Plan Review Details - Permit 03101109
Plan Review Stops For Permit 03101109
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-12-11 Cont ID  
Sent By csiegber Date 2003-12-11 Time 15:18 Rev Time 0.00
Received By csiegber Date 2003-12-11 Time 15:18 Sent To M
Notes
2003-12-11 00:00:00TO PK BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-10-17 Cont ID  
Sent By csiegber Date 2003-10-17 Time 16:08 Rev Time 0.00
Received By csiegber Date 2003-10-17 Time 16:08 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-12-18 Cont ID  
Sent By pkrauss Date 2003-12-18 Time 15:22 Rev Time 0.33
Received By pkrauss Date 2003-12-18 Time 15:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-10-22 Cont ID  
Sent By csiegber Date 2003-12-11 Time 15:18 Rev Time 0.33
Received By pkrauss Date 2003-10-22 Time 12:38 Sent To  
Notes
2003-10-22 00:00:00DENIED:
 RETURN AIR REQUIRED FROM BEDROOM AREAS.
 PLEASE SIZE RETURN AIR TO COMPLY WITH
 REVISION TO THE 2001 FBC(M) 601.4,
 EFFECTIVE JUNE 30,2003:
  
 BALANCED AIR RETURN - RETURN/TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM ITS SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.