| 2003-11-14 00:00:00 | UNSAT |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) SUBMIT A SIGNED AND SEALED COPY OF |
| | THE SOIL TEST. PLEASE UPDATE THE COVER |
| | PAGE TO REFERENCE THE 2001 FLORIDA |
| | BUILDING CODE. |
| | |
| | 3) UPDATE THE FOUNDATION NOTES ON A1 TO |
| | REFERENCE THE ACI AND TMS 2002 EDITIONS |
| | AS REFERENCED IN FBC CHAPTER 35. |
| | |
| | 4) SOMEONE HAS USED WHITEOUT TO CHANGE |
| | THE DIMENSIONS FOR THE CHANGE IN BEAM |
| | HEIGHT ON SHEET A2. THE ELEVATIONS HAVE |
| | NOT BEEN REVISED TO REFLECT THE CHANGE. |
| | ALL CHANGES TO THE DRAWINGS MUST BE DONE |
| | BY THE DESIGNER OF RECORD. |
| | |
| | 5) SPECIFY SAFETY GLAZING FOR THE |
| | WINDOWS AT THE MASTER BATH WHIRLPOOL TUB |
| | AS REQUIRED BY FBC 2405.2. |
| | |
| | 6)FL BLDG 1909.3 (EXEPTION# 2) |
| | CONCRETE SLABS ON GRADE CONTAINING 6X6/ |
| | W1.4XW1.4 WELDED WIRE REINFORCEMENT |
| | FABRIC LOCATED IN THE MIDDLE TO THE |
| | UPPER 1/3RD OF THE SLAB SHALL BE SUP- |
| | PORTED BY APPROVED MATERIALS OR SUPPORTS |
| | AT SPACING NOT TO EXCEED 3 FT OR IN |
| | ACCORDANCE WITH MANUFACTURER'S SPEC. |
| | |
| | 7)1609.4.3 LOAD REDUCTION. |
| | WHEN STRUCTURAL EFFECTS DUE TO TWO OR |
| | MORE LOADS IN COMBINATION WITH DEAD LOAD |
| | ARE INVESTIGATED IN LOAD COMBINATIONS OF |
| | 1609.4.1 OR 1609.4.2, THE COMBINED |
| | EFFECTS DUE TO THE TWO OR LOADS MULTI- |
| | PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD |
| | LOADS SHALL NOT BE LESS THAN THE EFFECTS |
| | FROM THE LOAD COMBINATION OF THE DEAD |
| | LOAD PLUS THE LOAD PRODUCING THE LARGEST |
| | EFFECTS. INCREAS IN ALLOWABLE STRESS SPE |
| | CIFIED IN THE MATERIALS SECTIONS OF THIS |
| | CODE OR A REFRENCED STANDARD SHALL NOT |
| | BE USED WITH THESE LOAD COMBINATIONS |
| | EXCEPT THAT A DURATION OF LOAD INCREASE |
| | SHALL BE PERMITTED IN ACCORDANCE WITH |
| | CHAPTER 23. |
| | REVISE THE ANCHOR LEGEND ON A5. SEE THE |
| | NOTES ON PLAN AND THE 2003 USP CATALOG. |
| | |
| | 8) ON DETAIL 6 ON A5 SPECIFY THE TYPE, |
| | SIZE, LENGTH/EMBED DEPTH OF THE THREE |
| | FASTENERS SHOWN THROUGH THE GIRDER. |
| | |
| | 9) UPDATE THE HUGHES CONNECTOR SPECIFIED |
| | IN DETAIL 7 ON A5. HUGHES IS NO LONGER |
| | IN BUSINESS. |
| | |
| | 10) REVISE DETAIL 7 ON A5 THERE APPEARS |
| | TO BE A CONFLICT BETWEEN NOTE #6 AND THE |
| | 3/4" BOLTS SPECIFIED ON THE DRAWING. |
| | |
| | 11) ON SHEET A5 THE STEEL COLUMN HEIGHT |
| | WAS WHITED OUT AND CHANGED. CHANGES |
| | MUST BE MADE BY THE DESIGNER OF RECORD. |
| | PLEASE CORRECT. |
| | |
| | 12) THE WALL SECTIONS (1 & 2) ON A7 |
| | LIST INCORRECT FASTENER SPACING FOR THE |
| | ROOF SHEATHING. PLEASE CORRECT. SEE CITY |
| | AMENDMENTS TO FBC TABLE 2306.1. |
| | |
| | 13) CLARIFY THE WIRE LATH NAILING |
| | SPECIFIED IN THE NAILING SCHEDULE ON A8. |
| | ASTM C 1063 REQUIRES 3/8" RIB LATH TO BE |
| | FASTENED AT EVERY RIB (4"O.C.) AND |
| | FASTENERS ARE REQUIRED TO PENETRATE |
| | 1-3/4" INTO FRAMING MEMBERS WHEN APPLIED |
| | HORIZONTALLY. |
| | |
| | 14) INDICATE THE POSITIVE AND NEGATIVE |
| | WINDLOADS FOR THE SPAN AND OPENING SIZE |
| | FOR THE MULLION IN DETAIL 8 ON A8. |
| | |
