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-03-03 Cont ID  
Sent By pkrauss Date 2004-03-03 Time 16:12 Rev Time 0.40
Received By pkrauss Date 2004-03-03 Time 16:09 Sent To  
Notes
2004-03-03 00:00:00DENIED:
 SEE COMMENTS BY PLUMBING PLAN REVIEW,
 REFERENCE FS 471.025.PLANS ARE OTHER-
 WISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-01-07 Cont ID  
Sent By pkrauss Date 2004-01-07 Time 09:53 Rev Time 0.45
Received By pkrauss Date 2004-01-07 Time 09:36 Sent To  
Notes
2004-01-07 00:00:00PROVISO:
 FAN SHUTDOWN BY DUCT SMOKE DETECTORS ARE
 REQUIRED FOR SYSTEMS THAT SHARE A COMMON
 RETURN AIR PLENUM.PLEASE PROVIDE DUCT
 SMOKE DETECTORS FOR THE SUPPLY AND
 RETURN AIR SYSTEM, PER 2001 FBC(M)
 606.2.2.
  
 FAN SHUTDOWN REQUIRED AT FINAL
 INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-12-19 Cont ID  
Sent By pkrauss Date 2003-12-19 Time 12:32 Rev Time 0.45
Received By pkrauss Date 2003-12-19 Time 12:18 Sent To  
Notes
2003-12-19 00:00:00DENIED:
 ONLY ONE SET OF PLANS SUBMITTED PER
 2001 FBC 104.2.1, TWO OR MORE COPIES
 OF PLANS AND SPECIFICATIONS SHALL BE
 SUBMITTED FOR REVIEW.PLANS ARE OTHER-
 WISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-11-18 Cont ID  
Sent By pkrauss Date 2003-11-18 Time 06:56 Rev Time 0.35
Received By pkrauss Date 2003-11-18 Time 06:43 Sent To  
Notes
2003-11-18 00:00:00DENIED:
 PLEASE NOTE SIGNATURE REQUIRED BY THE
 ENGINEER OF RECORD AS PER FS 471.025 &
 FAC 61G15-23.002.
  
 MECHANICAL PLANS ARE OTHERWISE CODE
 COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 4 Status F Date 2004-02-28 Cont ID  
Sent By kstevens Date 2004-02-28 Time 08:39 Rev Time 1.00
Received By kstevens Date 2004-02-28 Time 08:38 Sent To  
Notes
2004-02-28 00:00:00REVISION DENIED
 REFERENCE: FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1) - FS 471.
 025.
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025 - INITIALS NOT ACCEPTABLE
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET.
  
 2) ONE SET OF REVISIONS WILL BE HELD FOR
 FILE FOR FBPE REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-01-14 Cont ID  
Sent By kstevens Date 2004-01-14 Time 18:07 Rev Time 0.25
Received By kstevens Date 2004-01-14 Time 18:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-12-17 Cont ID  
Sent By kstevens Date 2003-12-17 Time 09:01 Rev Time 0.33
Received By kstevens Date 2003-12-17 Time 08:59 Sent To  
Notes
2003-12-17 00:00:00DENIED
 REFERENCE: FLA. ADMIN. CODE
 FLA. STATUTES
  
 COMMENT #3 FROM PREVIOUS REVIEW HAS NOT
 BEEN ADDRESSED. A SIGNATURE IS REQUIRED
 ON THE ENGINEERS SEAL ALONG WITH THE
 DATE. FAC 61G15-23.002(1) & FS 471.025
 SIGNATURE REQUIRED PER FBPE & BLDG. OFF-
 ICIAL.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-11-05 Cont ID  
Sent By kstevens Date 2003-11-05 Time 11:24 Rev Time 1.00
Received By kstevens Date 2003-11-05 Time 11:24 Sent To  
Notes
2003-11-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT P2.1 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. THE FLOOR
 DRAIN IN ROOM #23 IS NOT SHOWN ON THE
 RISER DIAGRAM.
 2) SHT P3.1 WATER HAMMER ARRESTORS SHALL
 BE LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING.
 PDI-WH 201 AND MANUF. INSTALL. INSTRUCT.
 (SEE NOTE #13 PLUMBING NOTES SHT P0.1)
 3) A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME AND AFFIX HIS SEAL TO ALL PLANS
 PER 61G15-23.002(1) & FS471.025. A CALL
 TO THE FBPE CONFIRMED THAT A SIGNITURE
 IS REQUIRED.
 4) THE SHEETS FOR PLUMBING HAVE BEEN
 SEALED BY ONE ENGINEER AND SIGNED AND
 DATED BY ANOTHER ENGINEER.
 5) ONE SET OF PLANS SHALL BE RETAINED
 FOR OUR FILE FOR REVIEW BY THE FBPE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]