Plan Review Details - Permit 03100957
Plan Review Stops For Permit 03100957
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-10-21 Cont ID  
Sent By pkrauss Date 2003-10-21 Time 11:22 Rev Time 0.00
Received By nmccray Date 2003-10-21 Time 11:34 Sent To  
Notes
2003-10-21 00:00:00*************PROVISO********************
 DUCT SMOKE DETECTORS SHALL INITIATE AN
 ALARM SIGNAL.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-10-17 Cont ID  
Sent By csiegber Date 2003-10-17 Time 13:38 Rev Time 0.00
Received By csiegber Date 2003-10-17 Time 13:38 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-10-21 Cont ID  
Sent By csiegber Date 2003-10-17 Time 13:38 Rev Time 0.40
Received By pkrauss Date 2003-10-21 Time 11:01 Sent To FIRE
Notes
2003-10-21 00:00:00PROVISO:
 AS PER 2001 FBC(M) 606.2.1, DUCT SMOKE
 DETECTORS SHALL BE INSTALLED IN THE
 SUPPLY AIR DUCT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.