| | 15) PRODUCT APPROVALS SUBMITTED AFTER |
| | OCTOBER 1, 2003 ARE REQUIRED TO COMPLY |
| | WITH THE STATE OF FLORIDA PRODUCT |
| | APPROVAL SYSTEM. FOR INFORMATION SEE THE |
| | STATE WEBSITE AT WWW.FLORIDABUILDING.ORG |
| | PRODUCTS WITH STATE APPROVAL ARE |
| | REQUIRED TO BE SUBMITTED WITH A COVER |
| | SHEET WHICH LISTS THE PRODUCT IDENTITY |
| | NUMBER FROM THE STATE. IF THE PRODUCT DO |
| | ES NOT HAVE STATEWIDE PRODUCT APPROVAL, |
| | SUBMIT AN APPLICATION FOR LOCAL PRODUCT |
| | APPROVAL PER RULE 9B-72. SEE ATTACHMENT. |
| | |
| | 16) THE PRODUCT APPROVAL FOR THE THERMA- |
| | TRU OUTSWING GLAZED STEEL DOOR IS |
| | ILLEGIBLE AND INCOMPLETE. |
| | |
| | 17) THE PRODUCT APPROVALS ARE FOR |
| | IMPACT WINDOWS AND DOORS, HOWEVER, THE |
| | STORM PANEL INFORMATION AND PLANS |
| | INDICATE THAT ALL GLAZING IS TO BE |
| | SHUTTERED. PLEASE CLARIFY. |
| | |
| | 18)FBC 1005.4.5 (GLITCH AMENDMENTS |
| | JULY 1, 2003) REQUIRES AT LEAST ONE |
| | MEANS OF ESCAPE FROM A DWELLING WHEN |
| | SHUTTERED FOR IMPACT PROTECTION. THE |
| | MEANS OF ESCAPE SHALL BE WITHIN THE |
| | FIRST FLOOR OF THE DWELLING AND CAN NOT |
| | BE LOCATED IN A GARAGE. OCCUPANTS IN ANY |
| | PART OF THE DWELLING SHALL HAVE ACCESS |
| | TO IT WITHOUT HAVING TO PASS THROUGH A |
| | LOCKABLE DOOR NOT UNDER THEIR CONTROL. |
| | INDICATE HOW COMPLIANCE WILL BE |
| | ACHIEVED. |
| | |
| | 19) THE PRODUCT APPROVAL FOR THE WINDOW |
| | WALL SYSTEM IS MISSING SHEET 3 OF THE |
| | DRAWINGS. PLEASE INDICATE WHERE THIS |
| | SYSTEM IS BEING INSTALLED IN THE |
| | STRUCTURE. |
| | |
| | 20) PLEASE CLARIFY THE STORE DOORS THAT |
| | ARE LISTED IN THE DOOR SCHEDULE ON A2. |
| | ARE THESE THE FRENCH DOORS WITH SIDELITE |
| | OR ARE THEY COMMERCIAL STOREFRONT DOORS? |
| | |
| | 21) SUBMIT PRODUCT APPROVALS FOR FRENCH |
| | DOORS WITHOUT SIDELITES. |
| | |
| | 22) THE PRODUCT APPROVALS SUBMITTED FOR |
| | THE MULLIONS ARE NOT ACCEPTABLE FOR USE |
| | BETWEEN THE FRENCH DOORS W/SIDELITES |
| | AND THE TRANSOM WINDOWS ABOVE. A LINTEL, |
| | STEEL OR CONC. BEAM MAY BE REQUIRED. |
| | |
| | 23) SUBMIT PRODUCT APPROVALS OR ENGINEER |
| | ING FOR THE BUTT GLASS ASSEMBLY. SUBMIT |
| | CALCULATIONS, TESTING, ETC. |
| | |
| | 24) PLEASE REMOVE PRODUCT APPROVALS FOR |
| | COMPONENTS THAT WILL NOT BE USED IN THIS |
| | STRUCTURE. (GLASS BLK.,SGD,CASEMENT |
| | WINDOWS) |
| | |
| | 25) TRUSS DRAWINGS ARE NOT REQUIRED TO |
| | BE SUBMITTED FOR REVIEW FOR ONE & TWO |
| | FAMILY DWELLINGS. THEY ARE TO BE GIVEN |
| | TO THE FIELD INSOECTOR AT TIME OF TRUSS |
| | INSPECTION. THE LAYOUT HAS THE WRONG |
| | WIND SPEED OF 110 MPH. IT IS REQIRED TO |
| | BE SIGNED BY THE DESIGNER OF RECORD FOR |
| | THE STRUCTURE AS HAVING BEEN REVIEWED & |
| | APPROVED. THE COVER SHEET FOR THE TRUSS |
| | DRAWINGS DOES NOT HAVE THE ORIGINAL WET |
| | SIGNATURE OF THE TRUSS ENGINEER. THE |
| | INFORMATION IS WRITTEN IN PENCIL AND NOT |
| | INK. THE BOTTOM CORD LIVE LOAD IS |
| | REQUIRED TO BE 10 PSF BY FBC TABLE |
| | 1604.1. PLEASE MAKE CORRECTIONS NOTED. |
| | |
| | IF YOU HAVE ANY QUESTIONS CALL: |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |